Skip to content
Redox · amperometric cell

LDRhCL

The LDRhCL controller measures and controls Redox potential (ORP) and a disinfectant read by an amperometric cell, in addition to temperature. Electrode and cell are fitted in the same flow-through probe holder, together with the flow sensor, and the controller drives up to three proportional pumps. It is used, for example, to control peracetic acid.

  • Redox and amperometric cell
  • SCL or ECL cells
  • 1 mV resolution
  • Up to 3 pumps
LDRhCL system for peracetic acid assembled in a cabinet with two dosing pumps
LDRhCLin a cabinet
LDRhCL system for peracetic acid on a skid with raised frame and three dosing pumps
On a skid
± 1,000mVRedox range
1mVRedox resolution
1Flow-through probe holder
3Proportional outputs
Controller

The controller

It acquires the measurements from the two probes and controls the dosing pumps in proportion to the measured values.

Colour display

Multicolour backlit display that indicates the different operating states by changing colour. Programming via a single knob.

Four modes

Proportional, ON/OFF, PWM and PID dosing, with delayed dosing start.

Data storage

Permanent data storage and a system log viewable on the display; the internal log can be exported to a USB memory stick for processing with a spreadsheet.

Alarms

Chemical level, no flow, maximum dosing time exceeded, probe failure, out-of-range reading; audible or visual signalling via the alarm output.

Colour display

Colour-coded status indication

The backlit display shows both measurements, the temperature and the status of the outputs at the same time and, by changing colour, indicates the different operating states, which can be recognised even from a distance.

Display Normal operation

Normal operation

Measurement and dosing according to the set parameters.

Display Stand-by

Stand-by

Controller in stand-by.

Display Warning

Warning

Warning signal, for example the chemical level.

Display Alarm

Alarm

Alarm signal, for example from the probe.

Versions

BASIC and PLUS versions

The instrument is available in two versions, which differ in the number of inputs and outputs: the PLUS version adds the meter input, PID control, and the circulation pump output.

BASICPLUS
Measuring channels2 + temperature2 + temperature
Level inputs33
Flow input11
Stand-by input11
Meter input–1
Outputs for pumps and loads (relays)2 (ON/OFF, PWM)2 (ON/OFF, PWM, PID)
Proportional outputs for dosing pumps33
Alarm output11
0-4/20 mA current loop outputsOptionalOptional
Circulation pump output–1
Modbus RTU●Optional
Ethernet, Wi-Fi, 4G, USBOptionalOptional
Data sheet

Controller data sheet

Inputs, outputs, control modes and alarms of the controller.

Inputs

  • Redox electrode (BNC connector)
  • Amperometric cell (terminal block)
  • PT100 temperature probe
  • Flow sensor
  • Stand-by
  • Redox chemical level (2 inputs)
  • Disinfectant level
  • Pulse-output water meter or mA signal (PLUS)

Outputs

  • 2 proportional pulse outputs for Redox
  • 1 proportional pulse output for the disinfectant
  • Relay output for Redox (ON/OFF or PWM)
  • Relay output for the disinfectant (ON/OFF or PWM)
  • Alarm output
  • Optional 0-4/20 mA outputs: Redox, disinfectant and temperature
  • Circulation pump (PLUS)

Control

  • Proportional
  • ON/OFF
  • PWM
  • PID (PLUS)
  • Delayed start

Alarms

  • Chemical levels
  • No flow
  • Maximum dosing time
  • Probe failure
  • Out-of-range reading

Power supply

  • 230 VAC
  • 12 – 24 VDC
Measurements

Redox and disinfectant

The first channel reads a Redox electrode and the second an amperometric cell, in the same flow-through probe holder. The PT100 probe provides the water temperature.

Redox (ORP)

The range is ± 1,000 mV with a resolution of 1 mV. The Redox potential indicates the oxidising capacity of the water.

Redox electrodes →

Amperometric cell

The SCL closed amperometric cell measures free chlorine, total chlorine, chlorine dioxide, bromine, hydrogen peroxide, peracetic acid, ozone or chlorites; the ECL open amperometric cell measures free chlorine in swimming pool water. Range and resolution depend on the selected cell.

