Measuring and dosing systems

Redox

The system continuously measures the Redox potential (ORP) of the water, expressed in mV, which indicates its disinfecting power, and drives the dosing pump for hypochlorite or another disinfectant in proportion to the measured value, up to the set point. It is based on an indirect measurement and is the most economical solution for linking disinfectant dosing to a continuous measurement.

  • Redox potential in mV
  • Proportional disinfectant dosing
  • High-linearity electrode for drinking water
LDsRh system pre-assembled on a panel with dosing pumps and filters
SystemRedox potential
ERhHLB SN6 high-linearity Redox electrode
Redox electrode
How it works

Disinfection control by means of Redox

The Redox potential to be maintained in the water is set (set point, for example 450 mV) and the system automatically doses the quantity of disinfectant required to reach and maintain it.

Learn more: the Redox potential →
Diagram of the LDsRh system on a water storage tank: controller, Redox electrode, chemical injection with the LINI injection lance, hypochlorite tank and booster pump
1

Continuous measurement

The Redox electrode continuously detects the potential of the water in the storage tank or in the pipe.

2

Proportional dosing

The controller drives one or more dosing pumps, which inject hypochlorite into the tank in proportion to the deviation of the measured potential from the set point.

3

Continuous disinfection

The incoming water, potentially contaminated by pathogenic organisms, immediately comes into contact with the free chlorine present and is disinfected, while the pump restores the set potential.

The action of chlorine requires a contact time appropriate to the organisms present, and in any case not less than 20 minutes, between the injection point and the first draw-off. By adding a pulse-output water meter and a dosing pump connected to it, dosing also becomes proportional to the volume of water treated; the controller can also drive solenoid valves or other equipment according to the measured Redox potential.

Components

Basic components

The system is supplied pre-assembled on a panel and consists of the measuring controller, the Redox electrode, the disinfectant dosing pump and the injection accessories. As an alternative to the wall-mounted controller, panel-mount controllers for installation in an electrical cabinet are available.

LDsRh controller

LDsRh controller

It acquires the mV measured by the electrode and drives the dosing pump until the set point is reached.

LDsRh controller →
ERhHLB SN6 high-linearity Redox electrode

Redox electrode

Combined electrode, also available in a high-linearity, high-sensitivity version, designed to detect the very low free chlorine concentrations typical of drinking water.

Redox electrodes →
KMS MF multifunction dosing pump

Dosing pump

Solenoid diaphragm pump of the VMS or KMS series, up to 18 l/h and 20 bar, with wetted parts in PVDF or PP according to the chemical dosed; for larger volumes, stepper motor or motor-driven pumps are used, up to 1,000 l/h or up to 100 bar.

Dosing pumps →
Injection lance

Injection lance

It introduces the disinfectant into the centre of the pipe, improving its mixing with the water; it can be withdrawn with the pipe under pressure.

Lances →
Installation

Probe positioning

Probe positioning is defined according to the characteristics of the installation and of the water to be analysed.

PEF flow-through probe holder and NPED probe holder

In a bypass line

The probes are housed in a PEF flow-through probe holder or an NPED probe holder, connected to a sampling point at the tank outlet and fed with about 30 l/h of sample water. A flow sensor can be added, which stops dosing when there is no flow.

Probe holders →
Immersion probe holder

Immersion

The electrode is immersed directly in the storage tank of the water to be treated, by means of an immersion probe holder.

Probe holders →
Immersion probe holder with cleaning nozzle

Immersion with cleaning

A solution suited to water with a high solids load: at programmed intervals the control panel puts the controller in stand-by and opens a solenoid valve that sends water or air to the nozzle; once cleaning is complete, it closes the valve and, after the electrode repolarisation time has elapsed, resumes dosing.

Probe holders →
In-line probe holder

In-line

The electrodes are inserted directly into the pipe carrying the water to be treated.

