The MTOWER 1CH controls the cooling tower on the basis of conductivity alone, measured with a contacting or inductive probe and temperature compensated. It drives the bleed-off valve, doses antiscalant and biodispersant through two proportional outputs and manages two biocides with their activators according to two independent programmes.

  • Contacting or inductive conductivity
  • Proportional antiscalant and biodispersant
  • Two biocides and two activators
  • Two programmes over 1, 2 or 4 weeks
MTOWER 1CH controller showing the conductivity reading
MTOWER 1CH
1Measuring channel (conductivity)
2Proportional outputs
2 + 2Biocides and activators
IP65Protection rating
Functions

What the controller manages

Antiscalant and biocide programming →
1

Bleed-off

Opening of the bleed-off valve when the conductivity set point is exceeded, with opening delay, dead band, maximum bleed-off time and manual control.

2

Antiscalant

Dosing linked to bleed-off (Feed & Bleed, Feed & % Bleed), to a percentage of time (Feed & % Time) or to the make-up volume measured by the water meter, or at a constant ppm.

3

Biocides

Two biocides (one on the PLUS version) and two activators on a weekly programme, on a 4-week cycle, or daily; in the versions with Redox or chlorine the biocide can also be dosed according to the measurement.

4

Pre-bleed

Before the biocide and the activator, the controller bleeds off water, for a set time or down to the set conductivity.

5

Lock-out

After the biocide has been dosed, bleed-off remains blocked for the set time, so that the chemical acts without being lost to bleed-off.

The model

MTOWER 1CH

MTOWER 1CH controller with conductivity reading
Conductivity

MTOWER 1CH

Conductivity, with contacting or inductive probe to be specified when ordering, and temperature. Bleed-off, antiscalant, two biocides and two activators.

Inputs and outputs

Inputs, outputs and alarms

Inputs

  • 5 chemical level inputs
  • 2 water meter inputs: make-up and bleed-off
  • Flow input
  • Input for one temperature probe
  • Stand-by input

Outputs

  • Bleed-off valve control
  • Proportional outputs for inhibitor and biodispersant
  • Control of the pumps for 2 biocides and 2 activators
  • Alarm output
  • mA output on request

Alarms

  • No water flow
  • 2 chemical level alarms
  • Bleed-off timeout

The probes are not included and are chosen according to the installation.

Display

Display

Settings

Bleed-off set point, antiscalant mode, biocide and activator programmes, pre-bleed and lock-out are set from the controller or remotely from the web portal.

Technical data

Technical data

The conductivity probe, contacting or inductive, is specified when ordering; the measuring range depends on the probe chosen.

Technical specifications

FeatureMTOWER 1CH
Measured parametersConductivity and temperature
Contacting conductivity0 – 300 µS … 0 – 300 mS
Inductive conductivity0 – 3, 30 or 300 mS
Inputs5 levels, 2 water meters, flow, temperature, stand-by
Proportional outputs2: inhibitor and biodispersant
Biocides and activators2 + 2
Biocide programmesTimer 1 and Timer 2, over 1, 2 or 4 weeks
AlarmsFlow, 2 levels, bleed-off timeout
Average power consumptionAbout 20 W
Antiscalant modesFeed and bleed, feed as a percentage of bleed-off, feed as a percentage of time, with water meter for a set time or with water meter at constant ppm
Temperature probes1, compensating all measurements
DisplayBacklit graphic LCD display
CommunicationOptional, one of USB, Ethernet, 4G, Wi-Fi and Modbus; 0-4/20 mA output optional
Power supply90 – 265 VAC, 50/60 Hz; 12 or 24 VDC on request
Protection ratingIP65 (NEMA 4X)
HousingABS
Dimensions325 × 255 × 118 mm
Ambient temperature−10 – 50 °C
Relative humidity0 – 95 %, non-condensing

The probes are not included and are ordered separately, according to the installation.

Probe data sheets

Contacting probes – ECDC

PVDF body, graphite electrodes.

ModelMountingConnectionRangeK factorTemperature compensation
ECDC/1In-line / bypassR3/4"0 – 20 mS1–
ECDCC/1In-line / bypassR3/4"0 – 20 mS1NTC 10K
ECDCCPT/1In-line / bypassR3/4"0 – 20 mS1PT100
ECDC/10In-line / bypassR3/4"0 – 200 mS10–
ECDCC/10In-line / bypassR3/4"0 – 200 mS10NTC 10K
ECDCCPT/10In-line / bypassR3/4"0 – 200 mS10PT100
ECDCIM/1ImmersionG1/2"0 – 20 mS1–
ECDCCIM/1ImmersionG1/2"0 – 20 mS1NTC 10K
ECDCCIMPT/1ImmersionG1/2"0 – 20 mS1PT100
ECDCIM/10ImmersionG1/2"0 – 200 mS10–
ECDCCIM/10ImmersionG1/2"0 – 200 mS10NTC 10K
ECDCCIMPT/10ImmersionG1/2"0 – 200 mS10PT100

Operating temperature 1 – 60 °C (100 °C at 2 bar), operating pressure 7 bar (2 bar at 100 °C).

