Continuous measurement
The SCT cell, installed in a flow-through probe holder, continuously analyses the treated water. Its membrane excludes free chlorine, chlorine dioxide and chlorates, so that the reading concerns chlorites only.
The system continuously measures chlorites, by-products of disinfection with chlorine dioxide, by means of a closed amperometric cell with selective membrane. When the set threshold is exceeded, the controller generates an alarm and stops chlorine dioxide dosing, and it allows the concentration in the treated water to be checked at any time.
In water disinfected with chlorine dioxide, the system adds the chlorite measurement to that of the disinfectant: a threshold is set and the controller acts automatically when the concentration exceeds it.

The SCT cell, installed in a flow-through probe holder, continuously analyses the treated water. Its membrane excludes free chlorine, chlorine dioxide and chlorates, so that the reading concerns chlorites only.
The chlorite concentration above which the controller must act is set; the measured value always remains visible on the display and is stored.
When the threshold is exceeded, the controller generates an alarm and stops chlorine dioxide dosing.
The system is supplied pre-assembled on a panel, ready for connection to the installation.
It acquires the chlorite measurement from the cell, compares it with the set threshold and operates the alarm and the dosing stop.
The controller →
It is a closed amperometric cell with selective membrane, dedicated to chlorites, with automatic temperature compensation.
The SCT cell →
It is made of PMMA, with sample flow rate adjustment and flow sensor, which signals when there is no circulation. A filter with washable cartridge is installed upstream.
Probe holders →The water to be analysed flows through the flow-through probe holder, in a bypass line on the installation, and returns to the circuit or storage tank.
The system works alongside the chlorine dioxide dosing system, which it acts on by stopping dosing when the threshold is exceeded.
In addition to the chlorite threshold, the controller signals out-of-range readings, a faulty probe and no flow in the probe holder, also via the alarm output.
In water intended for human consumption disinfected with chlorine dioxide, the system allows continuous checking of the chlorite concentration.
Drinking water systems →
In domestic water circuits treated with chlorine dioxide, chlorite control accompanies the measurement of the disinfectant.
Anti-Legionella →Controller, filter and probe holder are supplied mounted on a panel, to be connected in a bypass line to the water circuit to be monitored: the photo shows a panel with LDsCL controller, dosing pumps, filter and amperometric cell in the flow-through probe holder.

Systems are supplied pre-assembled and tested, in the form best suited to the plant room: on a panel, in a cabinet or on a skid (with cover, in a box or on a frame), or custom-built. Some examples are shown below.
Controller, pumps, probe holder and accessories mounted and wired on a wall panel.
System panel and chemical tanks housed in a single cabinet.
Pipework, pumps and electrical panel in a wall cabinet with door.
Skid with raised stainless steel frame and protective PMMA cover.
Skid enclosed in a box with door, with the chemical tanks at the base.
Skid on a frame with doors, pre-assembled and ready for connection.
Dosing pump mounted directly on the tank: the most compact solution.
Wall installation in the plant room, with the chemical tanks on the floor.
Pumps, controllers or components supplied by the customer can also be fitted, with custom dimensions, back panel and electrical panel. Dosing stations and skids →

Measuring range, resolution, cell and controller characteristics, display and remote control are described on the controller page.
The controllers support two-way remote access (read and write) through the web portal from a PC, tablet or smartphone: measurements can be viewed, set points, dosing and alarms changed, alarms received and logs downloaded. Alternatively, they can be integrated into your PLC via Modbus.
Connection to the web portal via network cable: measurements, set points, dosing and alarms accessible from a PC, tablet or smartphone.
Wireless connection to the web portal, with the same functions as the cable connection.
Connection via the 4G network for installations without a local network, with alarm notification by SMS or e-mail.
Web portalPC, tablet and smartphone
Integration into your PLC via serial port.
Current signal proportional to the measured value, for remote monitoring or for controlling pumps and other instrumentation.
Download of the logged data to a USB memory stick, for archiving and analysis with a spreadsheet.
One communication type at a time: Ethernet, Wi-Fi, 4G or Modbus RTU (built into the BASIC versions, optional on the PLUS versions). 0-4/20 mA current loop outputs standard on the PLUS versions, optional on the BASIC versions; meter input on the PLUS versions only.
A single account brings together all registered installations, each with its own devices: the web portal, free of charge and with no subscription, can be accessed from a PC, Mac, tablet or smartphone and allows every parameter to be both viewed and changed, with an encrypted connection and protected access.
On a single screen: probe readings, chemical levels, pump activation thresholds and active alarms, with the status of installations and devices (normal, warning, alarm, standby, not connected).
Installations appear on an interactive map with their status and open with a click; for each one, the local weather conditions and temperature are also shown.
Archive of measurements and alarms, available for consultation at any time with charts and numerical reports exportable in Excel format.
Alarm thresholds for readings, dosing, faulty probe and out-of-range readings, with notification by e-mail or SMS depending on the communication system; a warning is also issued when an installation remains disconnected beyond the set time.
Remote modification of the set points, of the dosing pump activation thresholds and of the corresponding hourly flow rate.
Status of relays, pulse outputs, digital inputs and current outputs, with the name assigned to each connection.
Tasks are scheduled by installation or by device and assigned to technicians; a reminder is sent by e-mail two days before the due date. Each task is shown as scheduled, due, overdue or completed.
The main account has full access and creates the technicians’ accounts, each enabled only for the assigned installations and devices; the last login and activity of each technician are visible.
Reports on devices, tasks and technicians, downloadable in PDF or CSV with the customer’s logo; the log keeps the history of operations and disconnections.
Logo, main colour and light or dark theme; the tiles on the main screen can be rearranged by dragging them. Two installations can be displayed side by side for comparison.
Each device is added through a guided procedure: the model is recognised automatically and associated with the installation, together with the technician to be contacted.
As an alternative to the portal, the Modbus RTU port allows integration into the plant supervision system.
Describe your plant and the chlorine dioxide dosing system: we will propose the most suitable controller, cell and accessories.
Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.