Measuring and dosing systems

Panel-mounted pH system with JA PRO

The system continuously measures the pH of the water and the temperature with the JA PRO pH controller, flush-mounted on the front of the electrical panel of the plant, and according to the set points it drives the acid or alkali dosing pumps, including those already installed, and the motorised valves. The two volt-free contact outputs work in ON/OFF, proportional or PID mode; the Modbus RTU port connects the controller to the PLC network of the plant.

  • pH from 0 to 14, resolution 0.01
  • ON/OFF, proportional or PID control
  • 96×96 mm flush mounting
  • Modbus RTU
JA PRO pH 96×96 flush-mount controller
JA PROpH
Combination pH electrodes
pH electrode
Composition

Basic composition

The controller is completed by the pH electrode, the probe holder, the dosing pumps for the correcting agent and the shut-off accessories of the plant.

JA PRO 96×96 flush-mount controller

JA PRO controller · JAPH PRO

Single-channel controller plus temperature, for 96×96 flush mounting, with two volt-free contact outputs, one proportional pump output, one 0-4/20 mA output and Modbus RTU communication.

JA PRO →
Combination pH electrodes

pH electrode

Combined double-junction electrode, also with self-cleaning head, installed immersed, in line or in a bypass line; temperature is read with a PT100 probe.

pH electrodes →
Flow-through probe holder

Probe holder and filter

Probe holder connected in a bypass line to the circuit, with 5" filter with washable 60 µm PET cartridges or 100 µm wound cartridges (maximum 5 bar).

Probe holders →
VMS MF multifunction dosing pump

Dosing pump

Flow rate and back pressure defined at the time of ordering, wetted parts in PVDF, PP, PVC or stainless steel. Supplied with a pre-calibrated injection valve and a magnetic level probe with foot suction pipe, which stops the pump when the chemical runs out.

Dosing pumps →
Flow sensor on the pump delivery

Flow sensor

Installed on the pump delivery, it checks the passage of the liquid: in the event of a fault the pump performs automatic re-priming and recovers the missed injections; if the anomaly persists, it is also signalled remotely. With an acquisition unit it records chemical consumption and transmits it via Modbus.

Flow sensor →
Motorised ball valve driven by the controller

Motorised valves

Connected to a set-point-controlled volt-free contact output, they shut off the water inlet or outlet according to the measured value.

Operation

Operation

The set points of the parameter to be controlled are entered; the controller drives the connected equipment automatically and continuously.

1

Measurement

The probe, installed in a probe holder in a bypass line, in line or immersed, continuously detects the parameter and the PT100 probe the temperature; the display shows the measured value, the temperature and the status of the outputs.

2

Dosing pump control

The two volt-free contact outputs work in ON/OFF, proportional or PID mode; the proportional pump output varies the injection frequency in proportion to the deviation from the set point and the 0-4/20 mA output drives a pump directly over the proportional band.

3

Existing pumps and motorised valves

The volt-free contact outputs control pumps already installed and motorised valves that shut off the water inlet or outlet when the set points are reached.

4

Flow, stand-by and Modbus RTU

The flow input suspends dosing when no water flows through the probe holder; the stand-by input stops the activity of the controller on an external command. The Modbus RTU port connects the controller to the PLC of the plant.

Display

Display view

Display of the JA PRO pH controller: pH, temperature and OUT1 output at 100%

JA PRO pH

Measured pH, temperature and status of output OUT1.

Inputs and outputs

Inputs, outputs and alarms

The probes, the external contacts and the controlled loads are connected to the terminal board of the controller.

Inputs

  • Parameter probe: BNC connector for pH and Redox electrodes, terminal board for conductivity probes and amperometric cells
  • PT100 temperature probe, 0 – 200 °C
  • SEPR flow sensor, with normally open or normally closed contact and response delay programmable up to 99 minutes
  • Stand-by from an external contact, normally open or normally closed, which stops the activity of the controller

Outputs

  • 2 volt-free contact outputs, maximum 2 A, in ON/OFF, proportional or PID mode
  • Opto-isolated pulse output for IS, MF and PLUS series dosing pumps (maximum 50 mA, 24 VDC)
  • Volt-free contact alarm output, maximum 2 A
  • 0-20 or 4-20 mA current output, galvanically isolated, maximum load 500 Ω
  • RS485 port with Modbus RTU protocol

Alarms

  • No flow: dosing suspended and NO FLOW message
  • Stand-by lasting longer than the set maximum time: alarm output activated and message on the display
  • Warning and alarm messages in the notification area of the display
Installation

Installation in the electrical panel

The controller is flush-mounted on the front of the electrical panel of the plant, in a 96×96 mm cut-out; ABS housing, IP40 protection (IP54 on request), 230 VAC or 12 or 24 VDC power supply.

Flush mounting of the JA PRO controller in the electrical panel
JA PRO 96×96 flush-mount controller

Connection to the PLC network

The RS485 port with Modbus RTU protocol connects the controller to the PLC network of the plant, for reading the measurements.

Diagram of the bypass connection of the PEF flow-through probe holder

Probe holder in a bypass line

The sample water is taken with a T-fitting on the pipe, flows through the filter and the probe holder and returns to the circuit or to drain.

Probe holders →
Applications

Where it is used

The panel-mounted system is used when measurement and control must be part of the electrical panel of the plant and communicate with the PLC.

Domestic water circuits

Domestic water circuits

pH control in domestic water circuits.

The controller

The JA PRO controller

JA PRO 96×96 flush-mount controller

JA PRO

Versions and models, parameters, measuring ranges, inputs, outputs and technical characteristics are given on the controller page.

Optional extras

Optional accessories

Accessories available on request to adapt the system to the requirements of the installation.

Tank

Tank

PE tanks for the chemical, with safety bund.

Details →
Injection lance

Injection lance

Injects the chemical into the centre of the pipe.

Details →
Multifunction valve

Multifunction valve

Pressure, safety and anti-siphon functions combined in a single valve.

Details →
Static mixer

Static mixer

Ensures the chemical is mixed with the water and protects the pipe from direct contact with it.

Details →
Pulsation dampener

Pulsation dampener

Attenuates the pulsations generated by the dosing pump.

Details →

Technical advice

Tell us the parameter to be controlled, the characteristics of the panel and the equipment to be driven: we will propose the most suitable probe, pumps and accessories.

Contact

Tell us about your plant

Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.

What do you need?
Please enter your name.
Please enter a valid email address.
Please enter your message.

Describe your plant: type, water volume or flow rate, parameters to be controlled.