Contacting probes – ECDI

PVDF body, stainless steel electrodes.

ModelMountingConnectionRangeK factorTemperature compensation
ECDI/1In-line / bypassR3/4"0 – 5 mS1–
ECDIC/1In-line / bypassR3/4"0 – 5 mS1NTC 10K
ECDICPT/1In-line / bypassR3/4"0 – 5 mS1PT100
ECDI/01In-line / bypassR3/4"0 – 200 µS0.1–
ECDIC/01In-line / bypassR3/4"0 – 200 µS0.1NTC 10K
ECDICPT/01In-line / bypassR3/4"0 – 200 µS0.1PT100
ECDIIM/1ImmersionG1/2"0 – 5 mS1–
ECDICIM/1ImmersionG1/2"0 – 5 mS1NTC 10K
ECDICPTIM/1ImmersionG1/2"0 – 5 mS1PT100
ECDIIM/01ImmersionG1/2"0 – 200 µS0.1–
ECDIIM/02ImmersionG1/2"0 – 500 µS0.2–
ECDICIM/01ImmersionG1/2"0 – 200 µS0.1NTC 10K
ECDICPTIM/01ImmersionG1/2"0 – 200 µS0.1PT100

Operating temperature 1 – 60 °C (100 °C at 2 bar), operating pressure 7 bar (2 bar at 100 °C).

Contacting probes – ECDHL

Epoxy body, platinum electrodes, diameter 12 mm.

ModelMountingRangeK factorTemperature compensation
ECDHL/1In-line / bypass0.2 – 20 mS1–
ECDHLC/1In-line / bypass0.2 – 20 mS1NTC 10K
ECDHLCPT/1In-line / bypass0.2 – 20 mS1PT100
ECDHL/01In-line / bypass0 – 200 µS0.1–
ECDHLC/01In-line / bypass0 – 200 µS0.1NTC 10K
ECDHLCPT/01In-line / bypass0 – 200 µS0.1PT100
ECDHL/10In-line / bypass20 – 200 mS10–
ECDHLC/10In-line / bypass20 – 200 mS10NTC 10K
ECDHLCPT/10In-line / bypass20 – 200 mS10PT100

Operating temperature 1 – 70 °C, operating pressure 7 bar.

Contacting probes – EICDC

Stainless steel body and electrodes, R3/4" connection, in-line or bypass mounting.

ModelRangeK factorTemperature compensationOperating temperature
EICDC/10 – 20 mS1NTC 10K1 – 130 °C
EICDCPT/10 – 20 mS1PT1001 – 130 °C
EICDC/010 – 200 µS0.1NTC 10K1 – 130 °C
EICDCPT/010 – 200 µS0.1PT1001 – 130 °C
EICDC/0010 – 20 µS0.01NTC 10K1 – 130 °C
EICDCPT/0010 – 20 µS0.01PT1001 – 130 °C
EICDCHPT/10 – 20 mS1PT1001 – 200 °C
EICDCHPT/010 – 200 µS0.1PT1001 – 200 °C
EICDCHPT/0010 – 20 µS0.01PT1001 – 200 °C

Operating pressure 15 bar.

Inductive probes
ECDINDPTECDSINDPT
Measuring range0.3 – 3 mS
0.3 – 30 mS
0.3 – 300 mS
0.3 – 10 mS
Measuring systemInductiveInductive
BodyPEEKPEEK
MountingIn-line / bypass / immersionIn-line / bypass / immersion
Temperature compensationPT100PT100
Operating temperature1 – 85 °C (100 °C for short periods)1 – 85 °C (100 °C for short periods)
Operating pressure8 bar8 bar
Complete systems

Complete systems with MTOWER

The controller is the core of the measuring and dosing system: the system page gives the composition, the installation diagram and the installation.

Cooling towers

Cooling towersCooling towers

The MTOWER is supplied pre-assembled on a panel or on a frame with probe holder, bleed-off valve, dosing pumps and water meters; the page also describes the programming of the antiscalant and biocides.

The system →
Summary

Main features

Conductivity-based bleed-off

When the conductivity set point is reached, the controller opens the drain valve, with opening delay, dead band and safety timer (timeout): beyond the set time the drain closes and the alarm is triggered.

