The system continuously measures the pH and the concentration of an oxidant, normally free chlorine, with a pH electrode and an amperometric cell housed in the same flow-through probe holder, and drives the dosing pumps of the pH corrector and of the disinfectant in proportion to the deviation from their set points.

  • pH and free chlorine in mg/l
  • SCL or ECL amperometric cell
  • pH control priority
  • Two proportional pumps
LDpHCL system pre-assembled on a panel with two dosing pumps, filter and probe holder
pH and chlorinethe system
Panel with LDpHCL controller, dosing pumps and closed SCL amperometric cell in the probe holder
With SCL cell
How it works

Two proportional controls

Two values are set for each channel: the SET POINT ON, at which the pump starts dosing at maximum frequency, and the SET POINT OFF, at which it stops. Between the two the controller progressively reduces the number of strokes, avoiding overdosing. In the layout the system is installed on a water storage tank, with the sample drawn by a sampling pump.

Layout of the LDpHCL system on a water storage tank: controller, pH and chlorine probes in the probe holder fed by a sampling pump, two dosing pumps with the acid and hypochlorite tanks and the injection points
1

pH channel

The corrector pump starts when the pH exceeds the SET POINT ON, for example 8.00 pH, and slows down as the value falls towards the SET POINT OFF, for example 7.00 pH, where it stops.

2

Chlorine channel

The disinfectant pump starts when chlorine falls below the SET POINT ON, for example 0.100 mg/l, and stops when the SET POINT OFF is reached, for example 0.500 mg/l.

3

pH priority

Priority can be given to pH control, with disinfectant control starting only afterwards: pH affects the effectiveness of chlorine.

Learn more: pH →
Components

Basic components

The system is supplied pre-assembled on a panel: controller, pumps, filter and probe holder are mounted and connected, ready for by-pass connection to the plant.

LDpHCL controller

LDpHCL controller

It reads the pH electrode from the BNC connector and the amperometric cell from the terminal board, in addition to temperature, and drives the dosing pumps and the flocculant output.

The controller →
Combined pH electrode

pH electrode

The combined electrode measures pH from 0 to 14; the reading is temperature-compensated by the controller.

pH electrodes →
Closed SCL amperometric cell

Amperometric cell

The closed SCL cell has its electrodes protected by a selective membrane and compensates temperature automatically; in swimming pool water the open ECL cell is also used.

Amperometric cells →
PEF flow-through probe holder

Flow-through probe holder

It houses the pH electrode, the cell and the temperature probe in the flow of sample water; the flow sensor stops dosing when there is no circulation.

Probe holders →
VMS MF dosing pump

Dosing pumps

One solenoid diaphragm pump for the pH corrector and one for the disinfectant, with flow rate and back pressure defined when ordering.

Dosing pumps →
Injection lance

Injection lances

They introduce the products into the centre of the pipe, improving mixing, and can be withdrawn with the pipe under pressure.

Lances →
Oxidants

The second channel: chlorine and other oxidants

The amperometric channel accepts any cell of the SCL series: by changing the cell, the same system measures a different oxidant, while the pH channel remains unchanged.

Closed SCL cells

They measure free chlorine, total chlorine, chlorine dioxide, bromine, hydrogen peroxide, peracetic acid, ozone or chlorites. With the closed amperometric cell the chlorine measurement is compensated for pH and temperature directly in the probe.

SCL cells →

Open ECL cell

It measures free chlorine in swimming pool water; pH compensation is performed by the controller using the measurement of the first channel.

ECL cells →
Operation

Checks and alarms

Alarms

For each channel the controller signals out-of-range readings, a faulty probe, maximum dosing time exceeded and depletion of the products in the tanks.

Flow

When there is no flow in the probe holder, for example with the circulation system stopped, the controller inhibits pump dosing.

Flocculant

A powered output drives the flocculant pump, active except in stand-by and flow alarm.

Applications

Fields of application

Private swimming pools

Private swimming pools

In private swimming pools the system controls the pH and keeps free chlorine at the set value, measured directly in mg/l.

Private swimming pools →
Drinking water

Drinking water

Disinfection of water from wells, springs and storage tanks, with control of the pH that affects the effectiveness of chlorine.

