Dissolved oxygen
The optical probe measures the dissolved oxygen in the contact tank.
In wastewater treatment plants a single Centurio PRO measures dissolved oxygen, pH, Redox, level, flow rate and turbidity and manages the dosing, timed or proportional to the flow rate, of flocculant, caustic soda, nutrients, acid, antifoam and chlorine.
How the plant works, one step at a time: a single controller for the measurements in the contact tank and in the treated water and for all the dosing pumps.
The optical probe measures the dissolved oxygen in the contact tank.
The pH electrode controls the caustic soda and acid pumps, which maintain the pH at the set value.
The Centurio PRO controls the dosing, timed or proportional to the flow rate, of flocculant, nutrients and antifoam.
The 0-4/20 mA current loop level probe measures the level in the treated water storage tank.
The Redox electrode in the treated water storage tank controls the chlorine pump.
The pulse-output water meter measures the water discharged to the receiving water body.
The bypass turbidity meter on the line to the receiving water body measures turbidity; the three-way valve on the bypass outlet diverts the turbid sample to drain.
The complete plant, managed by a single Centurio PRO.
Multi-channel controller with touch screen: up to 10 measuring channels and control of all the dosing pumps in the plant.
Centurio PRO →
Optical fluorescence probe: the measurement does not consume oxygen and is possible even in still water.
The probe →
The pH electrode in the contact tank controls caustic soda and acid; the Redox electrode in the treated water storage tank controls chlorine.
Turbidity probe in a bypass line on the line to the receiving water body, with drain valve for cleaning.
Turbidity →
Turbine or Woltmann type, on the line to the receiving water body: it measures the treated water leaving the plant.
Water meters →
Solenoid dosing pumps with adjustable flow rate, driven by the Centurio PRO: one for each product.
Dosing pumps →In the contact tank the Centurio PRO measures dissolved oxygen and pH and controls the caustic soda and acid pumps, which maintain the pH at the set value.
Flocculant, nutrients and antifoam are dosed on a timed basis or in proportion to the flow rate.
In the treated water storage tank the controller measures level and Redox and doses chlorine according to the measured value.
The water meter measures the water discharged to the receiving water body and the bypass turbidity meter checks its turbidity, diverting the turbid sample to drain.
Controller, pumps, probe holder and accessories are supplied pre-assembled on a panel, in a box or on a skid, with configurable dimensions.
The controller, the pumps and the product tanks are housed in a cabinet.
The controller and the pumps are wall-mounted on a panel, with the product tanks on the floor.
| EOLUM | |
|---|---|
| Measuring range | 0 – 20 mg/l |
| Resolution | 0.01 |
| Measuring system | Fluorescence |
| Automatic compensation | Temperature and pressure |
| Operating temperature | −5 / +50 °C |
| Operating pressure | 10 bar |
| Body | Stainless steel |
| Electrode | Pressure | Connection | Body | Minimum conductivity | Junction | Temperature | Cable | Diameter | Notes |
|---|---|---|---|---|---|---|---|---|---|
| EpHS | 7 bar (3.5 bar) | BNC | Epoxy | 100 µS | – | 70 °C (80 °C) | 0.8 m | 12 mm | – |
| EpHM | 7 bar (3.5 bar) | BNC | Epoxy | 100 µS | – | 70 °C (80 °C) | 4.5 m | 12 mm | – |
| EpHL | 7 bar (3.5 bar) | BNC | Epoxy | 100 µS | – | 70 °C (80 °C) | 15 m | 12 mm | – |
| EpHSN6 | 7 bar (3.5 bar) | SN6 with PG13.5 thread | Epoxy | 100 µS | – | 70 °C (80 °C) | 1 – 100 m | 12 mm | – |
| EpHMD/100 | 7 bar | BNC | Epoxy | 100 µS | Double | 100 °C | 4.5 m | 12 mm | – |
| EpHM/D | 7 bar (3.5 bar) | BNC | Epoxy | 100 µS | Double | 70 °C (80 °C) | 4.5 m | 12 mm | – |
| EpHM/D/SN6 | 7 bar (3.5 bar) | SN6 with PG13.5 thread | Epoxy | 100 µS | Double | 70 °C (80 °C) | 1 – 100 m | 12 mm | – |
| EpHMD/LI | 7 bar (3.5 bar) | SN6 with PG13.5 thread | Epoxy | 3 µS | Double | 70 °C (80 °C) | 1 – 100 m | 12 mm | For low-conductivity water |
| EpHSC | 7 bar (3.5 bar) | BNC | Epoxy | 100 µS | Double | 70 °C (80 °C) | 4.5 m | 12 mm | Self-cleaning |
| EpHSC/SN6 | 7 bar (3.5 bar) | SN6 with PG13.5 thread | Epoxy | 100 µS | Double | 70 °C (80 °C) | 1 – 100 m | 12 mm | Self-cleaning |
| EpHM/HF | 7 bar (3.5 bar) | BNC | Epoxy | 100 µS | Double | 70 °C (80 °C) | 4.5 m | 12 mm | Resistant to 1% hydrofluoric acid |
| EpHSN6 GK | 10 bar | SN6 | Glass | 150 µS | – | −5 / 135 °C | 1 – 100 m | 12 mm | High temperature |
All models: combination electrode, range 0 – 14 pH, resolution 0.01.
