Measurement and control

JA PRO

The JA PRO is a single-channel 96×96 flush-mount controller, with temperature reading by a PT100 probe, for pH, Redox, conductivity, free chlorine, chlorine dioxide, ozone and hydrogen peroxide. Its two volt-free contact outputs work in ON/OFF, proportional or PID mode and can also switch an ozone generator on and off; the controller also provides a proportional pump output, a stand-by input and Modbus RTU communication.

  • 96×96 mm flush mounting
  • Temperature with PT100 probe
  • PID control and Modbus RTU
  • IP54 protection on request
JA PRO 96×96 flush-mount controller
JA PRO96×96
Dimensions of the JA PRO controller
96×96 mm housing
96×96mmFlush mounting
0 – 200°CTemperature with PT100 probe
2Volt-free contact outputs
IP54Protection rating on request
The model

JA PRO

JA PRO flush-mount controller
96×96 flush mounting

JA PRO

For pH, Redox, conductivity (0 – 300 mS), free chlorine, chlorine dioxide, ozone and hydrogen peroxide. Two ON/OFF, proportional or PID digital outputs, one proportional pump output, one 0-4/20 mA current loop output and a Modbus RTU port for the PLC network; measuring channel plus temperature channel.

Available versions
Dimensions Dimensions96×96 mm housing.
Control

Digital logic and control modes

The alphanumeric display shows the measured value, the set points and the proportional band. The housing is made of ABS, with IP40 protection rating or IP54 on request.

Time-proportional (100-second cycle)

The output remains active for a fraction of the 100-second period proportional to the deviation from the set point: for example, at pH 7.30 it remains active for 30 seconds and inactive for 70. ON/OFF control is available as an alternative.

Proportional pump output

As in the LD controllers, the proportional pump output varies the injection frequency in proportion to the deviation from the set point, stopping the pump when the set value is reached.

Proportional 0-4/20 mA current loop

The current output drives the pump directly over the proportional band: 4 mA at SET POINT ON (maximum strokes) and 20 mA at SET POINT OFF (pump stopped), for example 4 mA at pH 8 and 20 mA at pH 7 with acid dosing, or 4 mA at 600 mV and 20 mA at 650 mV for Redox.

Existing pumps and solenoid valves

The volt-free contact outputs control pumps already installed and solenoid valves that shut off the water inlet or outlet when the set points are reached.

Inputs and outputs

Inputs, outputs and alarms

The probes, the external contacts and the controlled loads are connected to the terminal board of the controller.

Inputs

  • Parameter probe: BNC connector for pH and Redox electrodes, terminal board for conductivity probes and amperometric cells
  • PT100 temperature probe, 0 – 200 °C
  • SEPR flow sensor, with normally open or normally closed contact and response delay programmable up to 99 minutes
  • Stand-by from an external contact, normally open or normally closed, which stops the activity of the controller

Outputs

  • 2 volt-free contact outputs, maximum 2 A, in ON/OFF, proportional or PID mode
  • Opto-isolated pulse output for IS, MF and PLUS series dosing pumps (maximum 50 mA, 24 VDC)
  • Volt-free contact alarm output, maximum 2 A
  • 0-20 or 4-20 mA current output, galvanically isolated, maximum load 500 Ω
  • RS485 port with Modbus RTU protocol

Alarms

  • No flow: dosing suspended and NO FLOW message
  • Stand-by lasting longer than the set maximum time: alarm output activated and message on the display
  • Warning and alarm messages in the notification area of the display
Display

Display screens

JA PRO pH controller display: pH, temperature and OUT1 output at 100%

JA PRO pH

Measured pH, temperature and status of the OUT1 output.

JA PRO conductivity controller display: conductivity in mS, output status and temperature

JA PRO conductivity

Conductivity in mS, output status, temperature and time.

Setting the proportional output of the JA PRO conductivity controller between 25 and 10 mS

Proportional output

OUT 1 in proportional mode: 0% at 25.00 mS, 100% at 10.00 mS.

