Skip to content
Measurement and control

LDspH

The LDspH measures pH with a resolution of 0.01 and temperature with a PT100 probe, which automatically compensates the measurement. Depending on the deviation from the set point it controls one or two dosing pumps for acid or base.

  • Range 0 – 14 pH, resolution 0.01
  • Compensation with PT100 probe
  • Acid, base or both
  • BASIC and PLUS versions
LDspH controller
LDspHcontroller
Combined pH electrodes
pH electrode
0 – 14pHMeasuring range
0.01pHResolution
3Electrode positions
IP65Protection rating
Controller

The controller

It acquires the measurement from the electrode and controls the dosing pump in proportion to the measured value.

Colour display

Multicolour backlit display that indicates the different operating states by changing colour. Programming via a single knob.

Four modes

Proportional, ON/OFF, PWM and PID dosing, with delayed dosing start.

Data storage

Permanent data storage and a system log viewable on the display; the internal log can be exported to a USB memory stick for processing with a spreadsheet.

Alarms

Chemical level, no flow, maximum dosing time exceeded, probe failure, out-of-range reading; audible or visual signalling via the alarm output.

Colour display

Colour-coded status indication

By changing colour, the controller’s backlit display indicates the different operating states, which can be recognised even from a distance.

Display Normal operation

Normal operation

Measurement and dosing according to the set parameters.

Display Stand-by

Stand-by

Controller in stand-by.

Display Warning

Warning

Warning signal, for example the chemical level.

Display Alarm

Alarm

Alarm signal, for example from the probe.

Settings from the display

LDspH display: set point setting
Proportional mode: 180 pulses per minute at pH 7.60, pump stopped at pH 7.20
Versions

BASIC and PLUS versions

The instrument is available in two versions, which differ in the number of inputs and outputs: the PLUS version adds the meter input, PID control, a second level input, a second dosing pump output, the 0-4/20 mA current loop outputs and the outputs for probe self-cleaning and for the circulation pump.

BASICPLUS
Measuring channels1 + temperature1 + temperature
Level inputs12
Flow input11
Stand-by input11
Meter input–1
Outputs for pumps and loads (relays)1 (ON/OFF, PWM)2 (ON/OFF, PWM, PID)
Proportional outputs for dosing pumps12
Alarm output11
0-4/20 mA current loop outputs2 on request3
Probe self-cleaning output–1
Circulation pump output–1
Modbus RTU●Optional
Ethernet, Wi-Fi, 4G, USBOptionalOptional
Data sheet

Controller data sheet

Inputs, outputs, control modes and alarms of the controller.

Inputs

  • Measuring probe
  • Temperature
  • Flow sensor
  • Stand-by
  • Chemical level: 1 (BASIC), 2 (PLUS)
  • Pulse-output water meter or mA signal (PLUS)

Outputs

  • Proportional dosing pumps: 1 (BASIC), 2 (PLUS)
  • Relay outputs for pumps and loads: 1 (BASIC), 2 (PLUS)
  • Alarm output
  • 0-4/20 mA current loop outputs: 3 (PLUS), 2 on request (BASIC)
  • Probe self-cleaning and circulation pump (PLUS)

Control

  • Proportional
  • ON/OFF
  • PWM
  • PID (PLUS)
  • Delayed start

Alarms

  • Chemical level
  • No flow
  • Maximum dosing time
  • Probe failure
  • Out-of-range reading

Power supply

  • 230 VAC
  • 12 – 24 VDC
The model

LDspH

LDspH controller
pH control

LDspH

pH measurement and control with acid or base dosing. Wide flexibility in electrode positioning: in a flow-through probe holder, in-line on the pipe or immersed in the tank.

Electrode

pH electrode

Learn more: how pH is measured →
Combination pH electrodes

Versions for every type of water

Single or double junction combination electrode, resistant to acids and bases, high temperatures and hydrofluoric acid, also suitable for low-conductivity water; available in a self-cleaning version.

pH electrodes →
Immersion probe holder with cleaning nozzle

Jet self-cleaning

In the immersion probe holder with nozzle, a jet of water or air keeps the electrode clean in water with a high impurity load.

