Skip to content
Measuring and dosing systems

pH and Redox

The system continuously measures the pH and the Redox potential (ORP) of the water with two electrodes and drives the dosing pumps of the pH corrector and of the disinfectant up to their set points. Redox, expressed in mV, indicates the oxidising power of the water: it is an indirect measurement, which makes the system the most economical solution for linking disinfectant dosing to a continuous measurement together with pH.

  • pH and Redox in mV
  • Two electrodes with BNC connector
  • pH control priority
  • In by-pass, in-line or immersion
LDpHRh system on a panel with two dosing pumps and probe holder
pH and Redoxthe system
Panel with LDpHRh controller, dosing pumps, filter and probe holder
On a panel
How it works

pH correction and disinfectant dosing

The two electrodes, immersed in the storage tank or in a flow-through probe holder, transmit the pH and the Redox potential to the controller; each channel drives its own dosing pump with independent set points.

Layout of a dual-parameter system on a water storage tank: controller, immersed electrodes, two dosing pumps with the product tanks, two injection points and booster pump
1

pH channel

The controller drives the acid or alkali pump in proportion to the deviation from the set point; the reading is temperature-compensated.

2

Redox channel

The potential is positive in the presence of oxidants, such as chlorine, and decreases as the disinfectant is consumed: between the set values the controller progressively reduces the pump strokes, stopping it at the set point.

3

pH priority

Priority can be given to pH control, with disinfectant control starting only afterwards: with chlorine as the disinfectant, the Redox potential depends directly on pH.

The Redox system →
Components

Basic components

The system consists of the dual-channel controller, the two electrodes, the dosing pumps for the two products and the injection accessories; it is also available pre-assembled on a panel.

LDpHRh controller

LDpHRh controller

It reads the two electrodes from the BNC connectors and the temperature from the PT100 probe, and drives the pumps and the flocculant output.

The controller →
Combined Redox electrode

pH and Redox electrodes

One combined electrode for pH, from 0 to 14 pH, and one for the Redox potential, from −1,000 to +1,000 mV with 1 mV resolution.

VMS MF dosing pump

Dosing pumps

One solenoid diaphragm pump for the pH corrector and one for the disinfectant, driven by the proportional outputs of the controller.

Dosing pumps →
Injection lance

Injection lances

They introduce the products into the centre of the pipe, improving mixing, and can be withdrawn with the pipe under pressure.

Lances →
Operation

Checks and alarms

Alarms

For each parameter the controller signals maximum or minimum reading reached, set point not reached within the set time, an electrode showing the same reading for too long and product depletion.

Flow

With the electrodes in by-pass, the flow sensor stops dosing when no water circulates in the probe holder.

Flocculant

A powered output drives the flocculant pump, active except in stand-by and flow alarm.

Applications

Fields of application

Private swimming pools

Private swimming pools

Control of pH and disinfection by measuring the Redox potential, a simple and economical solution for private swimming pools.

Private swimming pools →
Drinking water

Drinking water

pH correction and maintenance of the disinfecting power in water from wells, springs and storage tanks.

Drinking water systems →
Installation

Probe positioning

Probe positioning is defined according to the characteristics of the installation and of the water to be analysed.

PEF flow-through probe holder and NPED probe holder

In a bypass line

The probes are housed in a PEF flow-through probe holder or an NPED probe holder, connected to a sampling point at the tank outlet and fed with about 30 l/h of sample water. A flow sensor can be added, which stops dosing when there is no flow.

Probe holders →
Immersion probe holder

Immersion

The electrode is immersed directly in the storage tank of the water to be treated, by means of an immersion probe holder.

Probe holders →
Immersion probe holder with cleaning nozzle

Immersion with cleaning

A solution suited to water with a high solids load: at programmed intervals the control panel puts the controller in stand-by and opens a solenoid valve that sends water or air to the nozzle; once cleaning is complete, it closes the valve and, after the electrode repolarisation time has elapsed, resumes dosing.

Probe holders →
In-line probe holder

In-line

The electrodes are inserted directly into the pipe carrying the water to be treated.

