Level
The controller monitors the water level in the tank by means of the maximum and minimum level sensors.
The system automatically manages the pH neutralisation of process water and wastewater collected in a tank: the LDsPN PLUS controller drives the motorised inlet and drain valves, the mixer and the acid and base dosing pumps, and repeats the cycle at each activation signal.
Automatic, fully programmable system for the pH neutralisation of water in a tank. The diagram follows the cycle phases, which are repeated at each activation signal: each phase adds the component that performs it. Two modes are available: neutralisation to the set pH, or alkaline precipitation (for example of heavy metals) at a settable pH, with reaction time, followed by neutralisation.
Learn more: adjusting pH →
The controller monitors the water level in the tank by means of the maximum and minimum level sensors.
The motorised inlet valve opens and closes again when the set level is reached.
The electrode measures the pH of the water collected in the tank.
The dosing pumps inject acid or base for neutralisation, with the mixer running.
With dosing stopped, the controller waits for the set reaction time.
The motorised drain valve opens and the tank is emptied.
The complete plant repeats the cycle at each activation signal.
In addition to the neutralisation tank with the maximum and minimum level sensors, the plant includes the following components. The filling and draining of the tank are controlled by solenoid valves or by motorised valves.
It controls the filling and draining of the tank, the mixer and the dosing pumps until the desired pH is reached.
LDsPN PLUS →
Combined electrode with single or double junction, resistant to acids and bases, to high temperatures and to hydrofluoric acid.
pH electrodes →
It keeps the water in the tank in motion during dosing, so that the pH adjuster is distributed evenly.
Mixers →
Two pumps, one for the acid and one for the base, controlled by the controller; the levels of the two tanks are monitored by the controller.
Dosing pumps →
Driven by the controller, it opens and closes the filling or draining of the tank according to the maximum and minimum levels.
As an alternative to the solenoid valve, the motorised ball valve opens and closes the filling or draining of the tank on command from the controller.
Probe positioning is defined according to the characteristics of the installation and of the water to be analysed.
The electrode is immersed directly in the storage tank of the water to be treated, by means of an immersion probe holder.
Probe holders →
A solution suited to water with a high solids load: at programmed intervals the control panel puts the controller in stand-by and opens a solenoid valve that sends water or air to the nozzle; once cleaning is complete, it closes the valve and, after the electrode repolarisation time has elapsed, resumes dosing.
Probe holders →
The electrodes are inserted directly into the pipe carrying the water to be treated.
Probe holders →
Batch neutralisation of industrial process water collected in a tank.
Learn more: industrial water →
Neutralisation of acidic or alkaline discharges and alkaline precipitation of heavy metals, followed by neutralisation.
Learn more: wastewater →
Measuring range, resolution, display, inputs, outputs, alarms and connections are given in the controller data sheet; the controller is available in the PLUS version only.
The controllers support two-way remote access (read and write) through the web portal from a PC, tablet or smartphone: measurements can be viewed, set points, dosing and alarms changed, alarms received and logs downloaded. Alternatively, they can be integrated into your PLC via Modbus.
Connection to the web portal via network cable: measurements, set points, dosing and alarms accessible from a PC, tablet or smartphone.
Wireless connection to the web portal, with the same functions as the cable connection.
Web portalPC, tablet and smartphone
Connection via the 4G network for installations without a local network, with alarm notification by SMS or e-mail.
Integration into your PLC via serial port.
Current signal proportional to the measured value, for remote monitoring or for controlling pumps and other instrumentation.
One communication type at a time: Ethernet, Wi-Fi, 4G or Modbus RTU (built into the BASIC versions, optional on the PLUS versions). 0-4/20 mA current loop outputs standard on the PLUS versions, optional on the BASIC versions; meter input on the PLUS versions only.
A single account brings together all registered installations, each with its own devices: the web portal, free of charge and with no subscription, can be accessed from a PC, Mac, tablet or smartphone and allows every parameter to be both viewed and changed, with an encrypted connection and protected access.
On a single screen: probe readings, chemical levels, pump activation thresholds and active alarms, with the status of installations and devices (normal, warning, alarm, standby, not connected).
Installations appear on an interactive map with their status and open with a click; for each one, the local weather conditions and temperature are also shown.
Archive of measurements and alarms, available for consultation at any time with charts and numerical reports exportable in Excel format.
Alarm thresholds for readings, dosing, faulty probe and out-of-range readings, with notification by e-mail or SMS depending on the communication system; a warning is also issued when an installation remains disconnected beyond the set time.
Remote modification of the set points, of the dosing pump activation thresholds and of the corresponding hourly flow rate.
Status of relays, pulse outputs, digital inputs and current outputs, with the name assigned to each connection.
Tasks are scheduled by installation or by device and assigned to technicians; a reminder is sent by e-mail two days before the due date. Each task is shown as scheduled, due, overdue or completed.
The main account has full access and creates the technicians’ accounts, each enabled only for the assigned installations and devices; the last login and activity of each technician are visible.
Reports on devices, tasks and technicians, downloadable in PDF or CSV with the customer’s logo; the log keeps the history of operations and disconnections.
Logo, main colour and light or dark theme; the tiles on the main screen can be rearranged by dragging them. Two installations can be displayed side by side for comparison.
Each device is added through a guided procedure: the model is recognised automatically and associated with the installation, together with the technician to be contacted.
As an alternative to the portal, the Modbus RTU port allows integration into the plant supervision system.
Tell us the type of water, the tank volume and the chemicals used: we will propose the most suitable electrode, pumps, mixer, valves and accessories.
Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.