Colour display
Multicolour backlit display that indicates the different operating states by changing colour. Programming via a single knob.
In water with a high impurity load the pH electrode, with a flat measuring membrane, is mounted in an immersion probe holder with a nozzle. At programmed intervals the controller suspends dosing and opens a solenoid valve that sends a jet of water or compressed air onto the electrode; afterwards it waits for the measurement to recover before resuming control. Cleaning is driven by the dedicated output of the PLUS version.
It acquires the measurement from the electrode and controls the dosing pump in proportion to the measured value.
Multicolour backlit display that indicates the different operating states by changing colour. Programming via a single knob.
Proportional, ON/OFF, PWM and PID dosing, with delayed dosing start.
Permanent data storage and a system log viewable on the display; the internal log can be exported to a USB memory stick for processing with a spreadsheet.
Chemical level, no flow, maximum dosing time exceeded, probe failure, out-of-range reading; audible or visual signalling via the alarm output.
By changing colour, the controller’s backlit display indicates the different operating states, which can be recognised even from a distance.
Measurement and dosing according to the set parameters.
Controller in stand-by.
Warning signal, for example the chemical level.
Alarm signal, for example from the probe.
The instrument is available in two versions, which differ in the number of inputs and outputs: the PLUS version adds the meter input, PID control, a second level input, a second dosing pump output, the 0-4/20 mA current loop outputs and the outputs for probe self-cleaning and for the circulation pump.
| BASIC | PLUS | |
|---|---|---|
| Measuring channels | 1 + temperature | 1 + temperature |
| Level inputs | 1 | 2 |
| Flow input | 1 | 1 |
| Stand-by input | 1 | 1 |
| Meter input | – | 1 |
| Outputs for pumps and loads (relays) | 1 (ON/OFF, PWM) | 2 (ON/OFF, PWM, PID) |
| Proportional outputs for dosing pumps | 1 | 2 |
| Alarm output | 1 | 1 |
| 0-4/20 mA current loop outputs | 2 on request | 3 |
| Probe self-cleaning output | – | 1 |
| Circulation pump output | – | 1 |
| Modbus RTU | ● | Optional |
| Ethernet, Wi-Fi, 4G, USB | Optional | Optional |
Inputs, outputs, control modes and alarms of the controller.
The electrode, with a flat measuring membrane kept clean by the water flow, is mounted in an immersion probe holder with nozzle: at programmed intervals the controller opens a solenoid valve that sends a jet of water or compressed air onto the electrode, removing deposits. During cleaning the pump outputs are disabled.
Single or double junction combination electrode, resistant to acids and bases, high temperatures and hydrofluoric acid, also suitable for low-conductivity water; available in a self-cleaning version.
pH electrodes →
In the immersion probe holder with nozzle, a jet of water or air keeps the electrode clean in water with a high impurity load.
Probe holders →
At programmed intervals the controller suspends dosing (stand-by) and opens the solenoid valve on the water or compressed air line: the jet comes out of the nozzle below the electrode tip and removes deposits. When cleaning is complete, the valve closes and, once the electrode repolarisation time has elapsed, dosing resumes.
| Electrode | Pressure | Connection | Body | Minimum conductivity | Junction | Temperature | Cable | Diameter | Notes |
|---|---|---|---|---|---|---|---|---|---|
| EpHS | 7 bar (3.5 bar) | BNC | Epoxy | 100 µS | – | 70 °C (80 °C) | 0.8 m | 12 mm | – |
| EpHM | 7 bar (3.5 bar) | BNC | Epoxy | 100 µS | – | 70 °C (80 °C) | 4.5 m | 12 mm | – |
| EpHL | 7 bar (3.5 bar) | BNC | Epoxy | 100 µS | – | 70 °C (80 °C) | 15 m | 12 mm | – |
| EpHSN6 | 7 bar (3.5 bar) | SN6 with PG13.5 thread | Epoxy | 100 µS | – | 70 °C (80 °C) | 1 – 100 m | 12 mm | – |
| EpHMD/100 | 7 bar | BNC | Epoxy | 100 µS | Double | 100 °C | 4.5 m | 12 mm | – |
| EpHM/D | 7 bar (3.5 bar) | BNC | Epoxy | 100 µS | Double | 70 °C (80 °C) | 4.5 m | 12 mm | – |
| EpHM/D/SN6 | 7 bar (3.5 bar) | SN6 with PG13.5 thread | Epoxy | 100 µS | Double | 70 °C (80 °C) | 1 – 100 m | 12 mm | – |
| EpHMD/LI | 7 bar (3.5 bar) | SN6 with PG13.5 thread | Epoxy | 3 µS | Double | 70 °C (80 °C) | 1 – 100 m | 12 mm | For low-conductivity water |
| EpHSC | 7 bar (3.5 bar) | BNC | Epoxy | 100 µS | Double | 70 °C (80 °C) | 4.5 m | 12 mm | Self-cleaning |
| EpHSC/SN6 | 7 bar (3.5 bar) | SN6 with PG13.5 thread | Epoxy | 100 µS | Double | 70 °C (80 °C) | 1 – 100 m | 12 mm | Self-cleaning |
| EpHM/HF | 7 bar (3.5 bar) | BNC | Epoxy | 100 µS | Double | 70 °C (80 °C) | 4.5 m | 12 mm | Resistant to 1% hydrofluoric acid |
| EpHSN6 GK | 10 bar | SN6 | Glass | 150 µS | – | −5 / 135 °C | 1 – 100 m | 12 mm | High temperature |
All models: combination electrode, range 0 – 14 pH, resolution 0.01.