Flush mounting

Flush mounting in the panel

The controller is flush-mounted on the front of the electrical panel of the plant: the 89 × 90 mm body fits into an 89 × 89 mm panel cut-out, leaving the 96.2 × 96.2 mm front panel visible, with the display and the programming knob; the depth is 87.1 mm.

JA PRO controller fitting into the cut-out of the electrical panel: 96.2 × 96.2 mm front panel
Probes

Measurable parameters and probes

The controller connects to the same probes as the LD controllers; the data sheets are given further down.

Combination pH electrodes

pH

Combination electrodes, including double-junction, self-cleaning or for low conductivity.

pH electrodes →
Contacting conductivity probes

Contacting conductivity

Probes with graphite, stainless steel or platinum electrodes.

Contacting probes →
Inductive conductivity probes

Inductive conductivity

Inductive probes up to 0 – 300 mS, not subject to polarisation and deposits.

Inductive probes →
Amperometric cells for free chlorine

Free chlorine

Closed amperometric cells with selective membrane, pH and temperature compensation.

SCL cells →
SCL2 and SCL17 amperometric cells for chlorine dioxide

Chlorine dioxide

SCL2 closed amperometric cells and SCL17 self-cleaning cells for hot water.

SCL cells →
Closed amperometric cell for ozone

Ozone

SCL10 closed amperometric cell with selective membrane.

SCL10 cell →

Probe data sheets

pH electrodes
ElectrodePressureConnectionBodyMinimum conductivityJunctionTemperatureCableDiameterNotes
EpHS7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)0.8 m12 mm–
EpHM7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)4.5 m12 mm–
EpHL7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)15 m12 mm–
EpHSN67 bar (3.5 bar)SN6 with PG13.5 threadEpoxy100 µS–70 °C (80 °C)1 – 100 m12 mm–
EpHMD/1007 barBNCEpoxy100 µSDouble100 °C4.5 m12 mm–
EpHM/D7 bar (3.5 bar)BNCEpoxy100 µSDouble70 °C (80 °C)4.5 m12 mm–
EpHM/D/SN67 bar (3.5 bar)SN6 with PG13.5 threadEpoxy100 µSDouble70 °C (80 °C)1 – 100 m12 mm–
EpHMD/LI7 bar (3.5 bar)SN6 with PG13.5 threadEpoxy3 µSDouble70 °C (80 °C)1 – 100 m12 mmFor low-conductivity water
EpHSC7 bar (3.5 bar)BNCEpoxy100 µSDouble70 °C (80 °C)4.5 m12 mmSelf-cleaning
EpHSC/SN67 bar (3.5 bar)SN6 with PG13.5 threadEpoxy100 µSDouble70 °C (80 °C)1 – 100 m12 mmSelf-cleaning
EpHM/HF7 bar (3.5 bar)BNCEpoxy100 µSDouble70 °C (80 °C)4.5 m12 mmResistant to 1% hydrofluoric acid
EpHSN6 GK10 barSN6Glass150 µS–−5 / 135 °C1 – 100 m12 mmHigh temperature

All models: combination electrode, range 0 – 14 pH, resolution 0.01.

Redox electrodes
ElectrodeRangePressureConnectionBodyMinimum conductivityJunctionTemperatureCableDiameterNotes
ERhS± 1,000 mV7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)0.8 m12 mm–
ERhM± 1,000 mV7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)4.5 m12 mm–
ERhL± 1,000 mV7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)15 m12 mm–
ERhHLB SN6± 1,500 mV6 barSN6 with PG13.5 threadGlass100 µS–80 °C10 m12 mmHigh linearity and sensitivity, for low chlorine concentrations
ERhSN6± 1,000 mV7 barSN6 with PG13.5 threadEpoxy100 µS–100 °C1 – 100 m12 mm–
ERhMD/100± 1,000 mV7 barBNCEpoxy100 µSDouble100 °C4.5 m12 mm–
ERhM/D± 1,000 mV7 bar (3.5 bar)BNCEpoxy100 µSDouble70 °C (80 °C)4.5 m12 mm–
ERhSC± 1,000 mV7 bar (3.5 bar)BNCEpoxy100 µSDouble70 °C (80 °C)4.5 m12 mmSelf-cleaning
ERhSC/SN6± 1,000 mV7 bar (3.5 bar)SN6 with PG13.5 threadEpoxy100 µSDouble70 °C (80 °C)1 – 100 m12 mmSelf-cleaning

All models: combination electrode, resolution 1 mV.