Probe holders →
Diagram of electrode cleaning: solenoid valve on the water or compressed air line, cleaning pipe, nozzle below the electrode tip in the immersion probe holder, controller

How cleaning works

At programmed intervals the controller suspends dosing (stand-by) and opens the solenoid valve on the water or compressed air line: the jet comes out of the nozzle below the electrode tip and removes deposits. When cleaning is complete, the valve closes and, once the electrode repolarisation time has elapsed, dosing resumes.

Probe data sheets

pH electrodes
ElectrodePressureConnectionBodyMinimum conductivityJunctionTemperatureCableDiameterNotes
EpHS7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)0.8 m12 mm–
EpHM7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)4.5 m12 mm–
EpHL7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)15 m12 mm–
EpHSN67 bar (3.5 bar)SN6 with PG13.5 threadEpoxy100 µS–70 °C (80 °C)1 – 100 m12 mm–
EpHMD/1007 barBNCEpoxy100 µSDouble100 °C4.5 m12 mm–
EpHM/D7 bar (3.5 bar)BNCEpoxy100 µSDouble70 °C (80 °C)4.5 m12 mm–
EpHM/D/SN67 bar (3.5 bar)SN6 with PG13.5 threadEpoxy100 µSDouble70 °C (80 °C)1 – 100 m12 mm–
EpHMD/LI7 bar (3.5 bar)SN6 with PG13.5 threadEpoxy3 µSDouble70 °C (80 °C)1 – 100 m12 mmFor low-conductivity water
EpHSC7 bar (3.5 bar)BNCEpoxy100 µSDouble70 °C (80 °C)4.5 m12 mmSelf-cleaning
EpHSC/SN67 bar (3.5 bar)SN6 with PG13.5 threadEpoxy100 µSDouble70 °C (80 °C)1 – 100 m12 mmSelf-cleaning
EpHM/HF7 bar (3.5 bar)BNCEpoxy100 µSDouble70 °C (80 °C)4.5 m12 mmResistant to 1% hydrofluoric acid
EpHSN6 GK10 barSN6Glass150 µS–−5 / 135 °C1 – 100 m12 mmHigh temperature

All models: combination electrode, range 0 – 14 pH, resolution 0.01.

Technical data

Technical data

The controller measures pH from 0 to 14 with a resolution of 0.01 and temperature from 0 to 100 °C with a resolution of 0.1 °C. The controller specifications are followed by the data sheets of the electrodes that can be used.

Controller technical specifications

FeatureLDspH BASIC and PLUS
Measured parameterpH, with temperature reading
Measuring range0 – 14 pH
Resolution0.01 pH
Temperature0 – 100 °C, resolution 0.1 °C
Temperature compensationAutomatic, with PT100 probe
Control modesON/OFF, proportional, PWM; PID in the PLUS version
Delayed dosing startUp to 60 minutes
Relay outputs5 A at 230 VAC, fuse-protected
Power supply85 – 264 VAC, 50/60 Hz; 9 – 30 VDC optional
Average power consumption25 W
DisplayRGB LCD display
Protection ratingIP65
HousingABS
Weight1.45 kg
MountingWall-mounted, with 4 fixing points
Ambient temperature−10 – 50 °C
Relative humidity0 – 95 %, non-condensing

The inputs and outputs of the BASIC and PLUS versions are given in the dedicated section and in the controller data sheet.

Complete systems

Complete systems with LDspH

The controller is the core of the measuring and dosing system: for each application, the system page gives the composition, the installation diagram and the installation.

pH

LDspHpH

pH control with acid or base dosing in proportion to the measured value.

The system →
Neutralisation

LDsPN PLUSNeutralisation

Batch pH neutralisation in a tank with filling, acid and base dosing, reaction and draining.

The system →
Fertigation

pH and conductivityFertigation

Control of pH and conductivity, with fertiliser and acid dosed by measurement or by volume.

The system →
Industrial water

Industrial water

Industrial water treatment ensures efficient processes, protects equipment and allows compliance with environmental regulations.

The sector →
Fire-fighting water tanks

Disinfection of standing waterFire-fighting water tanks

Free chlorine or Redox and pH, with integrated or dedicated pumps.

The system →
Food and beverage industry

Food and beverage industry

In the food industry, safety and quality allow no compromise.

The sector →
Drinking water

Disinfection and residual in the networkDrinking water

Volumetric dosing, control of residual chlorine or Redox, chlorine dioxide, monochloramine and water supply networks.

