Solenoid dosing pump

TMS Rh

Diaphragm dosing pump with a built-in Redox controller, for automatic measurement and control of the Redox potential (ORP) over the 0 – 1,000 mV range with flow rates up to 100 l/h; the electrode, ordered separately, connects directly to the pump. Display, level control and stand-by input are standard. A self-purging version and a P version for liquids up to 50,000 cP are also available.

  • Built-in Redox controller
  • 0 – 1,000 mV range
  • Up to 20 bar
  • Up to 100 l/h
TMS Rh dosing pump
100l/hMaximum flow rate
20barMaximum pressure
16Configurations
50,000cPMaximum viscosity (P version)
The model

TMS Rh

TMS Rh dosing pump
Integrated Redox meter

TMS Rh

With integrated Redox meter for control of the Redox potential (ORP).

  • Proportional to Redox
  • Automatic Redox dosing
Compatible components
ERhS ERhSRedox (ORP) electrode

Pump head: PVDF, PP, PMMA or AISI 316L

Operation

Dosing modes

Proportional to Redox

The required Redox potential (ORP) (SET POINT) is set: the pump measures it by means of a Redox electrode and progressively reduces the injection frequency as the measured value approaches the set point, stopping when the SET POINT is reached.

Automatic Redox dosing

Once the pool volume has been set, the pump automatically adjusts dosing according to the required Redox potential (ORP) (SET POINT), measured by means of a Redox electrode: the injection frequency is progressively reduced as the measured value approaches the set point, until the pump stops when the SET POINT is reached.

Technical data

Performance and configurations

The pump code is made up of the model name and the performance: maximum pressure in bar as two digits followed by the flow rate in l/h (TMS Rh 0515 = 5 bar, 15 l/h). It is followed by the pump head code and the power supply code, listed in the tables at the end of this section. Performance varies with the working back pressure and with the characteristics of the chemical.

Manual air bleed

Suitable for most chemicals: the standard configuration for the most common applications.

CodeMax pressure (bar)Max flow rate (l/h)Delivery tube (mm)Suction tube (mm)cc per stroke
TMS Rh 20052054 x 64 x 60.7
TMS Rh 05155156 x 86 x 82.1
TMS Rh 04204206 x 86 x 82.8
TMS Rh 03303308 x 108 x 124.2
TMS Rh 01501508 x 108 x 127
TMS Rh 00100010012 x 18 (braided PVC)12 x 18 (braided PVC)14

Automatic air bleed

Required with chemicals that release gas (e.g. peroxides), to prevent the pump from becoming air-locked.

CodeMax pressure (bar)Max flow rate (l/h)Delivery tube (mm)Suction tube (mm)cc per stroke
TMSA Rh 203.2203.24 x 64 x 60.44
TMSA Rh 05105106 x 86 x 81.39
TMSA Rh 04134136 x 86 x 81.8
TMSA Rh 03203208 x 108 x 122.78
TMSA Rh 01351358 x 108 x 124.86

High-viscosity liquids

For chemicals with a viscosity between 8,000 and 50,000 cP.

CodeMax pressure (bar)Max flow rate (l/h)Delivery tube (mm)Suction tube (mm)cc per stroke
TMSP Rh 06016116 x 2220 x 270.14
TMSP Rh 04034316 x 2220 x 270.42
TMSP Rh 02082816 x 2220 x 271.2
TMSP Rh 012012016 x 2220 x 272.8
TMSP Rh 002502516 x 2220 x 273.5

Nominal flow rate measured with water at room temperature. The P version is supplied without injection valve, level probe and foot filter.

Technical specifications

SpecificationValue
StrokesUp to 120 per minute; up to 150 per minute on the P 0601 model
Maximum chemical viscosity100 cP; 8,000 cP with the $ pump head; 50,000 cP in the P version
Average power draw at maximum flow rate (manual and automatic air bleed)27 W at 230 VAC and 21 W at 115 VAC; on models 0515 and 0510, 15 W at 115 VAC and 14 W at 24 VAC and 24 VDC
Protection ratingIP65
Noise level62.0 dB(A); 57.4 dB(A) in the P version
Weight5.7 kg; 5 kg in the P version (5.7 kg for model 0120)
HousingPP
MountingVertical, or horizontal with the dedicated bracket
Ambient temperature0 – 45 °C; 10 – 45 °C in the P version
Product temperature0 – 50 °C
Transport and storage temperature−10 – 50 °C
Relative humidity85 % up to 40 °C, 70 % at 45 °C, non-condensing
Maximum altitude2,000 m a.s.l.
Installation categoryII
Pollution degree2

Pump head codes

HeadMaterialO-ringsValvesBallsDelivery tubeSuction tubeMax viscosity (cP)
KPVDFFKMPVDFCeramicPVDFPVC100
PPVDFEPDMPVDFCeramicPVDFPVC100
WPVDFNBRPVDFCeramicPVDFPVC100
VPPFKM–CeramicPEPVC100
DPPEPDM–CeramicPEPVC100
TPVDFFKM + PTFEPVDFCeramicPVDFPVC100
APMMAFKMPVDFCeramicPVDFPVC100
ZAISI 316LFKMAISI 316LAISI 316L––100
$PMMAFKMPPStainless steel, Hastelloy springPEPVC8,000
B (P version)PMMAFKMPPPTFE, Hastelloy springPVCPVC50,000

PTFE diaphragm for all pump heads. The tube size may vary with the pump head material; with low-viscosity liquids the $ pump head may reduce the flow rate.