The cleaning cycle is programmed on the controller with three times: the interval between two cleanings, the duration of the jet and the waiting time the electrode needs to return to a stable reading. During the cycle the pump outputs remain disabled.
| Setting | Value |
|---|---|
| Interval between two cleanings | 6 hours – 10 days |
| Cleaning duration | 0 – 999 seconds |
| Measurement recovery time | 0 – 999 minutes |
| Cleaning on threshold alarm | Can be enabled |
| Control output | Dedicated relay of the PLUS version, powered at 85 – 264 VAC, maximum 5 A |
| Feature | LDspH BASIC and PLUS |
|---|---|
| Measured parameter | pH, with temperature reading |
| Measuring range | 0 – 14 pH |
| Resolution | 0.01 pH |
| Temperature | 0 – 100 °C, resolution 0.1 °C |
| Temperature compensation | Automatic, with PT100 probe |
| Control modes | ON/OFF, proportional, PWM; PID in the PLUS version |
| Delayed dosing start | Up to 60 minutes |
| Relay outputs | 5 A at 230 VAC, fuse-protected |
| Power supply | 85 – 264 VAC, 50/60 Hz; 9 – 30 VDC optional |
| Average power consumption | 25 W |
| Display | RGB LCD display |
| Protection rating | IP65 |
| Housing | ABS |
| Weight | 1.45 kg |
| Mounting | Wall-mounted, with 4 fixing points |
| Ambient temperature | −10 – 50 °C |
| Relative humidity | 0 – 95 %, non-condensing |
The inputs and outputs of the BASIC and PLUS versions are given in the dedicated section and in the controller data sheet.
The controller is the core of the measuring and dosing system: for each application, the system page gives the composition, the installation diagram and the installation.
pH control with acid or base dosing in proportion to the measured value.
The system →
Batch pH neutralisation in a tank with filling, acid and base dosing, reaction and draining.
The system →
Control of pH and conductivity, with fertiliser and acid dosed by measurement or by volume.
The system →
Industrial water treatment ensures efficient processes, protects equipment and allows compliance with environmental regulations.
The sector →
Free chlorine or Redox and pH, with integrated or dedicated pumps.
The system →
In the food industry, safety and quality allow no compromise.
The sector →
Volumetric dosing, control of residual chlorine or Redox, chlorine dioxide, monochloramine and water supply networks.
The system →For plants with special requirements the system is defined on the characteristics of the plant: contact us.
The controllers support two-way remote access (read and write) through the web portal from a PC, tablet or smartphone: measurements can be viewed, set points, dosing and alarms changed, alarms received and logs downloaded. Alternatively, they can be integrated into your PLC via Modbus.
Connection to the web portal via network cable: measurements, set points, dosing and alarms accessible from a PC, tablet or smartphone.
Wireless connection to the web portal, with the same functions as the cable connection.
Connection via the 4G network for installations without a local network, with alarm notification by SMS or e-mail.
Web portalPC, tablet and smartphone
Integration into your PLC via serial port.
Current signal proportional to the measured value, for remote monitoring or for controlling pumps and other instrumentation.
Download of the logged data to a USB memory stick, for archiving and analysis with a spreadsheet.
One communication type at a time: Ethernet, Wi-Fi, 4G or Modbus RTU (built into the BASIC versions, optional on the PLUS versions). 0-4/20 mA current loop outputs standard on the PLUS versions, optional on the BASIC versions; meter input on the PLUS versions only.
A single account brings together all registered installations, each with its own devices: the web portal, free of charge and with no subscription, can be accessed from a PC, Mac, tablet or smartphone and allows every parameter to be both viewed and changed, with an encrypted connection and protected access.
On a single screen: probe readings, chemical levels, pump activation thresholds and active alarms, with the status of installations and devices (normal, warning, alarm, standby, not connected).
Installations appear on an interactive map with their status and open with a click; for each one, the local weather conditions and temperature are also shown.
Archive of measurements and alarms, available for consultation at any time with charts and numerical reports exportable in Excel format.
Alarm thresholds for readings, dosing, faulty probe and out-of-range readings, with notification by e-mail or SMS depending on the communication system; a warning is also issued when an installation remains disconnected beyond the set time.
Remote modification of the set points, of the dosing pump activation thresholds and of the corresponding hourly flow rate.
Status of relays, pulse outputs, digital inputs and current outputs, with the name assigned to each connection.
Tasks are scheduled by installation or by device and assigned to technicians; a reminder is sent by e-mail two days before the due date. Each task is shown as scheduled, due, overdue or completed.
The main account has full access and creates the technicians’ accounts, each enabled only for the assigned installations and devices; the last login and activity of each technician are visible.
Reports on devices, tasks and technicians, downloadable in PDF or CSV with the customer’s logo; the log keeps the history of operations and disconnections.
Logo, main colour and light or dark theme; the tiles on the main screen can be rearranged by dragging them. Two installations can be displayed side by side for comparison.
Each device is added through a guided procedure: the model is recognised automatically and associated with the installation, together with the technician to be contacted.
As an alternative to the portal, the Modbus RTU port allows integration into the plant supervision system.
Tell us the type of water, the volumes to be treated and the pH adjuster used: we will propose the most suitable electrode, probe holder, pump and accessories.
Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.