MTOWER 1CH
Conductivity and temperature: bleed-off, antiscalant, two biocides and two activators.
MTOWER 1CH →The MTOWER 1CH controller, supplied on a panel with the dosing pumps, the probe holder, the motorised bleed-off valve and the make-up and bleed-off water meters. Conductivity (contacting or inductive probe) and temperature. Bleed-off, antiscalant, two biocides and two activators, with 2 water meter inputs and 6 inputs for product levels.
The controller manages bleed-off, antiscalant, two biocides (one on the PLUS model) and two activators with external pumps; two water meters measure make-up and bleed-off.

System components, supplied mounted and wired on a panel.
Conductivity and temperature: bleed-off, antiscalant, two biocides and two activators.
MTOWER 1CH →
Probe holder for cooling towers: water sampling, chemical injection and bleed-off via a motorised valve.
Manifold →
Electrode probes for the conductivity of the tower water, with temperature compensation.
Contacting probes →
Free from polarisation and largely insensitive to fouling, they also measure in the absence of flow.
Inductive probes →
Antiscalant, biodispersant, biocides and activators, driven by the controller.
Dosing pumps →
They measure the make-up and bleed-off water; the make-up water meter controls the antiscalant dosing.
Water meters →Probes that can be connected to the MTOWER 1CH. Selecting a probe shows its technical features and its data sheet.
MTOWER 1CH
ECDC0 – 20 · 0 – 200 mS
ECDI0 – 200 µS · 0 – 500 µS · 0 – 5 mS
ECDHL0 – 200 µS · 0.2 – 20 · 20 – 200 mS
EICDC0 – 20 µS · 0 – 200 µS · 0 – 20 mS
ECDINDPT0.3 – 3 · 0.3 – 30 · 0.3 – 300 mS
ECDSINDPT0.3 – 10 mS
Pulse-output water meterPulse input · turbine or Woltmann
Choose a probe: its characteristics appear below.

0 – 20 · 0 – 200 mS
PVDF body and graphite electrodes. Range up to 0 – 200 mS, in-line, in a bypass line or immersion.
PVDF body, graphite electrodes.
| Model | Mounting | Connection | Range | K factor | Temperature compensation |
|---|---|---|---|---|---|
| ECDC/1 | In-line / bypass | R3/4" | 0 – 20 mS | 1 | – |
| ECDCC/1 | In-line / bypass | R3/4" | 0 – 20 mS | 1 | NTC 10K |
| ECDCCPT/1 | In-line / bypass | R3/4" | 0 – 20 mS | 1 | PT100 |
| ECDC/10 | In-line / bypass | R3/4" | 0 – 200 mS | 10 | – |
| ECDCC/10 | In-line / bypass | R3/4" | 0 – 200 mS | 10 | NTC 10K |
| ECDCCPT/10 | In-line / bypass | R3/4" | 0 – 200 mS | 10 | PT100 |
| ECDCIM/1 | Immersion | G1/2" | 0 – 20 mS | 1 | – |
| ECDCCIM/1 | Immersion | G1/2" | 0 – 20 mS | 1 | NTC 10K |
| ECDCCIMPT/1 | Immersion | G1/2" | 0 – 20 mS | 1 | PT100 |
| ECDCIM/10 | Immersion | G1/2" | 0 – 200 mS | 10 | – |
| ECDCCIM/10 | Immersion | G1/2" | 0 – 200 mS | 10 | NTC 10K |
| ECDCCIMPT/10 | Immersion | G1/2" | 0 – 200 mS | 10 | PT100 |
Operating temperature 1 – 60 °C (100 °C at 2 bar), operating pressure 7 bar (2 bar at 100 °C).
Probe data sheet →
0 – 200 µS · 0 – 500 µS · 0 – 5 mS
PVDF body and stainless steel electrodes. For low-conductivity water, from 0 – 200 µS to 0 – 5 mS.
PVDF body, stainless steel electrodes.