Drinking water systems →
The controller

The LDpHCL controller

LDpHCL system pre-assembled on a panel with two dosing pumps, filter and probe holder

LDpHCL

Measuring ranges, resolution, compensations, inputs, outputs, display and connections are given in the controller data sheet.

Remote control

System remote control

The controllers support two-way remote access (read and write) through the web portal from a PC, tablet or smartphone: measurements can be viewed, set points, dosing and alarms changed, alarms received and logs downloaded. Alternatively, they can be integrated into your PLC via Modbus.

Ethernet

Connection to the web portal via network cable: measurements, set points, dosing and alarms accessible from a PC, tablet or smartphone.

Optional (one only)

Wi-Fi

Wireless connection to the web portal, with the same functions as the cable connection.

Optional (one only)

4G

Connection via the 4G network for installations without a local network, with alarm notification by SMS or e-mail.

Optional (one only)
NIMBUS web portal for remote control of the systemsWeb portalPC, tablet and smartphone

Modbus RTU

Integration into your PLC via serial port.

Standard (BASIC), optional (PLUS)

0-4/20 mA current loop output

Current signal proportional to the measured value, for remote monitoring or for controlling pumps and other instrumentation.

Optional (3 outputs)

USB port

Download of the logged data to a USB memory stick, for archiving and analysis with a spreadsheet.

Optional

One communication type at a time: Ethernet, Wi-Fi, 4G or Modbus RTU (built into the BASIC versions, optional on the PLUS versions). 0-4/20 mA current loop outputs optional; meter input on the PLUS versions only.

The NIMBUS portal

A single account brings together all registered installations, each with its own devices: the web portal, free of charge and with no subscription, can be accessed from a PC, Mac, tablet or smartphone and allows every parameter to be both viewed and changed, with an encrypted connection and protected access.

The NIMBUS portal on monitor, laptop, tablet and smartphone

Overview

On a single screen: probe readings, chemical levels, pump activation thresholds and active alarms, with the status of installations and devices (normal, warning, alarm, standby, not connected).

Installation map

Installations appear on an interactive map with their status and open with a click; for each one, the local weather conditions and temperature are also shown.

History and charts

Archive of measurements and alarms, available for consultation at any time with charts and numerical reports exportable in Excel format.

Alarms and notifications

Alarm thresholds for readings, dosing, faulty probe and out-of-range readings, with notification by e-mail or SMS depending on the communication system; a warning is also issued when an installation remains disconnected beyond the set time.

Set points and dosing

Remote modification of the set points, of the dosing pump activation thresholds and of the corresponding hourly flow rate.

Inputs and outputs

Status of relays, pulse outputs, digital inputs and current outputs, with the name assigned to each connection.

Maintenance calendar

Tasks are scheduled by installation or by device and assigned to technicians; a reminder is sent by e-mail two days before the due date. Each task is shown as scheduled, due, overdue or completed.

Team and permissions

The main account has full access and creates the technicians’ accounts, each enabled only for the assigned installations and devices; the last login and activity of each technician are visible.

Reports and activity log

Reports on devices, tasks and technicians, downloadable in PDF or CSV with the customer’s logo; the log keeps the history of operations and disconnections.

Customisation

Logo, main colour and light or dark theme; the tiles on the main screen can be rearranged by dragging them. Two installations can be displayed side by side for comparison.

Guided registration

Each device is added through a guided procedure: the model is recognised automatically and associated with the installation, together with the technician to be contacted.

PLC integration

As an alternative to the portal, the Modbus RTU port allows integration into the plant supervision system.

NIMBUS portal: Real-time readings, counters and timers
Real-time readings, counters and timers
NIMBUS portal: Free chlorine and temperature trends
Free chlorine and temperature trends
NIMBUS portal: Set point and operating mode of each channel
Set point and operating mode of each channel
NIMBUS portal: Status of relays, pulses, inputs and mA outputs
Status of relays, pulses, inputs and mA outputs

Technical advice

Tell us about the plant, the water flow rate and the disinfectant used: we will propose the most suitable cell, pumps and accessories.

Contact

Tell us about your plant

Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.

What do you need?
Please enter your name.
Please enter a valid email address.
Please enter your message.

Describe your plant: type, water volume or flow rate, parameters to be controlled.

You must accept the privacy notice to continue.