Proportional pH
The pump starts when the pH exceeds the SET POINT ON, for example 8.00 pH, and progressively reduces its strokes until it stops at the SET POINT OFF, for example 7.00 pH.
The system continuously measures the pH and the electrical conductivity of the water, which depends on the amount of dissolved salts. The pH is corrected by proportional dosing, while conductivity is controlled ON/OFF between two thresholds: the output of the second channel drives the pump of a product, for example the fertiliser, or a solenoid valve.
The layout shows a fertigation plant: the pH electrode and the conductivity probe are in the mixing tank, one pump doses the acid and the other the fertiliser.

The pump starts when the pH exceeds the SET POINT ON, for example 8.00 pH, and progressively reduces its strokes until it stops at the SET POINT OFF, for example 7.00 pH.
The output switches on when conductivity falls below the SET POINT ON, for example 1.50 mS, and switches off when the SET POINT OFF is reached, for example 2.00 mS.
The PT100 temperature probe allows both pH and conductivity to be temperature-compensated.
The system consists of the dual-channel controller, the pH electrode, the conductivity probe, the dosing pumps and the injection accessories.
It reads the pH electrode from the BNC connector and the conductivity probe from the terminal board, and drives the dosing pumps or solenoid valves connected to the outputs.
The controller →
The combined electrode measures pH from 0 to 14 and can be installed by immersion, in-line or in by-pass.
pH electrodes →
Conductive or inductive, chosen according to the measuring range and the characteristics of the water.
Conductivity probes →
Solenoid diaphragm pumps for the pH corrector and for the product of the second channel, driven by the controller.
Dosing pumps →Conductivity is measured with two different principles; the range and resolution depend on the selected probe.
They have graphite, stainless steel or platinum electrodes, with automatic temperature compensation; some models can also be installed by immersion or at high temperature.
Conductive probes →It has no electrodes in contact with the water, is not affected by polarisation or fouling and also measures in still water, from 0.3 to 300 mS; it can be installed in by-pass, in-line or by immersion.
Inductive probe →The probe must be installed with the flow directed onto its tip: this prevents air bubbles from building up and sediment from settling, which would alter the reading and, consequently, the control of pumps and valves.
Installed on the pipe, the probe is oriented so that the flow strikes its tip; some models can also be installed by immersion in the tank.
The probes can also be installed in flow-through probe holders connected in by-pass to the plant.
Probe holders →
Control of the pH of the nutrient solution with the acid and of conductivity with the fertiliser, using a single controller.
The fertigation system →
Control of pH and salinity in industrial process water.
Learn more: industrial water →
Measuring ranges, resolution, measuring principles, inputs, outputs, display and connections are given in the controller data sheet.
The controllers support two-way remote access (read and write) through the web portal from a PC, tablet or smartphone: measurements can be viewed, set points, dosing and alarms changed, alarms received and logs downloaded. Alternatively, they can be integrated into your PLC via Modbus.
Connection to the web portal via network cable: measurements, set points, dosing and alarms accessible from a PC, tablet or smartphone.
Wireless connection to the web portal, with the same functions as the cable connection.
Connection via the 4G network for installations without a local network, with alarm notification by SMS or e-mail.
Web portalPC, tablet and smartphone
Integration into your PLC via serial port.
Current signal proportional to the measured value, for remote monitoring or for controlling pumps and other instrumentation.
Download of the logged data to a USB memory stick, for archiving and analysis with a spreadsheet.
One communication type at a time: Ethernet, Wi-Fi, 4G or Modbus RTU (built into the BASIC versions, optional on the PLUS versions). 0-4/20 mA current loop outputs optional; meter input on the PLUS versions only.
A single account brings together all registered installations, each with its own devices: the web portal, free of charge and with no subscription, can be accessed from a PC, Mac, tablet or smartphone and allows every parameter to be both viewed and changed, with an encrypted connection and protected access.
On a single screen: probe readings, chemical levels, pump activation thresholds and active alarms, with the status of installations and devices (normal, warning, alarm, standby, not connected).
Installations appear on an interactive map with their status and open with a click; for each one, the local weather conditions and temperature are also shown.
Archive of measurements and alarms, available for consultation at any time with charts and numerical reports exportable in Excel format.
Alarm thresholds for readings, dosing, faulty probe and out-of-range readings, with notification by e-mail or SMS depending on the communication system; a warning is also issued when an installation remains disconnected beyond the set time.
Remote modification of the set points, of the dosing pump activation thresholds and of the corresponding hourly flow rate.
Status of relays, pulse outputs, digital inputs and current outputs, with the name assigned to each connection.
Tasks are scheduled by installation or by device and assigned to technicians; a reminder is sent by e-mail two days before the due date. Each task is shown as scheduled, due, overdue or completed.
The main account has full access and creates the technicians’ accounts, each enabled only for the assigned installations and devices; the last login and activity of each technician are visible.
Reports on devices, tasks and technicians, downloadable in PDF or CSV with the customer’s logo; the log keeps the history of operations and disconnections.
Logo, main colour and light or dark theme; the tiles on the main screen can be rearranged by dragging them. Two installations can be displayed side by side for comparison.
Each device is added through a guided procedure: the model is recognised automatically and associated with the installation, together with the technician to be contacted.
As an alternative to the portal, the Modbus RTU port allows integration into the plant supervision system.
Tell us the water quality, the required conductivity range and the products to be dosed: we will propose the most suitable probe, pumps and accessories.
Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.