Contacting probes – ECDC

PVDF body, graphite electrodes.

ModelMountingConnectionRangeK factorTemperature compensation
ECDC/1In-line / bypassR3/4"0 – 20 mS1–
ECDCC/1In-line / bypassR3/4"0 – 20 mS1NTC 10K
ECDCCPT/1In-line / bypassR3/4"0 – 20 mS1PT100
ECDC/10In-line / bypassR3/4"0 – 200 mS10–
ECDCC/10In-line / bypassR3/4"0 – 200 mS10NTC 10K
ECDCCPT/10In-line / bypassR3/4"0 – 200 mS10PT100
ECDCIM/1ImmersionG1/2"0 – 20 mS1–
ECDCCIM/1ImmersionG1/2"0 – 20 mS1NTC 10K
ECDCCIMPT/1ImmersionG1/2"0 – 20 mS1PT100
ECDCIM/10ImmersionG1/2"0 – 200 mS10–
ECDCCIM/10ImmersionG1/2"0 – 200 mS10NTC 10K
ECDCCIMPT/10ImmersionG1/2"0 – 200 mS10PT100

Operating temperature 1 – 60 °C (100 °C at 2 bar), operating pressure 7 bar (2 bar at 100 °C).

Contacting probes – ECDI

PVDF body, stainless steel electrodes.

ModelMountingConnectionRangeK factorTemperature compensation
ECDI/1In-line / bypassR3/4"0 – 5 mS1–
ECDIC/1In-line / bypassR3/4"0 – 5 mS1NTC 10K
ECDICPT/1In-line / bypassR3/4"0 – 5 mS1PT100
ECDI/01In-line / bypassR3/4"0 – 200 µS0.1–
ECDIC/01In-line / bypassR3/4"0 – 200 µS0.1NTC 10K
ECDICPT/01In-line / bypassR3/4"0 – 200 µS0.1PT100
ECDIIM/1ImmersionG1/2"0 – 5 mS1–
ECDICIM/1ImmersionG1/2"0 – 5 mS1NTC 10K
ECDICPTIM/1ImmersionG1/2"0 – 5 mS1PT100
ECDIIM/01ImmersionG1/2"0 – 200 µS0.1–
ECDIIM/02ImmersionG1/2"0 – 500 µS0.2–
ECDICIM/01ImmersionG1/2"0 – 200 µS0.1NTC 10K
ECDICPTIM/01ImmersionG1/2"0 – 200 µS0.1PT100

Operating temperature 1 – 60 °C (100 °C at 2 bar), operating pressure 7 bar (2 bar at 100 °C).

Contacting probes – ECDHL

Epoxy body, platinum electrodes, diameter 12 mm.

ModelMountingRangeK factorTemperature compensation
ECDHL/1In-line / bypass0.2 – 20 mS1–
ECDHLC/1In-line / bypass0.2 – 20 mS1NTC 10K
ECDHLCPT/1In-line / bypass0.2 – 20 mS1PT100
ECDHL/01In-line / bypass0 – 200 µS0.1–
ECDHLC/01In-line / bypass0 – 200 µS0.1NTC 10K
ECDHLCPT/01In-line / bypass0 – 200 µS0.1PT100
ECDHL/10In-line / bypass20 – 200 mS10–
ECDHLC/10In-line / bypass20 – 200 mS10NTC 10K
ECDHLCPT/10In-line / bypass20 – 200 mS10PT100

Operating temperature 1 – 70 °C, operating pressure 7 bar.

Contacting probes – EICDC

Stainless steel body and electrodes, R3/4" connection, in-line or bypass mounting.

