Skip to content
Systems for fire-fighting water tanks

WNpHRh

The WNpHRh controller measures pH and Redox potential with the electrodes immersed in the tank and controls two integrated stepper-motor peristaltic pumps for the acid and the hypochlorite, with Wi-Fi as standard.

  • pH and Redox
  • Two integrated peristaltic pumps
  • Wi-Fi as standard
WNpHRh
WNpHRh
Components

Basic components

WNpHRh controller

WNpHRh controller

It measures pH and Redox potential and controls two integrated stepper-motor peristaltic pumps, quiet and precise, one for the acid and one for the hypochlorite.

WNpHRh pump →
pH electrode

pH electrode

Combination electrode, 0 – 14 pH scale, with temperature compensation.

pH electrodes →
High-linearity Redox electrode

High-linearity Redox electrode

Combination electrode for measuring the Redox potential in drinking water.

Redox electrodes →
Injection lance

Injection lance

It introduces the product into the centre of the pipe, improving mixing; it can be withdrawn with the pipe under pressure.

Lances →
1

Electrodes in the tank

The pH and Redox electrodes are immersed in the fire-fighting water tank.

2

pH priority

The controller first adjusts the pH and only then doses the hypochlorite.

3

Periodic check

The correspondence between mV and free chlorine must be checked periodically with the colorimetric test.

4

Alarms

Product levels, maximum dosing time and faulty probe.

Colour display

Colour-coded status indication

The colour of the display changes according to the operating status, so that an alarm can be recognised even from a distance.

Display Green

Green

Normal operation according to the set parameters, no active alarms.

Display Yellow

Yellow

Non-blocking alarm, for example waiting for an external signal.

Display Red

Red

Blocking alarm, for example the chemical in the tank running out.

Display White

White

Pump stopped by an external control signal (stand-by).

Technical data

Probe data sheet

pH electrodes
ElectrodePressureConnectionBodyMinimum conductivityJunctionTemperatureCableDiameterNotes
EpHS7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)0.8 m12 mm–
EpHM7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)4.5 m12 mm–
EpHL7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)15 m12 mm–
EpHSN67 bar (3.5 bar)SN6 with PG13.5 threadEpoxy100 µS–70 °C (80 °C)1 – 100 m12 mm–
EpHMD/1007 barBNCEpoxy100 µSDouble100 °C4.5 m12 mm–
EpHM/D7 bar (3.5 bar)BNCEpoxy100 µSDouble70 °C (80 °C)4.5 m12 mm–
EpHM/D/SN67 bar (3.5 bar)SN6 with PG13.5 threadEpoxy100 µSDouble70 °C (80 °C)1 – 100 m12 mm–
EpHMD/LI7 bar (3.5 bar)SN6 with PG13.5 threadEpoxy3 µSDouble70 °C (80 °C)1 – 100 m12 mmFor low-conductivity water
EpHSC7 bar (3.5 bar)BNCEpoxy100 µSDouble70 °C (80 °C)4.5 m12 mmSelf-cleaning
EpHSC/SN67 bar (3.5 bar)SN6 with PG13.5 threadEpoxy100 µSDouble70 °C (80 °C)1 – 100 m12 mmSelf-cleaning
EpHM/HF7 bar (3.5 bar)BNCEpoxy100 µSDouble70 °C (80 °C)4.5 m12 mmResistant to 1% hydrofluoric acid
EpHSN6 GK10 barSN6Glass150 µS–−5 / 135 °C1 – 100 m12 mmHigh temperature

All models: combination electrode, range 0 – 14 pH, resolution 0.01.

Redox electrode
ERhHLB SN6
Range± 1,500 mV
Pressure6 bar
ConnectionSN6 with PG13.5 thread
BodyGlass
Minimum conductivity100 µS
Temperature80 °C
Cable10 m
Diameter12 mm
NotesHigh linearity and sensitivity, for low chlorine concentrations

All models: combination electrode, resolution 1 mV.

Other systems

Fire-fighting water tanks

The requirements of the sector and the comparison with the other systems available.

Systems for fire-fighting water tanks →
Remote control

Remote control

Wi-Fi is standard: from the web portal, free of charge and with no subscription, you can read the measurements, change set points and dosing and receive alarm notifications, from a PC, tablet or smartphone.

NIMBUS web portal for remote control of the systems

Wi-Fi

Wireless connection to the web portal, with the same functions as the cable connection.

The NIMBUS portal

A single account brings together all registered installations, each with its own devices: the web portal, free of charge and with no subscription, can be accessed from a PC, Mac, tablet or smartphone and allows every parameter to be both viewed and changed, with an encrypted connection and protected access.

The NIMBUS portal on monitor, laptop, tablet and smartphone

Overview

On a single screen: probe readings, chemical levels, pump activation thresholds and active alarms, with the status of installations and devices (normal, warning, alarm, standby, not connected).

Installation map

Installations appear on an interactive map with their status and open with a click; for each one, the local weather conditions and temperature are also shown.

History and charts

Archive of measurements and alarms, available for consultation at any time with charts and numerical reports exportable in Excel format.

Alarms and notifications

Alarm thresholds for readings, dosing, faulty probe and out-of-range readings, with notification by e-mail or SMS depending on the communication system; a warning is also issued when an installation remains disconnected beyond the set time.

Set points and dosing

Remote modification of the set points, of the dosing pump activation thresholds and of the corresponding hourly flow rate.

Inputs and outputs

Status of relays, pulse outputs, digital inputs and current outputs, with the name assigned to each connection.

Maintenance calendar

Tasks are scheduled by installation or by device and assigned to technicians; a reminder is sent by e-mail two days before the due date. Each task is shown as scheduled, due, overdue or completed.

Team and permissions

The main account has full access and creates the technicians’ accounts, each enabled only for the assigned installations and devices; the last login and activity of each technician are visible.

Reports and activity log

Reports on devices, tasks and technicians, downloadable in PDF or CSV with the customer’s logo; the log keeps the history of operations and disconnections.

Customisation

Logo, main colour and light or dark theme; the tiles on the main screen can be rearranged by dragging them. Two installations can be displayed side by side for comparison.

Guided registration

Each device is added through a guided procedure: the model is recognised automatically and associated with the installation, together with the technician to be contacted.

NIMBUS portal: Real-time readings, counters and timers
Real-time readings, counters and timers
NIMBUS portal: Free chlorine and temperature trends
Free chlorine and temperature trends
NIMBUS portal: Set point and operating mode of each channel
Set point and operating mode of each channel
NIMBUS portal: Status of relays, pulses, inputs and mA outputs
Status of relays, pulses, inputs and mA outputs

Technical advice

Describe your plant and the flow rate of water to be treated: we will size the controller, pumps and accessories.

Contact

Tell us about your plant

Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.

What do you need?
Please enter your name.
Please enter a valid email address.
Please enter your message.

Describe your plant: type, water volume or flow rate, parameters to be controlled.

You must accept the privacy notice to continue.