| Model | Mounting | Connection | Range | K factor | Temperature compensation |
|---|---|---|---|---|---|
| ECDI/1 | In-line / bypass | R3/4" | 0 – 5 mS | 1 | – |
| ECDIC/1 | In-line / bypass | R3/4" | 0 – 5 mS | 1 | NTC 10K |
| ECDICPT/1 | In-line / bypass | R3/4" | 0 – 5 mS | 1 | PT100 |
| ECDI/01 | In-line / bypass | R3/4" | 0 – 200 µS | 0.1 | – |
| ECDIC/01 | In-line / bypass | R3/4" | 0 – 200 µS | 0.1 | NTC 10K |
| ECDICPT/01 | In-line / bypass | R3/4" | 0 – 200 µS | 0.1 | PT100 |
| ECDIIM/1 | Immersion | G1/2" | 0 – 5 mS | 1 | – |
| ECDICIM/1 | Immersion | G1/2" | 0 – 5 mS | 1 | NTC 10K |
| ECDICPTIM/1 | Immersion | G1/2" | 0 – 5 mS | 1 | PT100 |
| ECDIIM/01 | Immersion | G1/2" | 0 – 200 µS | 0.1 | – |
| ECDIIM/02 | Immersion | G1/2" | 0 – 500 µS | 0.2 | – |
| ECDICIM/01 | Immersion | G1/2" | 0 – 200 µS | 0.1 | NTC 10K |
| ECDICPTIM/01 | Immersion | G1/2" | 0 – 200 µS | 0.1 | PT100 |
Operating temperature 1 – 60 °C (100 °C at 2 bar), operating pressure 7 bar (2 bar at 100 °C).
Probe data sheet →
0 – 200 µS · 0.2 – 20 · 20 – 200 mS
Epoxy body and platinum electrodes, with high-linearity measurement over wide measuring ranges.
Epoxy body, platinum electrodes, diameter 12 mm.
| Model | Mounting | Range | K factor | Temperature compensation |
|---|---|---|---|---|
| ECDHL/1 | In-line / bypass | 0.2 – 20 mS | 1 | – |
| ECDHLC/1 | In-line / bypass | 0.2 – 20 mS | 1 | NTC 10K |
| ECDHLCPT/1 | In-line / bypass | 0.2 – 20 mS | 1 | PT100 |
| ECDHL/01 | In-line / bypass | 0 – 200 µS | 0.1 | – |
| ECDHLC/01 | In-line / bypass | 0 – 200 µS | 0.1 | NTC 10K |
| ECDHLCPT/01 | In-line / bypass | 0 – 200 µS | 0.1 | PT100 |
| ECDHL/10 | In-line / bypass | 20 – 200 mS | 10 | – |
| ECDHLC/10 | In-line / bypass | 20 – 200 mS | 10 | NTC 10K |
| ECDHLCPT/10 | In-line / bypass | 20 – 200 mS | 10 | PT100 |
Operating temperature 1 – 70 °C, operating pressure 7 bar.
Probe data sheet →
0 – 20 µS · 0 – 200 µS · 0 – 20 mS
Stainless steel body and electrodes, for water at high temperature and/or pressure: up to 200 °C and 15 bar.
Stainless steel body and electrodes, R3/4" connection, in-line or bypass mounting.
| Model | Range | K factor | Temperature compensation | Operating temperature |
|---|---|---|---|---|
| EICDC/1 | 0 – 20 mS | 1 | NTC 10K | 1 – 130 °C |
| EICDCPT/1 | 0 – 20 mS | 1 | PT100 | 1 – 130 °C |
| EICDC/01 | 0 – 200 µS | 0.1 | NTC 10K | 1 – 130 °C |
| EICDCPT/01 | 0 – 200 µS | 0.1 | PT100 | 1 – 130 °C |
| EICDC/001 | 0 – 20 µS | 0.01 | NTC 10K | 1 – 130 °C |
| EICDCPT/001 | 0 – 20 µS | 0.01 | PT100 | 1 – 130 °C |
| EICDCHPT/1 | 0 – 20 mS | 1 | PT100 | 1 – 200 °C |
| EICDCHPT/01 | 0 – 200 µS | 0.1 | PT100 | 1 – 200 °C |
| EICDCHPT/001 | 0 – 20 µS | 0.01 | PT100 | 1 – 200 °C |
Operating pressure 15 bar.
Probe data sheet →
0.3 – 3 · 0.3 – 30 · 0.3 – 300 mS
ECDINDPT probes measure conductivity according to the inductive principle: the reading is more stable as it is unaffected by polarisation and deposits. Suitable for all types of water, including hot water, high-pressure water and water containing suspended solids. Measuring ranges 0.3 – 3, 0.3 – 30 and 0.3 – 300 mS.
| ECDINDPT | |
|---|---|
| Measuring range | 0.3 – 3 mS 0.3 – 30 mS 0.3 – 300 mS |
| Measuring system | Inductive |
| Body | PEEK |
| Mounting | In-line / bypass / immersion |
| Temperature compensation | PT100 |
| Operating temperature | 1 – 85 °C (100 °C for short periods) |
| Operating pressure | 8 bar |

0.3 – 10 mS
ECDSINDPT probes measure conductivity according to the inductive principle: the reading is more stable as it is unaffected by polarisation and deposits. Suitable for all types of water, including hot water, high-pressure water and water containing suspended solids. Measuring range 0.3 – 10 mS.