Metered make-up and bleed-off

Inputs for pulse-output water meters: counting of make-up and drain volumes and control of the cycles of concentration.

Antiscalant proportional to make-up

The antiscalant is dosed in proportion to the make-up water (via a water meter or at constant ppm), together with the bleed-off or for a percentage of its duration.

Two alternating biocides

Management of two different biocides with daily or weekly scheduling, alternated to prevent microorganisms from adapting to a single product.

Pre-biocides (activators)

Two outputs dedicated to pre-biocides, dosed for the set time before the biocide: they generally act as activators of the subsequent dosing.

Pre-bleed

Before biocide dosing the controller opens the drain, on a timed basis or down to a lower conductivity value; with conductivity-based pre-bleed, the bleed-off timeout applies.

Drain lock-out

After biocide dosing the drain remains inhibited for the set time, so as to ensure the necessary contact time and prevent loss of chemical through the drain.

Flow control

In the absence of flow in the probe holder (circulation pump stopped), dosing is suspended and the alarm is triggered.

Remote control

System remote control

The controllers support two-way remote access (read and write) through the web portal from a PC, tablet or smartphone: measurements can be viewed, set points, dosing and alarms changed, alarms received and logs downloaded. Alternatively, they can be integrated into your PLC via Modbus.

4G

Connection via the 4G network for installations without a local network, with alarm notification by SMS or e-mail.

Optional (one only)

Ethernet

Connection to the web portal via network cable: measurements, set points, dosing and alarms accessible from a PC, tablet or smartphone.

Optional (one only)

USB port

Download of the logged data to a USB memory stick, for archiving and analysis with a spreadsheet.

Optional (one only)
NIMBUS web portal for remote control of the systemsWeb portalPC, tablet and smartphone

Wi-Fi

Wireless connection to the web portal, with the same functions as the cable connection.

Optional (one only)

Modbus RTU

Integration into your PLC via serial port.

Optional (one only)

0-4/20 mA current loop output

Current signal proportional to the measured value, for remote monitoring or for controlling pumps and other instrumentation.

Optional

Optional communication: one only, chosen from 4G, Ethernet, USB, Wi-Fi and Modbus. The 0-4/20 mA current loop output is available as an option with all communication types.

The NIMBUS portal

A single account brings together all registered installations, each with its own devices: the web portal, free of charge and with no subscription, can be accessed from a PC, Mac, tablet or smartphone and allows every parameter to be both viewed and changed, with an encrypted connection and protected access.

The NIMBUS portal on monitor, laptop, tablet and smartphone

Overview

On a single screen: probe readings, chemical levels, pump activation thresholds and active alarms, with the status of installations and devices (normal, warning, alarm, standby, not connected).

Installation map

Installations appear on an interactive map with their status and open with a click; for each one, the local weather conditions and temperature are also shown.

History and charts

Archive of measurements and alarms, available for consultation at any time with charts and numerical reports exportable in Excel format.

Alarms and notifications

Alarm thresholds for readings, dosing, faulty probe and out-of-range readings, with notification by e-mail or SMS depending on the communication system; a warning is also issued when an installation remains disconnected beyond the set time.

Set points and dosing

Remote modification of the set points, of the dosing pump activation thresholds and of the corresponding hourly flow rate.

Inputs and outputs

Status of relays, pulse outputs, digital inputs and current outputs, with the name assigned to each connection.

Maintenance calendar

Tasks are scheduled by installation or by device and assigned to technicians; a reminder is sent by e-mail two days before the due date. Each task is shown as scheduled, due, overdue or completed.

Team and permissions

The main account has full access and creates the technicians’ accounts, each enabled only for the assigned installations and devices; the last login and activity of each technician are visible.

Reports and activity log

Reports on devices, tasks and technicians, downloadable in PDF or CSV with the customer’s logo; the log keeps the history of operations and disconnections.

Customisation

Logo, main colour and light or dark theme; the tiles on the main screen can be rearranged by dragging them. Two installations can be displayed side by side for comparison.

Guided registration

Each device is added through a guided procedure: the model is recognised automatically and associated with the installation, together with the technician to be contacted.

PLC integration

As an alternative to the portal, the Modbus RTU port allows integration into the plant supervision system.

NIMBUS portal: Real-time readings, counters and timers
Real-time readings, counters and timers
NIMBUS portal: Free chlorine and temperature trends
Free chlorine and temperature trends
NIMBUS portal: Set point and operating mode of each channel
Set point and operating mode of each channel
NIMBUS portal: Status of relays, pulses, inputs and mA outputs
Status of relays, pulses, inputs and mA outputs

Choosing the controller

Tell us the characteristics of the tower and the chemicals used: we will propose the most suitable model, probes and panel.

Contact

Tell us about your plant