Panel-mounted ozone system with DIN Digital

The system continuously measures the ozone dissolved in the water with the SCL10 closed amperometric cell and the DIN Digital controller, mounted on a DIN rail in the electrical panel of the plant. Since ozone is generated on site and decomposes rapidly, the controller does not drive a dosing pump but starts and stops the ozone generator until the set point is reached.

  • Ranges 0 – 2 and 0 – 20 mg/l
  • SCL10 closed amperometric cell
  • Control of the ozone generator
  • DIN rail, 6 modules
DIN Digital ozone DIN-rail panel-mount controller
DIN Digitalozone
SCL9, SCL10 and SCL11 closed amperometric cells
SCL10 cell
Composition

Basic composition

The ozone system has no dosing pump: the controller acts directly on the ozone generator of the plant.

DIN Digital panel-mount controller on DIN rail

DIN Digital controller · O3DIN

Single-channel DIN-rail controller, 6 modules, with two ON/OFF or proportional volt-free contact outputs and one programmable 0-4/20 mA output.

DIN Digital →
SCL10 closed amperometric cell

SCL10 closed amperometric cell

The selective membrane allows ozone alone to be measured; the cell is available in two ranges and automatically compensates for temperature. The galvanic part, the only one subject to wear, can be regenerated without replacing the electronic part.

SCL10 cell →
Flow-through probe holder

Probe holder and filter

Probe holder connected in a bypass line to the circuit, with 5" filter with washable 60 µm PET cartridges or 100 µm wound cartridges (maximum 5 bar).

Probe holders →
Operation

Operation

The set points of the parameter to be controlled are entered; the controller drives the connected equipment automatically and continuously.

1

Measurement

The sample water flows through the filter and the probe holder in a bypass line, where the SCL10 cell measures the dissolved ozone; the display shows the measured value, the set points and the proportional band. The programmable delay waits for the probe to polarise before starting control.

2

Generator control

When the concentration falls below the set point, the controller starts the ozone generator; once the set point is reached, it stops it.

3

Flow control

The flow sensor input allows control to be suspended when no water flows through the probe holder and the measurement is not representative.

Inputs and outputs

Inputs, outputs and alarms

The probes, the flow sensor and the controlled loads are connected to the terminal board of the controller.

Inputs

  • Parameter probe: BNC connector for pH and Redox electrodes, terminal board for conductivity probes, amperometric cells and temperature probes
  • NTC 10K temperature probe for the compensation of the pH and conductivity measurement
  • SEPR flow sensor or volt-free contact, which can be shared by two controllers connected in Master/Slave mode

Outputs

  • 2 volt-free contact outputs (set points 1 and 2), in ON/OFF mode or proportional over a 100-second period
  • 0-20 or 4-20 mA current output, programmable and galvanically isolated, maximum load 350 Ω, for a dosing pump or a recorder

Alarms

  • No flow: NO FLOW message and control stopped
  • Probe calibration errors, shown on the display

The controller has no dedicated alarm output: alarm conditions are shown on the display.

Installation

Installation in the electrical panel

The controller is mounted on a DIN rail, 6 modules, in the electrical panel of the plant, next to the other control devices; ABS housing, IP40 protection, 24, 115 or 230 VAC or 24 VDC power supply.

Installation of the DIN Digital controller in the electrical panel
DIN Digital controller mounted in an enclosure with transparent cover

In the plant panel or in its own enclosure

The controller is installed in the existing panel or in its own enclosure with transparent cover, ready for connection; several controllers can be connected to each other in Master/Slave mode.

Diagram of the bypass connection of the PEF flow-through probe holder

Probe holder in a bypass line

The sample water is taken with a T-fitting on the pipe, flows through the filter and the probe holder and returns to the circuit or to drain.

Probe holders →
Applications

Where it is used

Ozone disinfects at the moment of contact with the water and decomposes rapidly into oxygen, without leaving a residual: where the distribution network must be protected, it is combined with a disinfectant with a residual effect, such as chlorine.

Water supply and treatment

Water supply and treatment

In drinking water treatment plants, measuring the dissolved ozone allows production to be regulated according to the concentration actually present.

Learn more: drinking water →
Food industry

Food industry

In the processing and washing water of food plants, the ozone concentration remains controlled and documented.

Learn more: food industry →
The controller

The DIN Digital controller

DIN Digital panel controller on DIN rail

DIN Digital

Versions and code prefixes, parameters, measuring ranges, inputs, outputs and technical characteristics are given on the controller page.

Technical advice

Tell us the parameter to be controlled, the characteristics of the panel and the equipment to be driven: we will propose the most suitable probe, pumps and accessories.

Contact

Tell us about your plant

Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.

What do you need?
Please enter your name.
Please enter a valid email address.
Please enter your message.

Describe your plant: type, water volume or flow rate, parameters to be controlled.

You must accept the privacy notice to continue.