| ECDSINDPT | |
|---|---|
| Measuring range | 0.3 – 10 mS |
| Measuring system | Inductive |
| Body | PEEK |
| Mounting | In-line / bypass / immersion |
| Temperature compensation | PT100 |
| Operating temperature | 1 – 85 °C (100 °C for short periods) |
| Operating pressure | 8 bar |

Pulse input · turbine or Woltmann
Pulse-output water meter, connected to an input of the controller: it sends pulses according to the litres of water measured, so that the chemical can be dosed in proportion to the water treated. Turbine or Woltmann type, for cold and hot water.
| Turbine | Woltmann | |
|---|---|---|
| Cold water | Max 30 °C | Max 60 °C |
| Hot water | Max 90 °C | Max 130 °C |
| Dial | Wet or dry | Dry |
| Special finish | PTFE-coated inside and outside | PTFE-coated inside and outside |
| Pressure | 16 bar | 16 bar |
| Connections | Threaded | Flanged (2" also threaded) |
| Jet | Single (multi-jet for 2") | – |
When the conductivity set point is reached, the controller opens the drain valve, with opening delay, dead band and safety timer (timeout): beyond the set time the drain closes and the alarm is triggered.
Inputs for pulse-output water meters: counting of make-up and drain volumes and control of the cycles of concentration.
The antiscalant is dosed in proportion to the make-up water (via a water meter or at constant ppm), together with the bleed-off or for a percentage of its duration.
Management of two different biocides with daily or weekly scheduling, alternated to prevent microorganisms from adapting to a single product.
Two outputs dedicated to pre-biocides, dosed for the set time before the biocide: they generally act as activators of the subsequent dosing.
Before biocide dosing the controller opens the drain, on a timed basis or down to a lower conductivity value; with conductivity-based pre-bleed, the bleed-off timeout applies.
After biocide dosing the drain remains inhibited for the set time, so as to ensure the necessary contact time and prevent loss of chemical through the drain.
In the absence of flow in the probe holder (circulation pump stopped), dosing is suspended and the alarm is triggered.
Antiscalant dosing modes and biocide programmes set on the controller.
The antiscalant pump runs for the entire time the bleed-off valve is open.
At the end of bleed-off the pump doses for a percentage of its duration: with 10 minutes of bleed-off at 50%, 5 minutes of dosing.
The pump runs for a percentage of a cycle time: with a 1-hour cycle at 50% it doses for 30 minutes.
When a preset number of water meter pulses is reached, the pump doses for a set time, for example 30 minutes every 50 pulses.
The litres per pulse of the water meter, the ppm to be maintained, the product concentration and the volume of each injection are set; the controller calculates the dosing.
Each biocide has a dedicated programme, on a 4-week or daily cycle, with pre-bleed, activator, lock-out and optional start of the circulation pump; with a dedicated probe the biocide can also be dosed according to the measurement.
| MTOWER 1CH | |
|---|---|
| Parameters | Conductivity |
| Contacting conductivity | 0 – 300 µS … 0 – 300 mS |
| Inductive conductivity | 0 – 3, 30 or 300 mS |
| Temperature compensation | A single temperature probe |
| Inputs | 5 levels, 2 water meters, flow, temperature, stand-by |
| Outputs | 2 proportional (inhibitor and biodispersant); mA output on request |
| Alarms | Flow, 2 levels, bleed-off timeout |
Optional communication, one chosen from USB, Ethernet, 4G, Wi-Fi and Modbus, and optional 0-4/20 mA current loop output. Measurements are temperature-compensated; probes are ordered separately.
Controller, probes, pumps, bleed-off valve and water meters are supplied mounted and wired, ready for connection: management is centralised in a single point and operators do not come into contact with the chemicals.
Panel-mounted MTOWER (or Centurio Tower) for bleed-off valve management, measurement and dosing, with measurement of make-up water and bleed-off; also with 2 dosing pumps, manifold and 1" bleed-off valve. Conductivity, pH, Redox or pH and Redox versions, with contacting or inductive probe.
Up to 3 conductivity measurements and 3 bleed-off lines (expandable to 6) with 4 pumps: one for the antiscalant on the make-up water and three for the biocides. Or three measurements (conductivity, pH and Redox) with measuring pipework, 1 1/4" bleed-off and 4 injection points.
Centurio Tower with up to 6 measurements (conductivity, pH, Redox, tracer, corrosion and turbidity), water meter and valve on the panel, 1 1/4" bleed-off, 4 pumps; separate panels for turbidity and for double or triple corrosion. Modular configuration: probes, valves and pumps can be added or removed.
