JA PRO controller · JARH PRO
Single-channel controller plus temperature, for 96×96 flush mounting, with two volt-free contact outputs, one proportional pump output, one 0-4/20 mA output and Modbus RTU communication.
JA PRO →The system continuously measures the Redox potential (ORP) of the water, expressed in mV, which indicates its disinfecting power, with the JA PRO Redox controller flush-mounted on the front of the electrical panel of the plant. According to the set points it drives the dosing pumps for hypochlorite or another disinfectant, including those already installed, and the motorised valves; the Modbus RTU port connects the controller to the PLC network of the plant.
The controller is completed by the Redox electrode, the probe holder, the disinfectant dosing pump and the shut-off accessories of the plant.
Single-channel controller plus temperature, for 96×96 flush mounting, with two volt-free contact outputs, one proportional pump output, one 0-4/20 mA output and Modbus RTU communication.
JA PRO →
Combined double-junction electrode, also with self-cleaning head, installed immersed, in line or in a bypass line; temperature is read with a PT100 probe.
Redox electrodes →
Probe holder connected in a bypass line to the circuit, with 5" filter with washable 60 µm PET cartridges or 100 µm wound cartridges (maximum 5 bar).
Probe holders →
Flow rate and back pressure defined at the time of ordering, wetted parts in PVDF, PP, PVC or stainless steel. Supplied with a pre-calibrated injection valve and a magnetic level probe with foot suction pipe, which stops the pump when the chemical runs out.
Dosing pumps →
Installed on the pump delivery, it checks the passage of the liquid: in the event of a fault the pump performs automatic re-priming and recovers the missed injections; if the anomaly persists, it is also signalled remotely. With an acquisition unit it records chemical consumption and transmits it via Modbus.
Flow sensor →
Connected to a set-point-controlled volt-free contact output, they shut off the water inlet or outlet according to the measured value.
The set points of the parameter to be controlled are entered; the controller drives the connected equipment automatically and continuously.
The probe, installed in a probe holder in a bypass line, in line or immersed, continuously detects the parameter and the PT100 probe the temperature; the display shows the measured value, the temperature and the status of the outputs.
The two volt-free contact outputs work in ON/OFF, proportional or PID mode; the proportional pump output varies the injection frequency in proportion to the deviation from the set point and the 0-4/20 mA output drives a pump directly over the proportional band.
The volt-free contact outputs control pumps already installed and motorised valves that shut off the water inlet or outlet when the set points are reached.
The flow input suspends dosing when no water flows through the probe holder; the stand-by input stops the activity of the controller on an external command. The Modbus RTU port connects the controller to the PLC of the plant.
The probes, the external contacts and the controlled loads are connected to the terminal board of the controller.
The controller is flush-mounted on the front of the electrical panel of the plant, in a 96×96 mm cut-out; ABS housing, IP40 protection (IP54 on request), 230 VAC or 12 or 24 VDC power supply.

The RS485 port with Modbus RTU protocol connects the controller to the PLC network of the plant, for reading the measurements.
The sample water is taken with a T-fitting on the pipe, flows through the filter and the probe holder and returns to the circuit or to drain.
Probe holders →The system is used wherever the disinfecting power of the water must be kept constant with a simple and economical solution.
In raw water from private wells and springs and from public water supply networks, hypochlorite is dosed according to the Redox potential measured in the storage tank.
In fire-fighting water reserves the electrode is immersed in the tank and the system maintains the disinfecting power of the water by automatically dosing hypochlorite.
In domestic water circuits the system maintains the set Redox potential as consumption varies.
In water used in industrial processes, disinfectant dosing follows the variations in the pollutant load.
Learn more: industrial water →
In municipal and industrial wastewater the system adjusts disinfectant dosing to the potential actually measured.

Versions and models, parameters, measuring ranges, inputs, outputs and technical characteristics are given on the controller page.
Accessories available on request to adapt the system to the requirements of the installation.
PE tanks for the chemical, with safety bund.
Details →
Injects the chemical into the centre of the pipe.
Details →
Pressure, safety and anti-siphon functions combined in a single valve.
Details →
Ensures the chemical is mixed with the water and protects the pipe from direct contact with it.
Details →
Attenuates the pulsations generated by the dosing pump.
Details →Tell us the parameter to be controlled, the characteristics of the panel and the equipment to be driven: we will propose the most suitable probe, pumps and accessories.