| Electrode | Range | Pressure | Connection | Body | Minimum conductivity | Junction | Temperature | Cable | Diameter | Notes |
|---|---|---|---|---|---|---|---|---|---|---|
| ERhS | ± 1,000 mV | 7 bar (3.5 bar) | BNC | Epoxy | 100 µS | – | 70 °C (80 °C) | 0.8 m | 12 mm | – |
| ERhM | ± 1,000 mV | 7 bar (3.5 bar) | BNC | Epoxy | 100 µS | – | 70 °C (80 °C) | 4.5 m | 12 mm | – |
| ERhL | ± 1,000 mV | 7 bar (3.5 bar) | BNC | Epoxy | 100 µS | – | 70 °C (80 °C) | 15 m | 12 mm | – |
| ERhHLB SN6 | ± 1,500 mV | 6 bar | SN6 with PG13.5 thread | Glass | 100 µS | – | 80 °C | 10 m | 12 mm | High linearity and sensitivity, for low chlorine concentrations |
| ERhSN6 | ± 1,000 mV | 7 bar | SN6 with PG13.5 thread | Epoxy | 100 µS | – | 100 °C | 1 – 100 m | 12 mm | – |
| ERhMD/100 | ± 1,000 mV | 7 bar | BNC | Epoxy | 100 µS | Double | 100 °C | 4.5 m | 12 mm | – |
| ERhM/D | ± 1,000 mV | 7 bar (3.5 bar) | BNC | Epoxy | 100 µS | Double | 70 °C (80 °C) | 4.5 m | 12 mm | – |
| ERhSC | ± 1,000 mV | 7 bar (3.5 bar) | BNC | Epoxy | 100 µS | Double | 70 °C (80 °C) | 4.5 m | 12 mm | Self-cleaning |
| ERhSC/SN6 | ± 1,000 mV | 7 bar (3.5 bar) | SN6 with PG13.5 thread | Epoxy | 100 µS | Double | 70 °C (80 °C) | 1 – 100 m | 12 mm | Self-cleaning |
All models: combination electrode, resolution 1 mV.
| ETORB2 | |
|---|---|
| Measuring range | 0/40 NTU – 0/400 NTU – 0/4,000 NTU |
| Measurement error | ± 5% of reading |
| Measuring system | NIR scattered light at 90°, nephelometric principle |
| Body | PVC |
| Optical window | Sapphire glass |
| Automatic compensation | Temperature |
| Self-cleaning | ●(water jet, max 1 bar) |
| Operating temperature | 0 – 40 °C |
| Operating pressure | 2 bar |
The controllers support two-way remote access (read and write) through the web portal from a PC, tablet or smartphone: measurements can be viewed, set points, dosing and alarms changed, alarms received and logs downloaded. Alternatively, they can be integrated into your PLC via Modbus.
Connection to the web portal via network cable: measurements, set points, dosing and alarms accessible from a PC, tablet or smartphone.
Wireless connection to the web portal, with the same functions as the cable connection.
Download of the logged data to a USB memory stick, for archiving and analysis with a spreadsheet.
Web portalPC, tablet and smartphone
Integration into your PLC via serial port.
Integration into your PLC or SCADA via Ethernet network.
Current signal proportional to the measured value, for remote monitoring or for controlling pumps and other instrumentation.
Connection via the 4G network for installations without a local network, with alarm notification by SMS or e-mail.
Ethernet, Wi-Fi, USB, Modbus RTU, Modbus TCP/IP and 0-4/20 mA current loop outputs as standard; 4G modem optional.
A single account brings together all registered installations, each with its own devices: the web portal, free of charge and with no subscription, can be accessed from a PC, Mac, tablet or smartphone and allows every parameter to be both viewed and changed, with an encrypted connection and protected access.
On a single screen: probe readings, chemical levels, pump activation thresholds and active alarms, with the status of installations and devices (normal, warning, alarm, standby, not connected).
Installations appear on an interactive map with their status and open with a click; for each one, the local weather conditions and temperature are also shown.
Archive of measurements and alarms, available for consultation at any time with charts and numerical reports exportable in Excel format.
Alarm thresholds for readings, dosing, faulty probe and out-of-range readings, with notification by e-mail or SMS depending on the communication system; a warning is also issued when an installation remains disconnected beyond the set time.
Remote modification of the set points, of the dosing pump activation thresholds and of the corresponding hourly flow rate.
Status of relays, pulse outputs, digital inputs and current outputs, with the name assigned to each connection.
Tasks are scheduled by installation or by device and assigned to technicians; a reminder is sent by e-mail two days before the due date. Each task is shown as scheduled, due, overdue or completed.
The main account has full access and creates the technicians’ accounts, each enabled only for the assigned installations and devices; the last login and activity of each technician are visible.
Reports on devices, tasks and technicians, downloadable in PDF or CSV with the customer’s logo; the log keeps the history of operations and disconnections.
Logo, main colour and light or dark theme; the tiles on the main screen can be rearranged by dragging them. Two installations can be displayed side by side for comparison.
Each device is added through a guided procedure: the model is recognised automatically and associated with the installation, together with the technician to be contacted.
As an alternative to the portal, the Modbus RTU or TCP/IP port allows integration into the plant supervision system.
Describe the wastewater treatment plant, the tanks and the products to be dosed: we will size controller, probes, pumps and accessories and supply the system assembled on a panel, in a box or on a skid.
Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.