Stainless steel or plastic skids, boxes with protective screen or window, electrical panels for the entire system: electrical connections and pipework prepared for installation.
Skid →Pumps, controllers or components supplied by the customer can also be mounted, with customised dimensions, back panel, logo and electrical panel.

Conductivity, with contacting or inductive probe, and temperature: bleed-off, antiscalant, two biocides and two activators.
| Feature | MTOWER 1CH |
|---|---|
| Measuring channels | 1 (conductivity) |
| Measuring range | Depending on the probes |
| Water meters: make-up and bleed-off | 2 |
| Proportional outputs | 2 (inhibitor and biodispersant) |
| Outputs for pumps and loads | 6, plus the bleed-off relay and the alarm output |
| Display | Backlit graphic LCD |
| Connections | 4G, Ethernet, USB port, Wi-Fi, Modbus RTU: optional (one only); 0-4/20 mA current loop output: optional |
The needs of the sector, how the tower works and the comparison between the systems are on the cooling towers page.
Systems for cooling towers →
The most complete solution: channel 1 for conductivity (contacting or inductive), other channels for pH, Redox, chlorine and biocides, tracer, corrosion, turbidity and mA inputs. Ethernet, Wi-Fi and Modbus as standard; 230 VAC or 12 – 24 VDC power supply.
The Centurio Tower system →
Three simultaneous parameters: conductivity, pH and chlorine (CD pH CL) or conductivity, pH and Redox (CD pH Rh), plus temperature. mA output and 12 or 24 VDC power supply on request.
The MTOWER PLUS system →
Conductivity plus a second parameter of choice: pH (CD pH), Redox (CD Rh) or free chlorine, bromine or another biocide (CD CL). mA output and 12 or 24 VDC power supply on request.
The MTOWER 2CH system →
The most compact solution: conductivity, bleed-off and two integrated pumps (antiscalant and biocide), peristaltic or solenoid, with colour display, Bluetooth and Wi-Fi.
WT EM →
The most compact solution: conductivity, bleed-off and two integrated pumps (antiscalant and biocide), peristaltic or solenoid, with colour display, Bluetooth and Wi-Fi.
WT PER →The controllers support two-way remote access (read and write) through the web portal from a PC, tablet or smartphone: measurements can be viewed, set points, dosing and alarms changed, alarms received and logs downloaded. Alternatively, they can be integrated into your PLC via Modbus.
Connection to the web portal via network cable: measurements, set points, dosing and alarms accessible from a PC, tablet or smartphone.
Wireless connection to the web portal, with the same functions as the cable connection.
Connection via the 4G network for installations without a local network, with alarm notification by SMS or e-mail.
Web portalPC, tablet and smartphone
Integration into your PLC via serial port.
Integration into your PLC or SCADA via Ethernet network.
Current signal proportional to the measured value, for remote monitoring or for controlling pumps and other instrumentation.
A single account brings together all registered installations, each with its own devices: the web portal, free of charge and with no subscription, can be accessed from a PC, Mac, tablet or smartphone and allows every parameter to be both viewed and changed, with an encrypted connection and protected access.
On a single screen: probe readings, chemical levels, pump activation thresholds and active alarms, with the status of installations and devices (normal, warning, alarm, standby, not connected).
Installations appear on an interactive map with their status and open with a click; for each one, the local weather conditions and temperature are also shown.
Archive of measurements and alarms, available for consultation at any time with charts and numerical reports exportable in Excel format.
Alarm thresholds for readings, dosing, faulty probe and out-of-range readings, with notification by e-mail or SMS depending on the communication system; a warning is also issued when an installation remains disconnected beyond the set time.
Remote modification of the set points, of the dosing pump activation thresholds and of the corresponding hourly flow rate.
Status of relays, pulse outputs, digital inputs and current outputs, with the name assigned to each connection.
Tasks are scheduled by installation or by device and assigned to technicians; a reminder is sent by e-mail two days before the due date. Each task is shown as scheduled, due, overdue or completed.
The main account has full access and creates the technicians’ accounts, each enabled only for the assigned installations and devices; the last login and activity of each technician are visible.
Reports on devices, tasks and technicians, downloadable in PDF or CSV with the customer’s logo; the log keeps the history of operations and disconnections.
Logo, main colour and light or dark theme; the tiles on the main screen can be rearranged by dragging them. Two installations can be displayed side by side for comparison.
Each device is added through a guided procedure: the model is recognised automatically and associated with the installation, together with the technician to be contacted.
As an alternative to the portal, the Modbus RTU or TCP/IP port allows integration into the plant supervision system.
Tell us the characteristics of the tower, the recirculation flow rate and the products used: we will size probes, pumps and panel, supplied assembled and tested.
Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.