Continuous measurement
The probe continuously detects conductivity, in the µS or mS range depending on the model, and the controller automatically compensates for the effect of temperature, measured with a PT100 probe.
The system continuously measures the conductivity of the water, which depends on the amount of dissolved salts, and according to the set values (set points) starts or stops the dosing of chemical products or controls the opening and closing of the inlet and drain solenoid valves.
The probe, immersed in the storage tank or installed on the pipe, sends the conductivity of the water to the controller; the controller compares it with the set values and drives the dosing pumps, solenoid valves or other equipment connected to its outputs accordingly.

The probe continuously detects conductivity, in the µS or mS range depending on the model, and the controller automatically compensates for the effect of temperature, measured with a PT100 probe.
The output is activated when the ON set point is exceeded and deactivated when the OFF set point is reached; when conductivity returns to the ON set point, the output is activated again.
The dosing pumps dose the chemical products according to the measured conductivity, while solenoid valves or motorised valves manage the inlet and drain of the water.
For example, with the ON set point at 2.00 mS and the OFF set point at 1.50 mS, the output is activated when conductivity exceeds 2.00 mS and remains active until it falls to 1.50 mS.
The system consists of the measuring controller, the conductivity probe and the controlled equipment: dosing pumps for the chemical products, solenoid valves or motorised valves for the inlet and drain of the water. It can be supplied pre-assembled on a panel, ready for connection.
It acquires the measurement from the probe and drives dosing pumps, solenoid valves or other equipment according to the detected value.
LDsCD controller →
Contacting or inductive, it is selected according to the measuring range and the characteristics of the water to be analysed.
Electromagnetic diaphragm pump, with flow rate and back pressure defined when ordering, driven by the controller.
Dosing pumps →
Operated by the controller according to the measured conductivity, it opens and closes the water inlet or drain.
The probe is selected according to the required measuring range and the quality of the water: contacting probes have graphite, stainless steel or platinum electrodes; the inductive probe has no electrodes in contact with the water and is unaffected by polarisation and deposits.
Four series are available: PVDF body with stainless steel electrodes (0 – 200 µS or 0 – 5 mS) or graphite electrodes (0 – 20 or 0 – 200 mS), stainless steel body and electrodes for immersion and high temperatures, epoxy body with high-linearity platinum electrodes.
Contacting probes →
It provides a particularly stable and accurate reading, measures even in still water up to 300 mS and is also suitable for hot water, high-pressure water and water containing suspended solids. It must be installed with the flow directed at the end of the probe.
Inductive probes →Probe positioning is defined according to the characteristics of the installation and of the water to be analysed.
The probes are housed in a PEF flow-through probe holder or an NPED probe holder, connected to a sampling point at the tank outlet and fed with about 30 l/h of sample water. A flow sensor can be added, which stops dosing when there is no flow.
Probe holders →
The electrode is immersed directly in the storage tank of the water to be treated, by means of an immersion probe holder.
Probe holders →
The electrodes are inserted directly into the pipe carrying the water to be treated.
Probe holders →A reliable reading requires the flow to strike the end of the probe: air bubbles and sediment deposits alter the measurement and, consequently, the control of the pumps and valves.
The flow is directed at the end of the probe.
The probe is on a vertical section, with upward flow.
Impurities and solids settle on the probe.
Air bubbles form around the probe.
Air bubbles collect around the probe.
The probe is exposed to air bubbles and deposits of solids.
The conductivity of the solution indicates the concentration of fertilisers: the system doses the fertiliser up to the set value.
In domestic water circuits the system monitors conductivity and controls dosing or drain according to the measured value.
In industrial process water the controller drives dosing pumps and inlet and drain solenoid valves.
Learn more: industrial water →
In cooling towers, bleed-off according to conductivity, together with the dosing of antiscalant and biocides, is managed by dedicated systems: WT pump, MTOWER and Centurio Tower.
Cooling tower systems →Accessories available on request to adapt the system to the requirements of the installation.