Probe holders →
Redox measurement

Factors affecting the Redox potential

Chlorine, bromine, hydrogen peroxide, peracetic acid and ozone oxidise organic contaminants, such as bacteria and algae. The Redox potential is positive in the presence of oxidants, such as chlorine, and negative in the presence of reducing substances, such as sodium bisulphite.

pH

The Redox potential depends directly on pH and, to a lesser extent, on temperature: as the pH increases, the effectiveness of the oxidant decreases and a larger quantity of disinfectant is required to reach the same potential. In certain circumstances the pH must therefore also be controlled.

pH system →

Pollutant load

With few oxidisable impurities (microorganisms, organic matter, iron, copper, manganese), a small quantity of disinfectant is sufficient to obtain a high potential. As the pollutant load increases, the potential decreases and the system increases dosing to restore it.

Setting and checking

The set point is determined by bringing the pH to the optimum value, measuring the free chlorine with the colorimetric kit and reading the corresponding Redox potential. The correspondence between mV and free chlorine must be checked periodically with the colorimetric test.

Direct measurement in mg/l

The Redox measurement does not compensate for pH variations or for the effect of chemicals that may alter it. For the direct measurement of free chlorine in mg/l, with automatic pH compensation, the LDsCL amperometric controller is used.

LDsCL controller →
Applications

Applications

The system is used wherever the disinfecting power of the water must be kept constant with a simple and economical solution.

Private swimming pools

Private swimming pools

In swimming pools the Redox potential is measured together with the pH, with two-channel controllers that adjust the pH first and then the disinfectant.

Private swimming pool systems →
Domestic water circuits

Domestic water circuits

In domestic water circuits the system maintains the set Redox potential as consumption varies.

Optional extras

Optional accessories

Accessories available on request to adapt the system to the requirements of the installation.

Tank

Tank

PE tanks for the chemical, with safety bund.

Details →
Pulse-output water meter

Pulse-output water meter

Enables dosing proportional to the volume of water actually treated.

Details →
Flow sensor

Flow sensor

Installed on the pump delivery line, it verifies that dosing actually takes place.

Details →
Static mixer

Static mixer

Ensures the chemical is mixed with the water and protects the pipe from direct contact with it.

Details →
Pulsation dampener

Pulsation dampener

Attenuates the pulsations generated by the dosing pump.

Details →
Injection lance

Injection lance

Injects the chemical into the centre of the pipe.

Details →
Multifunction valve

Multifunction valve

Pressure, safety and anti-siphon functions combined in a single valve.

Details →
Solenoid valve

Solenoid valve

Operated by the controller according to the measured value.

The controller

The LDsRh controller

LDsRh controller

LDsRh

Measuring range, resolution, BASIC and PLUS versions, dosing modes, inputs, outputs and connections are given in the controller data sheet; the characteristics of the electrodes are given on the Redox electrodes page.

Which one to choose

From the simplest to the most complete solution

For chlorine and other disinfectants the basic solution is the dosing station; to dose according to the concentration actually present in the water, measuring controllers are used.

Dosing station on a tank

Dosing station

The simplest solution: the pump doses at a constant rate or in proportion to the volume of water measured by the pulse-output water meter.

Details →
LDsRh system on a panel

LDsRh

Dosing based on the Redox potential of the water: an economical solution, based on an indirect measurement.

Details →
LDsCL system on a panel

LDsCL

The amperometric cell directly measures the disinfectant concentration in mg/l, ensuring maximum dosing accuracy.

Details →
Two-channel LD system on a panel

LD Dual Parameter

Simultaneous management of two parameters, for example pH and chlorine, with a single controller.

Details →
Centurio PRO on a panel

Centurio PRO

Management of up to 10 parameters and of all the pumps in the installation, with touch screen and remote control as standard.

Details →
Remote control

System remote control

The controllers support two-way remote access (read and write) through the web portal from a PC, tablet or smartphone: measurements can be viewed, set points, dosing and alarms changed, alarms received and logs downloaded. Alternatively, they can be integrated into your PLC via Modbus.