ModelRangeK factorTemperature compensationOperating temperature
EICDC/10 – 20 mS1NTC 10K1 – 130 °C
EICDCPT/10 – 20 mS1PT1001 – 130 °C
EICDC/010 – 200 µS0.1NTC 10K1 – 130 °C
EICDCPT/010 – 200 µS0.1PT1001 – 130 °C
EICDC/0010 – 20 µS0.01NTC 10K1 – 130 °C
EICDCPT/0010 – 20 µS0.01PT1001 – 130 °C
EICDCHPT/10 – 20 mS1PT1001 – 200 °C
EICDCHPT/010 – 200 µS0.1PT1001 – 200 °C
EICDCHPT/0010 – 20 µS0.01PT1001 – 200 °C

Operating pressure 15 bar.

Inductive probes
ECDINDPTECDSINDPT
Measuring range0.3 – 3 mS
0.3 – 30 mS
0.3 – 300 mS
0.3 – 10 mS
Measuring systemInductiveInductive
BodyPEEKPEEK
MountingIn-line / bypass / immersionIn-line / bypass / immersion
Temperature compensationPT100PT100
Operating temperature1 – 85 °C (100 °C for short periods)1 – 85 °C (100 °C for short periods)
Operating pressure8 bar8 bar
Amperometric cells – Free chlorine
SCL3N/0.5SCL3N/2SCL3N/20SCL18/0.5SCL18/2SCL18/20SCL3S/20
Measuring range0 – 0.5 mg/l0 – 2 mg/l0 – 20 mg/l0 – 0.5 mg/l0 – 2 mg/l0 – 20 mg/l0 – 20 mg/l
Resolution0.0010.0010.010.0010.0010.010.01
Free chlorineInorganicInorganicInorganicInorganicInorganicInorganicOrganic and inorganic
WaterFreshFreshFreshFreshFreshFreshFresh or salt
Electrodes2223332
Selective membrane●●●–––●
Automatic compensationpH and temperaturepH and temperaturepH and temperaturepH and temperaturepH and temperaturepH and temperatureTemperature
Self-cleaning–––●●●–
Operating pH5 – 9.55 – 9.55 – 9.55 – 95 – 95 – 95.5 – 9.5
Operating temperature1 – 40 °C1 – 40 °C1 – 40 °C5 – 70 °C5 – 70 °C5 – 70 °C5 – 45 °C
Operating pressure1 bar1 bar1 bar8 bar8 bar8 bar1 bar
Water flow30 l/h30 l/h30 l/h40 l/h40 l/h40 l/h30 l/h
Amperometric cells – Chlorine dioxide
SCL2/0.5SCL2/2SCL2/20SCL17/0.5SCL17/2SCL17/20
Measuring range0 – 0.5 mg/l0 – 2 mg/l0 – 20 mg/l0 – 0.5 mg/l0 – 2 mg/l0 – 20 mg/l
Resolution0.0010.0010.010.0010.0010.01
Electrodes222333
Selective membrane●●●–––
Self-cleaning–––●●●
Operating pH4 – 114 – 114 – 115 – 95 – 95 – 9
Operating temperature1 – 40 °C1 – 40 °C1 – 40 °C5 – 70 °C5 – 70 °C5 – 70 °C
Operating pressure1 bar1 bar1 bar8 bar8 bar8 bar
Water flow30 l/h30 l/h30 l/h40 l/h40 l/h40 l/h

Automatic temperature compensation on all models.

Amperometric cells – Other oxidants
SCL8/2SCL8/20SBR/20SCL9SCL11/200SCL11/2000SCL10SCT
MeasurementTotal chlorineTotal chlorineBromineHydrogen peroxidePeracetic acidPeracetic acidOzoneChlorites
Measuring range0 – 2 mg/l0 – 20 mg/l0 – 20 mg/l0 – 200 mg/l0 – 200 mg/l0 – 2,000 mg/l0 – 2 mg/l
0 – 20 mg/l
0 – 2 mg/l
Resolution0.0010.010.010.10.110.001
0.01
0.001
Operating pH4 – 124 – 126.5 – 9.51 – 111 – 91 – 92 – 115.5 – 9.5
Operating pressure1 bar1 bar0.5 bar1 bar1 bar1 bar1 bar1 bar

All models: 2 electrodes, selective membrane, automatic temperature compensation, operating temperature 1 – 40 °C, water flow 30 l/h.

