AMS pH
With integrated pH meter for automatic pH control.
- Proportional to pH
- Automatic pH dosing
Diaphragm dosing pump with an integrated instrument for measuring and automatically controlling pH, over the range from 0 to 14 pH, for flow rates up to 60 l/h and back pressures up to 25 bar. The pH electrode is not included and is chosen to suit the installation; display, level control and stand-by input are standard.
The required pH value (SET POINT) is set: the pump measures the pH by means of a pH electrode and progressively reduces the injection frequency as the measured value approaches the set point, stopping when the SET POINT is reached.
Once the pool volume has been set, the pump automatically adjusts dosing according to the required pH (SET POINT), measured by means of a pH electrode: the injection frequency is progressively reduced as the measured value approaches the set point, until the pump stops when the SET POINT is reached.
The pump code is made up of the model name and the performance: maximum pressure in bar as two digits followed by the flow rate in l/h (AMS pH 2505 = 25 bar, 5 l/h). It is followed by the pump head code and the power supply code, listed in the tables at the end of this section. Performance varies with the working back pressure and with the characteristics of the chemical.
Suitable for most chemicals: the standard configuration for the most common applications.
| Code | Max pressure (bar) | Max flow rate (l/h) | Delivery tube (mm) | Suction tube (mm) | cc per stroke |
|---|---|---|---|---|---|
| AMS pH 2505 | 25 | 5 | 4 x 6 | 4 x 6 | 0.7 |
| AMS pH 1510 | 15 | 10 | 4 x 6 | 4 x 6 | 1.4 |
| AMS pH 1015 | 10 | 15 | 6 x 8 | 6 x 8 | 2.08 |
| AMS pH 0720 | 7 | 20 | 6 x 8 | 6 x 8 | 2.8 |
| AMS pH 0340 | 3 | 40 | 8 x 10 | 8 x 12 | 5.6 |
| AMS pH 0260 | 2 | 60 | 8 x 10 | 8 x 12 | 7.7 |
Tube sizes may vary with the pump head material. The cc per stroke refer to the mechanical stroke adjustment set at 100%.
Required with chemicals that release gas (e.g. peroxides), to prevent the pump from becoming air-locked.
| Code | Max pressure (bar) | Max flow rate (l/h) | Delivery tube (mm) | Suction tube (mm) |
|---|---|---|---|---|
| AMSA pH 253.2 | 25 | 3.2 | 4 x 6 | 4 x 6 |
| AMSA pH 1506 | 15 | 6 | 4 x 6 | 4 x 6 |
| AMSA pH 1010 | 10 | 10 | 6 x 8 | 6 x 8 |
| AMSA pH 0713 | 7 | 13 | 6 x 8 | 6 x 8 |
| AMSA pH 0330 | 3 | 30 | 8 x 10 | 8 x 12 |
| AMSA pH 0238 | 2 | 38 | 8 x 10 | 8 x 12 |
For chemicals with a viscosity between 100 and 8,000 cP.
| Code | Max pressure (bar) | Max flow rate (l/h) |
|---|---|---|
| AMS pH LPV 2505 | 25 | 5 |
| AMS pH LPV 1510 | 15 | 10 |
| AMS pH LPV 1015 | 10 | 15 |
| AMS pH LPV 0720 | 7 | 20 |
| AMS pH LPV 0340 | 3 | 40 |
| AMS pH LPV 0260 | 2 | 60 |
Nominal flow rate measured with water at room temperature. The pump head is made of PMMA with manual air bleed; the package includes a 3/4” injection valve, a 16 x 22 PVC suction tube and an 8 x 12 PE delivery tube.
For chemicals with a viscosity between 8,000 and 50,000 cP.
| Code | Max pressure (bar) | Max flow rate (l/h) | cc per stroke |
|---|---|---|---|
| AMS P pH 0802 | 8 | 2 | 0.28 |
| AMS P pH 0604 | 6 | 4 | 0.56 |
| AMS P pH 0410 | 4 | 10 | 1.4 |
| AMS P pH 0425 | 4 | 25 | 3.5 |
| AMS P pH 0140 | 1 | 40 | 5.6 |
Nominal flow rate measured with water at room temperature: with viscous liquids the flow rate is lower. 20 x 27 suction tube and 16 x 22 delivery tube, 1” suction valve and 3/4” delivery valve; this version is supplied without injection valve, level probe and foot filter.
| Specification | Value |
|---|---|
| Strokes per minute | From 1 stroke per hour to 120 strokes per minute |
| Linearity of the mechanical adjustment | From 30 to 100% |
| Average power draw at maximum flow rate | 42 W at 230 VAC; 24 W at 115 VAC |
| Peak current | 2.5 A |
| Maximum chemical viscosity | 100 cP; 8,000 cP with the pump head for viscous liquids |
| Maximum suction height | 1.5 m |
| Ambient temperature | 10 – 45 °C |
| Chemical temperature | 0 – 50 °C |
| Transport and storage temperature | 10 – 50 °C |
| Relative humidity | 85% up to 40 °C, 70% at 45 °C, non-condensing |
| Maximum altitude | 2,000 m |
| Protection rating | IP65 |
| Noise level | 57.4 dB(A) |
| Weight | 9 kg |
| Housing | PP |
| Mounting | Horizontal, floor or wall |
Values for the standard version and the automatic air bleed version.