Ethernet

Connection to the web portal via network cable: measurements, set points, dosing and alarms accessible from a PC, tablet or smartphone.

Optional (one only)

Wi-Fi

Wireless connection to the web portal, with the same functions as the cable connection.

Optional (one only)

4G

Connection via the 4G network for installations without a local network, with alarm notification by SMS or e-mail.

Optional (one only)
NIMBUS web portal for remote control of the systemsWeb portalPC, tablet and smartphone

Modbus RTU

Integration into your PLC via serial port.

Standard (BASIC), optional (PLUS)

0-4/20 mA current loop output

Current signal proportional to the measured value, for remote monitoring or for controlling pumps and other instrumentation.

3 standard (PLUS), 2 on request (BASIC)

USB port

Download of the logged data to a USB memory stick, for archiving and analysis with a spreadsheet.

Optional

One communication type at a time: Ethernet, Wi-Fi, 4G or Modbus RTU (built into the BASIC versions, optional on the PLUS versions). 0-4/20 mA current loop outputs standard on the PLUS versions, optional on the BASIC versions; meter input on the PLUS versions only.

The NIMBUS portal

A single account brings together all registered installations, each with its own devices: the web portal, free of charge and with no subscription, can be accessed from a PC, Mac, tablet or smartphone and allows every parameter to be both viewed and changed, with an encrypted connection and protected access.

The NIMBUS portal on monitor, laptop, tablet and smartphone

Overview

On a single screen: probe readings, chemical levels, pump activation thresholds and active alarms, with the status of installations and devices (normal, warning, alarm, standby, not connected).

Installation map

Installations appear on an interactive map with their status and open with a click; for each one, the local weather conditions and temperature are also shown.

History and charts

Archive of measurements and alarms, available for consultation at any time with charts and numerical reports exportable in Excel format.

Alarms and notifications

Alarm thresholds for readings, dosing, faulty probe and out-of-range readings, with notification by e-mail or SMS depending on the communication system; a warning is also issued when an installation remains disconnected beyond the set time.

Set points and dosing

Remote modification of the set points, of the dosing pump activation thresholds and of the corresponding hourly flow rate.

Inputs and outputs

Status of relays, pulse outputs, digital inputs and current outputs, with the name assigned to each connection.

Maintenance calendar

Tasks are scheduled by installation or by device and assigned to technicians; a reminder is sent by e-mail two days before the due date. Each task is shown as scheduled, due, overdue or completed.

Team and permissions

The main account has full access and creates the technicians’ accounts, each enabled only for the assigned installations and devices; the last login and activity of each technician are visible.

Reports and activity log

Reports on devices, tasks and technicians, downloadable in PDF or CSV with the customer’s logo; the log keeps the history of operations and disconnections.

Customisation

Logo, main colour and light or dark theme; the tiles on the main screen can be rearranged by dragging them. Two installations can be displayed side by side for comparison.

Guided registration

Each device is added through a guided procedure: the model is recognised automatically and associated with the installation, together with the technician to be contacted.

PLC integration

As an alternative to the portal, the Modbus RTU port allows integration into the plant supervision system.

NIMBUS portal: Real-time readings, counters and timers
Real-time readings, counters and timers
NIMBUS portal: Free chlorine and temperature trends
Free chlorine and temperature trends
NIMBUS portal: Set point and operating mode of each channel
Set point and operating mode of each channel
NIMBUS portal: Status of relays, pulses, inputs and mA outputs
Status of relays, pulses, inputs and mA outputs

Technical advice

Tell us the type of water to be treated, the volumes and the disinfectant used: we will propose the most suitable electrode, probe holder, pump and accessories.

Contact

Tell us about your plant

Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.

What do you need?
Please enter your name.
Please enter a valid email address.
Please enter your message.

Describe your plant: type, water volume or flow rate, parameters to be controlled.

You must accept the privacy notice to continue.