Temperature probes
ETENTCETEPT
Measuring range0 – 100 °C0 – 100 °C
Resolution0.10.1
SensorNTC 10 kΩPT100
Pressure10 bar10 bar
BodyPVDFPVDF
Thread1/2"1/2"
Operation

Measuring principle of the closed amperometric cell

The cell consists of an electronic section and a galvanic section.

Learn more: Redox, open amperometric cell and closed amperometric cell →
1

Selective membrane

The measuring electrodes are protected from direct contact with the water by a semi-permeable membrane: only the specific oxidant is measured, without interference from other substances that could alter the measurement.

2

Galvanic measurement

The electrodes of the galvanic section detect the electric current generated by the dissociation of the oxidant.

3

Compensation and signal

The cell electronics compensate the reading for temperature (and, where applicable, pH) and send the signal to the controller, which shows the concentration in mg/l on the display.

Technical data

Technical data

Each controller measures one parameter, chosen when ordering, plus temperature; for chlorine and the other oxidants the range depends on the amperometric cell used.

Technical specifications

FeatureJA PRO
Mounting96×96 mm flush mounting
Measuring channels1 + temperature
Control outputs2 volt-free contacts, ON/OFF, proportional or PID
Proportional pump output1, opto-isolated
Alarm outputVolt-free contact
Current outputProgrammable 0-4/20 mA, galvanically isolated, maximum load 500 Ω
InputsProbe, temperature, flow, stand-by
Temperature compensationPT100 probe, 0 – 200 °C
Delayed start for probe polarisationProgrammable
Settings protectionPassword
DisplayBacklit LCD display
CommunicationModbus RTU over RS485
Power supply230 VAC; 12 / 24 VDC
Average power consumption4 W
Fuse0.5 A
Protection ratingIP40 (IP54 on request)
HousingABS
Ambient temperature0 – 50 °C
Relative humidity0 – 95 %, non-condensing

Versions and models

ParameterModel
pHJAPH PRO
RedoxJARH PRO
Free chlorine, chlorine dioxide, ozone, hydrogen peroxideJACL PRO
ConductivityJACD PRO
Inductive conductivityJACDIND PRO

In the JACL PRO model the measured parameter depends on the amperometric cell connected.

Parameters

ParameterRangeResolutionJA PRO
pH0 – 140.01 pH●
Redox−999 / +999 mV1 mV●
ConductivityAccording to the probe, up to 0 – 300 mS–●
Free chlorineClosed amperometric cell with membrane0.001 mg/l●
Chlorine dioxideClosed amperometric cell with membrane0.001 mg/l●
Ozone0 – 2 / 0 – 20 mg/l0.001 / 0.01 mg/l●
Hydrogen peroxideClosed amperometric cell with membrane0.1 mg/l●
Temperature0 – 100 °C0.1 °CAdditional channel

Free chlorine: pH and temperature compensation; maintenance-free electronic section and regenerable galvanic section.

Complete systems

Complete systems with JA PRO

The controller is the core of the measuring and dosing system: the system page gives the composition, the installation diagram and the installation.

Panel-mounted system with JA PRO

Measuring and dosing systemsPanel-mounted system with JA PRO

Controller for installation in the electrical panel to drive dosing pumps or motorised valves according to the set points, with flow sensor, probe holder and filter.

The system →

For plants with special requirements, the system is defined on the basis of the characteristics of the plant and of the electrical panel: contact us.

Choosing the controller

Tell us the parameters to be measured and the characteristics of the electrical panel: we will propose the most suitable controller, probes and pumps.

Contact

Tell us about your plant

Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.