SCL amperometric cells →

Temperature

The PT100 probe reads the temperature from 0 to 100 °C, which is shown on the display and transmitted on the mA output.

Temperature probes →

Probe data sheets

Redox electrodes
ElectrodeRangePressureConnectionBodyMinimum conductivityJunctionTemperatureCableDiameterNotes
ERhS± 1,000 mV7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)0.8 m12 mm–
ERhM± 1,000 mV7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)4.5 m12 mm–
ERhL± 1,000 mV7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)15 m12 mm–
ERhHLB SN6± 1,500 mV6 barSN6 with PG13.5 threadGlass100 µS–80 °C10 m12 mmHigh linearity and sensitivity, for low chlorine concentrations
ERhSN6± 1,000 mV7 barSN6 with PG13.5 threadEpoxy100 µS–100 °C1 – 100 m12 mm–
ERhMD/100± 1,000 mV7 barBNCEpoxy100 µSDouble100 °C4.5 m12 mm–
ERhM/D± 1,000 mV7 bar (3.5 bar)BNCEpoxy100 µSDouble70 °C (80 °C)4.5 m12 mm–
ERhSC± 1,000 mV7 bar (3.5 bar)BNCEpoxy100 µSDouble70 °C (80 °C)4.5 m12 mmSelf-cleaning
ERhSC/SN6± 1,000 mV7 bar (3.5 bar)SN6 with PG13.5 threadEpoxy100 µSDouble70 °C (80 °C)1 – 100 m12 mmSelf-cleaning

All models: combination electrode, resolution 1 mV.

Closed amperometric cells – Free chlorine
SCL3N/0.5SCL3N/2SCL3N/20SCL18/0.5SCL18/2SCL18/20SCL3S/20
Measuring range0 – 0.5 mg/l0 – 2 mg/l0 – 20 mg/l0 – 0.5 mg/l0 – 2 mg/l0 – 20 mg/l0 – 20 mg/l
Resolution0.0010.0010.010.0010.0010.010.01
Free chlorineInorganicInorganicInorganicInorganicInorganicInorganicOrganic and inorganic
WaterFreshFreshFreshFreshFreshFreshFresh or salt
Electrodes2223332
Selective membrane●●●–––●
Automatic compensationpH and temperaturepH and temperaturepH and temperaturepH and temperaturepH and temperaturepH and temperatureTemperature
Self-cleaning–––●●●–
Operating pH5 – 9.55 – 9.55 – 9.55 – 95 – 95 – 95.5 – 9.5
Operating temperature1 – 40 °C1 – 40 °C1 – 40 °C5 – 70 °C5 – 70 °C5 – 70 °C5 – 45 °C
Operating pressure1 bar1 bar1 bar8 bar8 bar8 bar1 bar
Water flow30 l/h30 l/h30 l/h40 l/h40 l/h40 l/h30 l/h
Closed amperometric cells – Chlorine dioxide
SCL2/0.5SCL2/2SCL2/20SCL17/0.5SCL17/2SCL17/20
Measuring range0 – 0.5 mg/l0 – 2 mg/l0 – 20 mg/l0 – 0.5 mg/l0 – 2 mg/l0 – 20 mg/l
Resolution0.0010.0010.010.0010.0010.01
Electrodes222333
Selective membrane●●●–––
Self-cleaning–––●●●
Operating pH4 – 114 – 114 – 115 – 95 – 95 – 9
Operating temperature1 – 40 °C1 – 40 °C1 – 40 °C5 – 70 °C5 – 70 °C5 – 70 °C
Operating pressure1 bar1 bar1 bar8 bar8 bar8 bar
Water flow30 l/h30 l/h30 l/h40 l/h40 l/h40 l/h

Automatic temperature compensation on all models.