Probe holders →
The controller

The LDpHRh controller

LDpHRh system on a panel with two dosing pumps and probe holder

LDpHRh

Measuring ranges, resolution, inputs, outputs, display and connections are given in the controller data sheet.

Remote control

System remote control

The controllers support two-way remote access (read and write) through the web portal from a PC, tablet or smartphone: measurements can be viewed, set points, dosing and alarms changed, alarms received and logs downloaded. Alternatively, they can be integrated into your PLC via Modbus.

Ethernet

Connection to the web portal via network cable: measurements, set points, dosing and alarms accessible from a PC, tablet or smartphone.

Optional (one only)

Wi-Fi

Wireless connection to the web portal, with the same functions as the cable connection.

Optional (one only)

4G

Connection via the 4G network for installations without a local network, with alarm notification by SMS or e-mail.

Optional (one only)
NIMBUS web portal for remote control of the systemsWeb portalPC, tablet and smartphone

Modbus RTU

Integration into your PLC via serial port.

Standard (BASIC), optional (PLUS)

0-4/20 mA current loop output

Current signal proportional to the measured value, for remote monitoring or for controlling pumps and other instrumentation.

Optional (3 outputs)

USB port

Download of the logged data to a USB memory stick, for archiving and analysis with a spreadsheet.

Optional

One communication type at a time: Ethernet, Wi-Fi, 4G or Modbus RTU (built into the BASIC versions, optional on the PLUS versions). 0-4/20 mA current loop outputs optional; meter input on the PLUS versions only.

The NIMBUS portal

A single account brings together all registered installations, each with its own devices: the web portal, free of charge and with no subscription, can be accessed from a PC, Mac, tablet or smartphone and allows every parameter to be both viewed and changed, with an encrypted connection and protected access.

The NIMBUS portal on monitor, laptop, tablet and smartphone

Overview

On a single screen: probe readings, chemical levels, pump activation thresholds and active alarms, with the status of installations and devices (normal, warning, alarm, standby, not connected).

Installation map

Installations appear on an interactive map with their status and open with a click; for each one, the local weather conditions and temperature are also shown.

History and charts

Archive of measurements and alarms, available for consultation at any time with charts and numerical reports exportable in Excel format.

Alarms and notifications

Alarm thresholds for readings, dosing, faulty probe and out-of-range readings, with notification by e-mail or SMS depending on the communication system; a warning is also issued when an installation remains disconnected beyond the set time.

Set points and dosing

Remote modification of the set points, of the dosing pump activation thresholds and of the corresponding hourly flow rate.

Inputs and outputs

Status of relays, pulse outputs, digital inputs and current outputs, with the name assigned to each connection.

Maintenance calendar

Tasks are scheduled by installation or by device and assigned to technicians; a reminder is sent by e-mail two days before the due date. Each task is shown as scheduled, due, overdue or completed.

Team and permissions

The main account has full access and creates the technicians’ accounts, each enabled only for the assigned installations and devices; the last login and activity of each technician are visible.

Reports and activity log

Reports on devices, tasks and technicians, downloadable in PDF or CSV with the customer’s logo; the log keeps the history of operations and disconnections.

Customisation

Logo, main colour and light or dark theme; the tiles on the main screen can be rearranged by dragging them. Two installations can be displayed side by side for comparison.

Guided registration

Each device is added through a guided procedure: the model is recognised automatically and associated with the installation, together with the technician to be contacted.

PLC integration

As an alternative to the portal, the Modbus RTU port allows integration into the plant supervision system.

NIMBUS portal: Real-time readings, counters and timers
Real-time readings, counters and timers
NIMBUS portal: Free chlorine and temperature trends
Free chlorine and temperature trends
NIMBUS portal: Set point and operating mode of each channel
Set point and operating mode of each channel
NIMBUS portal: Status of relays, pulses, inputs and mA outputs
Status of relays, pulses, inputs and mA outputs

Technical advice

Tell us about the plant and the products used: we will propose the most suitable electrodes, pumps and accessories.

Contact

Tell us about your plant

Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.

What do you need?
Please enter your name.
Please enter a valid email address.
Please enter your message.

Describe your plant: type, water volume or flow rate, parameters to be controlled.

You must accept the privacy notice to continue.