PE tanks for the chemical, with safety bund.
Details →
Enables dosing proportional to the volume of water actually treated.
Details →
Installed on the pump delivery line, it verifies that dosing actually takes place.
Details →
Ensures the chemical is mixed with the water and protects the pipe from direct contact with it.
Details →
Attenuates the pulsations generated by the dosing pump.
Details →
Injects the chemical into the centre of the pipe.
Details →
Pressure, safety and anti-siphon functions combined in a single valve.
Details →
Measuring ranges, resolution, BASIC and PLUS versions, connectable probes, inputs, outputs and connections are given in the controller data sheet.
For conductivity control the basic solution is the dosing station; when dosing has to be controlled by the measured value, measuring controllers are used.
The simplest solution: the pump doses at a constant rate or in proportion to the volume of water measured by the pulse-output water meter.
Details →
Conductivity measurement with contacting or inductive probes and dosing up to the set value.
Details →
Simultaneous management of two parameters, for example pH and chlorine, with a single controller.
Details →
Management of up to 10 parameters and of all the pumps in the installation, with touch screen and remote control as standard.
Details →The controllers support two-way remote access (read and write) through the web portal from a PC, tablet or smartphone: measurements can be viewed, set points, dosing and alarms changed, alarms received and logs downloaded. Alternatively, they can be integrated into your PLC via Modbus.
Connection to the web portal via network cable: measurements, set points, dosing and alarms accessible from a PC, tablet or smartphone.
Wireless connection to the web portal, with the same functions as the cable connection.
Connection via the 4G network for installations without a local network, with alarm notification by SMS or e-mail.
Web portalPC, tablet and smartphone
Integration into your PLC via serial port.
Current signal proportional to the measured value, for remote monitoring or for controlling pumps and other instrumentation.
Download of the logged data to a USB memory stick, for archiving and analysis with a spreadsheet.
One communication type at a time: Ethernet, Wi-Fi, 4G or Modbus RTU (built into the BASIC versions, optional on the PLUS versions). 0-4/20 mA current loop outputs standard on the PLUS versions, optional on the BASIC versions; meter input on the PLUS versions only.
A single account brings together all registered installations, each with its own devices: the web portal, free of charge and with no subscription, can be accessed from a PC, Mac, tablet or smartphone and allows every parameter to be both viewed and changed, with an encrypted connection and protected access.
On a single screen: probe readings, chemical levels, pump activation thresholds and active alarms, with the status of installations and devices (normal, warning, alarm, standby, not connected).
Installations appear on an interactive map with their status and open with a click; for each one, the local weather conditions and temperature are also shown.
Archive of measurements and alarms, available for consultation at any time with charts and numerical reports exportable in Excel format.
Alarm thresholds for readings, dosing, faulty probe and out-of-range readings, with notification by e-mail or SMS depending on the communication system; a warning is also issued when an installation remains disconnected beyond the set time.
Remote modification of the set points, of the dosing pump activation thresholds and of the corresponding hourly flow rate.
Status of relays, pulse outputs, digital inputs and current outputs, with the name assigned to each connection.
Tasks are scheduled by installation or by device and assigned to technicians; a reminder is sent by e-mail two days before the due date. Each task is shown as scheduled, due, overdue or completed.
The main account has full access and creates the technicians’ accounts, each enabled only for the assigned installations and devices; the last login and activity of each technician are visible.
Reports on devices, tasks and technicians, downloadable in PDF or CSV with the customer’s logo; the log keeps the history of operations and disconnections.
Logo, main colour and light or dark theme; the tiles on the main screen can be rearranged by dragging them. Two installations can be displayed side by side for comparison.
Each device is added through a guided procedure: the model is recognised automatically and associated with the installation, together with the technician to be contacted.
As an alternative to the portal, the Modbus RTU port allows integration into the plant supervision system.
Tell us the type of water, the conductivity to be maintained and the equipment to be controlled: we will propose the most suitable probe, probe holder, pumps, valves and accessories.
Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.