Closed amperometric cells – Other oxidants
SCL8/2SCL8/20SBR/20SCL9SCL11/200SCL11/2000SCL10SCT
MeasurementTotal chlorineTotal chlorineBromineHydrogen peroxidePeracetic acidPeracetic acidOzoneChlorites
Measuring range0 – 2 mg/l0 – 20 mg/l0 – 20 mg/l0 – 200 mg/l0 – 200 mg/l0 – 2,000 mg/l0 – 2 mg/l
0 – 20 mg/l
0 – 2 mg/l
Resolution0.0010.010.010.10.110.001
0.01
0.001
Operating pH4 – 124 – 126.5 – 9.51 – 111 – 91 – 92 – 115.5 – 9.5
Operating pressure1 bar1 bar0.5 bar1 bar1 bar1 bar1 bar1 bar

All models: 2 electrodes, selective membrane, automatic temperature compensation, operating temperature 1 – 40 °C, water flow 30 l/h.

ECL open amperometric cells
ECL6ECL6/EECL7ECL12ECL12/EECL20ECL21
WaterFreshFreshFreshSeaSeaFreshSea
Flow stabiliser●●●●●––
Flow sensor and regulation●●●●●––
Probe holder forTemperature, pH, RedoxTemperatureTemperature, pH, Redox (PG13.5)Temperature, pH, RedoxTemperature––

All models: amperometric system, range 0 – 10 mg/l, resolution 0.01, organic and inorganic free chlorine, operating temperature 1 – 40 °C, pressure 0.4 – 5 bar, water flow 40 l/h.

The model

LDRhCL

Two-channel LD system on a panel with electrode and amperometric cell in the probe holder
Redox · amperometric cell

LDRhCL

Redox electrode (resolution 1 mV) and amperometric cell, either SCL closed (free chlorine, total chlorine, chlorine dioxide, bromine, hydrogen peroxide, peracetic acid, ozone or chlorites) or ECL open (free chlorine in swimming pool water), in the same flow-through probe holder, with temperature probe and flow sensor. Up to 3 proportional pumps, 2 digital outputs from set point, 3 levels and audible and visual alarm.

Technical data

Technical data

Controller specifications taken from the manufacturer’s technical documentation. Ranges and resolution depend on the installed probes, described in the data sheets at the end of this section.

Technical specifications

SpecificationValue
MeasurementsRedox potential and disinfectant with an amperometric cell, plus temperature
Measuring range± 1,000 mV; disinfectant depending on the selected amperometric cell
Resolution1 mV; disinfectant depending on the selected amperometric cell
Measured temperature0 – 100 °C, PT100 probe
Power supply85 – 264 VAC, 50/60 Hz
Alternative power supply9 – 18 or 18 – 36 VDC, optional
Relay outputs2, maximum load 5 A at 230 VAC, for ON/OFF or PWM devices
Proportional pulse outputs3, optocoupled
Alarm outputPowered, 85 – 264 VAC
0-4/20 mA outputs3, optional (one for each measurement and one for temperature), maximum load 500 Ω
Communication portRS485
FusesMain 6 A T, outputs 3.15 A T
Ambient temperature−10 – 45 °C
Transport and storage temperature−10 – 50 °C
Installation classII, pollution degree 2
Protection ratingIP65
Dimensions (W × H × D)213 × 264 × 124 mm
Complete systems

Complete systems with LDRhCL

The controller is the core of the measuring and dosing system: for each application, the system page gives the composition, the installation diagram and the installation.

Redox and peracetic acid

LDRhCLRedox and peracetic acid

The system measures and controls the Redox potential (ORP) and the concentration of a disinfectant read with a closed amperometric cell, typically peracetic acid, in addition to temperature.

The system →
Peracetic acid

LDsCLPeracetic acid

Dosing of peracetic acid in the food industry and in washing processes.

The system →
Food and beverage industry

Food and beverage industry

In the food industry, safety and quality allow no compromise.

The sector →
Industrial water

Industrial water

Industrial water treatment ensures efficient processes, protects equipment and allows compliance with environmental regulations.

The sector →
Wastewater

Wastewater

Wastewater treatment reduces the environmental impact of domestic, industrial and municipal activities, protects water resources and allows water, an increasingly precious resource, to be reused.

The sector →

For wastewater and for plants with special requirements the system is defined on the characteristics of the plant: contact us.