The system →

For plants with special requirements the system is defined on the characteristics of the plant: contact us.

Remote control

System remote control

The controllers support two-way remote access (read and write) through the web portal from a PC, tablet or smartphone: measurements can be viewed, set points, dosing and alarms changed, alarms received and logs downloaded. Alternatively, they can be integrated into your PLC via Modbus.

Ethernet

Connection to the web portal via network cable: measurements, set points, dosing and alarms accessible from a PC, tablet or smartphone.

Optional (one only)

Wi-Fi

Wireless connection to the web portal, with the same functions as the cable connection.

Optional (one only)

4G

Connection via the 4G network for installations without a local network, with alarm notification by SMS or e-mail.

Optional (one only)
NIMBUS web portal for remote control of the systemsWeb portalPC, tablet and smartphone

Modbus RTU

Integration into your PLC via serial port.

Standard (BASIC), optional (PLUS)

0-4/20 mA current loop output

Current signal proportional to the measured value, for remote monitoring or for controlling pumps and other instrumentation.

3 standard (PLUS), 2 on request (BASIC)

USB port

Download of the logged data to a USB memory stick, for archiving and analysis with a spreadsheet.

Optional

One communication type at a time: Ethernet, Wi-Fi, 4G or Modbus RTU (built into the BASIC versions, optional on the PLUS versions). 0-4/20 mA current loop outputs standard on the PLUS versions, optional on the BASIC versions; meter input on the PLUS versions only.

The NIMBUS portal

A single account brings together all registered installations, each with its own devices: the web portal, free of charge and with no subscription, can be accessed from a PC, Mac, tablet or smartphone and allows every parameter to be both viewed and changed, with an encrypted connection and protected access.

The NIMBUS portal on monitor, laptop, tablet and smartphone

Overview

On a single screen: probe readings, chemical levels, pump activation thresholds and active alarms, with the status of installations and devices (normal, warning, alarm, standby, not connected).

Installation map

Installations appear on an interactive map with their status and open with a click; for each one, the local weather conditions and temperature are also shown.

History and charts

Archive of measurements and alarms, available for consultation at any time with charts and numerical reports exportable in Excel format.

Alarms and notifications

Alarm thresholds for readings, dosing, faulty probe and out-of-range readings, with notification by e-mail or SMS depending on the communication system; a warning is also issued when an installation remains disconnected beyond the set time.

Set points and dosing

Remote modification of the set points, of the dosing pump activation thresholds and of the corresponding hourly flow rate.

Inputs and outputs

Status of relays, pulse outputs, digital inputs and current outputs, with the name assigned to each connection.

Maintenance calendar

Tasks are scheduled by installation or by device and assigned to technicians; a reminder is sent by e-mail two days before the due date. Each task is shown as scheduled, due, overdue or completed.

Team and permissions

The main account has full access and creates the technicians’ accounts, each enabled only for the assigned installations and devices; the last login and activity of each technician are visible.

Reports and activity log

Reports on devices, tasks and technicians, downloadable in PDF or CSV with the customer’s logo; the log keeps the history of operations and disconnections.

Customisation

Logo, main colour and light or dark theme; the tiles on the main screen can be rearranged by dragging them. Two installations can be displayed side by side for comparison.

Guided registration

Each device is added through a guided procedure: the model is recognised automatically and associated with the installation, together with the technician to be contacted.

PLC integration

As an alternative to the portal, the Modbus RTU port allows integration into the plant supervision system.

NIMBUS portal: Real-time readings, counters and timers
Real-time readings, counters and timers
NIMBUS portal: Free chlorine and temperature trends
Free chlorine and temperature trends
NIMBUS portal: Set point and operating mode of each channel
Set point and operating mode of each channel
NIMBUS portal: Status of relays, pulses, inputs and mA outputs
Status of relays, pulses, inputs and mA outputs

Technical advice

Tell us the type of water, the volumes to be treated and the pH adjuster used: we will propose the most suitable electrode, probe holder, pump and accessories.

Contact

Tell us about your plant

Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.

What do you need?
Please enter your name.
Please enter a valid email address.
Please enter your message.

Describe your plant: type, water volume or flow rate, parameters to be controlled.

You must accept the privacy notice to continue.