Proportional chlorine
Below 0.100 mg/l the pump doses at maximum frequency, 180 pulses per minute; as chlorine rises the frequency decreases, until it stops at 0.500 mg/l.
The system measures and controls free chlorine and the electrical conductivity of the water in a single controller, and also reads its temperature. Chlorine is dosed in proportion to the distance from the desired value; conductivity, which increases with dissolved salts, is controlled ON/OFF between two thresholds and drives up to two dosing pumps or a motorised bleed valve.
The controller displays the two measurements, the status of the outputs and the temperature, and controls each channel with its own set points; it also records the data in an internal archive.
Below 0.100 mg/l the pump doses at maximum frequency, 180 pulses per minute; as chlorine rises the frequency decreases, until it stops at 0.500 mg/l.
Above 2.00 mS the output switches on, for example opening the bleed valve; it switches off when the reading falls to 1.50 mS and switches on again only when the reading returns to the activation threshold.
The PT100 temperature probe, integrated in the conductivity probe, allows the measurement to be compensated automatically, also with custom correction coefficients.
The system consists of the dual-channel controller, the chlorine cell with the flow-through probe holder, the conductive or inductive conductivity probe, and the dosing pumps or bleed valve driven by the outputs.
It reads the chlorine cell and the conductivity probe with the temperature, and drives dosing pumps and motorised valves according to the measured values.
LD dual-channel controllers →
Closed SCL amperometric cell, with resolution down to 0.001 mg/l and ranges of 0–0.5, 0–2 or 0–20 mg/l depending on the cell; alternatively the self-cleaning SCL18.
Amperometric cells →
Conductive, with full scale up to 200 mS, or inductive ECDINDPT up to 300 mS: it is chosen according to the characteristics of the water.
Conductivity probes →
Solenoid diaphragm pumps for chlorine and for the products of the conductivity channel, driven by the pulse outputs of the controller.
Dosing pumps →Free chlorine is measured with a closed amperometric cell, chosen according to the temperature and quality of the water.
The electrodes are protected by a selective membrane that excludes contaminants from the measurement; pH and temperature compensation is automatic. The galvanic part, the only one subject to wear, can be regenerated without replacing the electronics.
Amperometric cells →Closed amperometric cell without membrane, for hot water and high pressure: up to 70 °C and 8 bar, 5 bar in the probe holder. The ball self-cleaning system removes scale, making the cell less sensitive to fouling.
Amperometric cells →Conductivity is measured with two different principles: the probe is chosen according to the water to be analysed and the required range.
Body in PVDF, AISI 316L stainless steel or Epoxy, with graphite, stainless steel or platinum electrodes and automatic temperature compensation; the full scale, up to 200 mS, is set from the menu.
Conductive probes →It has no electrodes in contact with the water: it is not affected by polarisation, does not foul and also measures in still water. The 0.3–3, 0.3–30 and 0.3–300 mS ranges are set from the menu.
Inductive probe →The chlorine cell and the conductivity probe are installed in flow-through probe holders connected in by-pass to the circuit; the conductivity probe must be oriented so that the flow strikes its tip, to prevent air bubbles and sediment deposits that would alter the reading.
In PMMA, with 6 × 8 mm fittings, flow regulator, flow sensor and sampling tap; upstream the 5" NFIL filter with 60 micron washable cartridges.
Probe holders →
For the conductive probes: rigid PP head and transparent SAN bowl, up to 5 bar and 50 °C; alternatively the probe can be installed by immersion in the tank.
Probe holders →
For the inductive probe, with an alignment notch to orient it correctly with respect to the flow; alternatively the PEL-IND in-line or the PEC-IND immersion probe holder.
Probe holders →
The chlorine channel controls the disinfection of the recirculating water, while the conductivity channel drives the motorised bleed valve when the salt concentration exceeds the set threshold.
Evaporative towers →
In industrial circuits the system controls disinfection and water salinity together; it is also supplied in a cabinet or on a skid.
Process water →
Available parameter combinations, BASIC and PLUS versions, display and connections of the dual-channel controllers are given on the series page.
The controllers support two-way remote access (read and write) through the web portal from a PC, tablet or smartphone: measurements can be viewed, set points, dosing and alarms changed, alarms received and logs downloaded. Alternatively, they can be integrated into your PLC via Modbus.
Connection to the web portal via network cable: measurements, set points, dosing and alarms accessible from a PC, tablet or smartphone.
Wireless connection to the web portal, with the same functions as the cable connection.
Connection via the 4G network for installations without a local network, with alarm notification by SMS or e-mail.
Web portalPC, tablet and smartphone
Integration into your PLC via serial port.
Current signal proportional to the measured value, for remote monitoring or for controlling pumps and other instrumentation.
Download of the logged data to a USB memory stick, for archiving and analysis with a spreadsheet.
One communication type at a time: Ethernet, Wi-Fi, 4G or Modbus RTU (built into the BASIC versions, optional on the PLUS versions). 0-4/20 mA current loop outputs optional; meter input on the PLUS versions only.
A single account brings together all registered installations, each with its own devices: the web portal, free of charge and with no subscription, can be accessed from a PC, Mac, tablet or smartphone and allows every parameter to be both viewed and changed, with an encrypted connection and protected access.
On a single screen: probe readings, chemical levels, pump activation thresholds and active alarms, with the status of installations and devices (normal, warning, alarm, standby, not connected).
Installations appear on an interactive map with their status and open with a click; for each one, the local weather conditions and temperature are also shown.
Archive of measurements and alarms, available for consultation at any time with charts and numerical reports exportable in Excel format.
Alarm thresholds for readings, dosing, faulty probe and out-of-range readings, with notification by e-mail or SMS depending on the communication system; a warning is also issued when an installation remains disconnected beyond the set time.
Remote modification of the set points, of the dosing pump activation thresholds and of the corresponding hourly flow rate.
Status of relays, pulse outputs, digital inputs and current outputs, with the name assigned to each connection.
Tasks are scheduled by installation or by device and assigned to technicians; a reminder is sent by e-mail two days before the due date. Each task is shown as scheduled, due, overdue or completed.
The main account has full access and creates the technicians’ accounts, each enabled only for the assigned installations and devices; the last login and activity of each technician are visible.
Reports on devices, tasks and technicians, downloadable in PDF or CSV with the customer’s logo; the log keeps the history of operations and disconnections.
Logo, main colour and light or dark theme; the tiles on the main screen can be rearranged by dragging them. Two installations can be displayed side by side for comparison.
Each device is added through a guided procedure: the model is recognised automatically and associated with the installation, together with the technician to be contacted.
As an alternative to the portal, the Modbus RTU port allows integration into the plant supervision system.
Tell us the temperature and quality of the water, the required conductivity range and the products to be dosed: we will propose the most suitable cell, probe, pumps and accessories.
Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.