Coupons in the plant water
The coupons stay in the circuit, with the same water as the piping flowing over them, for the whole monitoring period.
The CORMIS checks over the long term how well the plant is actually protected against corrosion: a frame with four or three coupon holders, connected to the circuit with isolation valves, keeps the coupons in the plant water; the coupons are removed and their loss of thickness and weight is measured.
The purpose of corrosion monitoring is to check the effects of the chemical treatment on the plant. The CORMIS measures it by analysing coupons that stay in the circuit and collect the corroded metal.
The coupons stay in the circuit, with the same water as the piping flowing over them, for the whole monitoring period.
The isolation valves exclude the frame from the circuit: the coupon holders are removed by hand, without stopping the plant.
Comparing the coupons before and after exposure gives the average metal loss over the period, that is the effectiveness of the corrosion inhibitor.
The two models share the same construction and overall dimensions; they differ in the number of coupon holders, that is how many coupons can be exposed and removed in the same period.
Frame with four removable coupon holders, flow meter, inlet and outlet isolation valves and drain valve.
Frame with three removable coupon holders, flow meter, inlet and outlet isolation valves and drain valve.
The CORMIS is paired with the E-CORR corrosion probe connected to the Centurio Tower: the probe measures the corrosion rate continuously and controls the treatment, while the coupons check its effect on the plant over the long term.
Continuous corrosion rate, from 0.001 to 10 MPY: an instantaneous value, correlated with but not necessarily equal to the average weight loss of the coupons.
Corrosion probe →
The controller for cooling towers reads the E-CORR probe together with conductivity, pH, biocides and tracer.
The Centurio Tower →| Feature | CORMIS 4 | CORMIS 3 |
|---|---|---|
| Body | PVC | PVC |
| Piping | DN40 PN16 | DN40 PN16 |
| Coupon holders | 4 | 3 |
| Removal | Without tools | Without tools |
| Isolation valves | Inlet and outlet | Inlet and outlet |
| Drain valve | ● | ● |
| Flow meter | ● | ● |
| Y-strainer | On request | On request |
| Dimensions | 600 × 900 mm | 600 × 900 mm |
| Maximum temperature | 40 °C | 40 °C |
In cooling circuits the concentration of salts increases the risk of corrosion: the CORMIS checks the effectiveness of the antiscalant and corrosion inhibitor.
Cooling towers →In circuits treated for Legionella prevention the CORMIS checks the effect of the treatment on the plant piping.
Legionella control →Tell us about the circuit and the piping material: we will propose the CORMIS model suited to the plant.
Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.