| Specification | AMS P pH |
|---|---|
| Maximum chemical viscosity | 50,000 cP |
| Strokes per minute | From 1 stroke per hour to 120 strokes per minute |
| Average power draw at maximum flow rate | 42 W at 230 VAC |
| Compressed air supply | — |
| Ambient temperature | 10 – 45 °C |
| Transport and storage temperature | 10 – 50 °C |
| Noise level | 78.3 dB(A) |
| Weight | 9 kg |
| Electrical power supplies | Codes 00, 0S, 01 and 03 |
| Code | Pump head | Seals | Valves | Balls | Max viscosity (cP) |
|---|---|---|---|---|---|
| K | PVDF | FKM B | PVDF | Ceramic | 100 |
| P | PVDF | EPDM | PVDF | Ceramic | 100 |
| Y | PVDF | NBR | PVDF | Ceramic | 100 |
| V | PP | FKM B | PP | Ceramic | 100 |
| D | PP | EPDM | PP | Ceramic | 100 |
| J | PVDF | FKM B + PTFE | PVDF | Ceramic | 100 |
| A | PMMA | FKM B | PVDF | Ceramic | 100 |
| Z | AISI 316L | FKM B | AISI 316L | AISI 316L | 100 |
| $ | PMMA | FKM B | PP | Stainless steel, Hastelloy spring | 8,000 |
| B (AMS P) | PMMA | FKM B | PP | PTFE, Hastelloy spring | 50,000 |
PTFE diaphragm in all versions. The delivery tube is PVDF, or PE with PP pump heads and with code $; the suction tube is PVC. The stainless steel pump head (Z) is supplied without tubes.
| Code | Power supply |
|---|---|
| 00 | 230 VAC, Schuko plug |
| 0S | 230 VAC, Australian plug |
| 01 | 230 VAC, no plug |
| 03 | 115 VAC, US plug |
| 04 | 24 VAC, no plug |
| 05 | 12 VDC (some models only) |
| 07 | 24 VDC |
| Power supply | Voltage range | Fuse |
|---|---|---|
| 230 VAC | 190 – 265 VAC | 1.25 A |
| 115 VAC | 90 – 135 VAC | 1.6 A |
| 24 VAC | 20 – 32 VAC | 6.3 A |
| 12 VDC | 10 – 16 VDC | 5 A |
Suitable for most acids, for peroxides and for sodium hypochlorite (chlorine).
Suitable for sodium hydroxide (caustic soda).
Suitable for peracetic acid and sodium hydroxide.
Suitable for medium and high viscosity substances.
In addition to the standard configuration, versions dedicated to particular applications are available; the performance of each is given in the technical data. The pages by application compare the suitable pumps of all the series.
Self-venting pump head, required with chemicals that release gas (e.g. sodium hypochlorite and peroxides): it vents the gas and prevents the pump from locking.
For chemicals with a viscosity between 100 and 8,000 cP.
PMMA pump head for high-viscosity liquids, from 8,000 to 50,000 cP.
The most frequent causes of malfunction and the corrective actions to check before contacting technical support.
Learn more: the pump does not prime and does not dose →Adjustment is linear between 30 and 100%: below 30% the actual flow rate may differ from the expected one and must therefore be checked.
Connect all the tubing, open the bleed valve and set the adjustment to 100%; start the pump and close the bleed valve as soon as the chemical comes out. With viscous liquids the operation can be assisted with a 20 cc syringe applied to the bleed port.
If the problem persists, contact us. Before sending the pump for servicing, empty the pump head of chemical and dry it.
According to the operating mode and the set parameters, the pump automatically adapts the injection frequency to ensure the required dosing.
The knob reduces the stroke length of the diaphragm, i.e. the volume of each injection and, consequently, the maximum flow rate. This offers two advantages:
Linear dosing: a high number of small-volume injections promotes mixing of the chemical into the water flow and avoids concentration peaks.
Accuracy at low dosing rates: with a 10 l/h pump required to dose 1 l/h, reducing the stroke length to 50% brings the maximum flow rate down to 5 l/h and doubles the injection frequency. Particularly suitable in combination with the pulse-output water meter.
The integrated LCD display allows the pump to be programmed and its operating status to be monitored at all times.
The pump is supplied with a low-level probe for the tank: when the chemical runs out, it shows the alarm on the display and activates the corresponding output.
Pump start and stop can be controlled remotely by means of a run/stop contact from a PLC or another source.
In the event of a fault, a volt-free contact is activated, configurable as normally open (N.O.) or normally closed (N.C.), to drive a visual or audible signalling device, send an SMS or report the event to a PLC.
A dedicated button allows the lines to be filled with the chemical to be dosed.
Horizontal installation, or vertical installation by means of a dedicated bracket.
Tell us about your application: our technical staff will recommend the most suitable model, configuration and accessories.
Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.