Power supply codes

CodePower supply
00230 VAC, Schuko plug
0S230 VAC, Australian plug
01230 VAC, no plug
03115 VAC, US plug
0424 VAC, no plug
0512 VDC (some models only)
0724 VDC

In the P version only codes 00, 0S, 01 and 03 are available.

Supplied with

  • Level probe with PVDF axial foot filter
  • Delivery, suction and drain tubes (2 m each)
  • Stand-by signal cable (2.5 m)
  • 5 × 20 time-delay fuse
  • Mounting kit (wall plugs and screws)
  • Operating manual

Pump head materials

Pump head in PVDF

PVDF

Suitable for most acids, for peroxides and for sodium hypochlorite (chlorine).

Pump head in PP

PP

Suitable for sodium hydroxide (caustic soda).

Pump head in AISI 316L

AISI 316L

Suitable for peracetic acid and sodium hydroxide.

Pump head in PMMA

PMMA

Suitable for medium and high viscosity substances.

Learn more: chemical compatibility of materials →

Special versions

Special versions

In addition to the standard configuration, versions dedicated to particular applications are available; the performance of each is given in the technical data. The pages by application compare the suitable pumps of all the series.

TA and TMSA Series

TA and TMSA Series

Self-venting pump head, required with chemicals that release gas (e.g. sodium hypochlorite and peroxides): it vents the gas and prevents the pump from locking.

Technical support

Troubleshooting and error messages

The most frequent causes of malfunction and the corrective actions to check before contacting technical support.

Learn more: the pump does not prime and does not dose →

If the pump…

The pump strokes normally, but the chemical is not dosed
  • Air in the hydraulic circuitCheck fittings and tubing, tighten any loose ones and bleed the air.
  • Suction tube emptiedThe pump has lost its prime: repeat the priming procedure.
  • Foot filter cloggedRemove the lance or filter from the tank and clean it.
  • Gas released by the chemicalOpen the bleed valve to discharge the gas; if this recurs, fit a self-bleeding pump head.
No strokes, or weak and damped stroke
  • Valve balls blocked by crystallisation of the chemicalClean the valves and run the pump with 2 – 3 litres of water instead of the chemical; if the problem persists, replace the valves.
  • Injection valve cloggedReplace the injection valve.
The pump does not switch on
  • No power supplyCheck the mains connection and that the voltage matches the rated value.
  • Protection fuse blownReplace the fuse with one of the same rating.
  • Faulty circuit boardThe board must be replaced: contact our technical support service.

Display of the TMS pH and Rh

MessageMeaningAction
LOW LEVELProduct running low in the tank.Refill the tank.
LOW VOLTThe mains voltage is lower than the rated voltage.Check the power supply.
HIGH VOLThe mains voltage is higher than the rated voltage.Check the power supply.
DOSING · AL OFFThe maximum dosing time alarm (1 – 100 minutes) has been triggered.In STOP mode the pump remains stopped: press any key to restart it and check why the value does not reach the set point.
CALIB ERRORProbe calibration failed.Repeat the calibration, strictly following the procedure.
STAND-BYThe pump is completing the waiting phase.No action required.
DATA SAVEDThe data have been saved.No action required.

Flow rate between 30 and 100%

Adjustment is linear between 30 and 100%: below 30% the actual flow rate may differ from the expected one and must therefore be checked.

Priming

Connect all the tubing, open the bleed valve and set the adjustment to 100%; start the pump and close the bleed valve as soon as the chemical comes out. With viscous liquids the operation can be assisted with a 20 cc syringe applied to the bleed port.

Factory settings

With the pump switched off, hold down both arrow keys and restore power: LOAD DEFAULT appears and the programming is reset to the factory values (password 0000).

If the problem persists, contact us. Before sending the pump for servicing, empty the pump head of chemical and dry it.

Summary

Main features

Electronic flow rate adjustment

According to the operating mode and the set parameters, the pump automatically adapts the injection frequency to ensure the required dosing.

Digital display

The integrated LCD display allows the pump to be programmed and its operating status to be monitored at all times.

Level control

The pump is supplied with a low-level probe for the tank: when the chemical runs out, it shows the alarm on the display and activates the corresponding output.

Stand-by

Pump start and stop can be controlled remotely by means of a run/stop contact from a PLC or another source.

Alarm output

In the event of a fault, a volt-free contact is activated, configurable as normally open (N.O.) or normally closed (N.C.), to drive a visual or audible signalling device, send an SMS or report the event to a PLC.

Priming button

A dedicated button allows the lines to be filled with the chemical to be dosed.

Versatile mounting

Vertical installation, or horizontal installation by means of a dedicated bracket.

Technical advice

Tell us about your application: our technical staff will recommend the most suitable model, configuration and accessories.

Contact

Tell us about your plant

Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.

What do you need?
Please enter your name.
Please enter a valid email address.
Please enter your message.

Describe your plant: type, water volume or flow rate, parameters to be controlled.

You must accept the privacy notice to continue.