Remote control

System remote control

The controllers support two-way remote access (read and write) through the web portal from a PC, tablet or smartphone: measurements can be viewed, set points, dosing and alarms changed, alarms received and logs downloaded. Alternatively, they can be integrated into your PLC via Modbus.

Ethernet

Connection to the web portal via network cable: measurements, set points, dosing and alarms accessible from a PC, tablet or smartphone.

Optional (one only)

Wi-Fi

Wireless connection to the web portal, with the same functions as the cable connection.

Optional (one only)

4G

Connection via the 4G network for installations without a local network, with alarm notification by SMS or e-mail.

Optional (one only)
NIMBUS web portal for remote control of the systemsWeb portalPC, tablet and smartphone

Modbus RTU

Integration into your PLC via serial port.

Standard (BASIC), optional (PLUS)

0-4/20 mA current loop output

Current signal proportional to the measured value, for remote monitoring or for controlling pumps and other instrumentation.

Optional (3 outputs)

USB port

Download of the logged data to a USB memory stick, for archiving and analysis with a spreadsheet.

Optional

One communication type at a time: Ethernet, Wi-Fi, 4G or Modbus RTU (built into the BASIC versions, optional on the PLUS versions). 0-4/20 mA current loop outputs optional; meter input on the PLUS versions only.

The NIMBUS portal

A single account brings together all registered installations, each with its own devices: the web portal, free of charge and with no subscription, can be accessed from a PC, Mac, tablet or smartphone and allows every parameter to be both viewed and changed, with an encrypted connection and protected access.

The NIMBUS portal on monitor, laptop, tablet and smartphone

Overview

On a single screen: probe readings, chemical levels, pump activation thresholds and active alarms, with the status of installations and devices (normal, warning, alarm, standby, not connected).

Installation map

Installations appear on an interactive map with their status and open with a click; for each one, the local weather conditions and temperature are also shown.

History and charts

Archive of measurements and alarms, available for consultation at any time with charts and numerical reports exportable in Excel format.

Alarms and notifications

Alarm thresholds for readings, dosing, faulty probe and out-of-range readings, with notification by e-mail or SMS depending on the communication system; a warning is also issued when an installation remains disconnected beyond the set time.

Set points and dosing

Remote modification of the set points, of the dosing pump activation thresholds and of the corresponding hourly flow rate.

Inputs and outputs

Status of relays, pulse outputs, digital inputs and current outputs, with the name assigned to each connection.

Maintenance calendar

Tasks are scheduled by installation or by device and assigned to technicians; a reminder is sent by e-mail two days before the due date. Each task is shown as scheduled, due, overdue or completed.

Team and permissions

The main account has full access and creates the technicians’ accounts, each enabled only for the assigned installations and devices; the last login and activity of each technician are visible.

Reports and activity log

Reports on devices, tasks and technicians, downloadable in PDF or CSV with the customer’s logo; the log keeps the history of operations and disconnections.

Customisation

Logo, main colour and light or dark theme; the tiles on the main screen can be rearranged by dragging them. Two installations can be displayed side by side for comparison.

Guided registration

Each device is added through a guided procedure: the model is recognised automatically and associated with the installation, together with the technician to be contacted.

PLC integration

As an alternative to the portal, the Modbus RTU port allows integration into the plant supervision system.

NIMBUS portal: Real-time readings, counters and timers
Real-time readings, counters and timers
NIMBUS portal: Free chlorine and temperature trends
Free chlorine and temperature trends
NIMBUS portal: Set point and operating mode of each channel
Set point and operating mode of each channel
NIMBUS portal: Status of relays, pulses, inputs and mA outputs
Status of relays, pulses, inputs and mA outputs

Technical advice

Tell us the parameters to be monitored and the characteristics of the plant: we will propose the most suitable controller, probes, pumps and accessories.

Contact

Tell us about your plant

Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.

What do you need?
Please enter your name.
Please enter a valid email address.
Please enter your message.

Describe your plant: type, water volume or flow rate, parameters to be controlled.

You must accept the privacy notice to continue.