KMS CL2
With integrated controller for dosing hypochlorite by means of open amperometric cells.
- Proportional to free chlorine (open amperometric cell)
Diaphragm dosing pump with a built-in controller for measuring free chlorine over the 0 – 10 mg/l range and for proportional dosing of sodium hypochlorite. The measurement is made with an open amperometric cell, ordered separately; level control is standard, while the alarm output is available as an option.
The required free chlorine concentration in mg/l (SET POINT) is set: the pump measures it by means of an open amperometric cell and progressively reduces the injection frequency as the measured value approaches the set point, stopping when the SET POINT is reached.
The pump code is made up of the model name and the performance: maximum pressure in bar as two digits followed by the flow rate in l/h (KMS CL2 0218 = 2 bar, 18 l/h). It is followed by the pump head code and the power supply code, listed in the tables at the end of this section. Performance varies with the working back pressure and with the characteristics of the chemical.
Suitable for most chemicals, with a viscosity up to 100 cP: the standard configuration for the most common applications.
| Code | Max pressure (bar) | Max flow rate (l/h) | Tubing (mm) |
|---|---|---|---|
| KMS CL2 2001 | 20 | 1 | 4 x 6 |
| KMS CL2 1802 | 18 | 2 | 4 x 6 |
| KMS CL2 1504 | 15 | 4 | 4 x 6 |
| KMS CL2 1005 | 10 | 5 | 4 x 6 |
| KMS CL2 0808 | 8 | 8 | 4 x 6 |
| KMS CL2 0510 | 5 | 10 | 4 x 6 |
| KMS CL2 0501 | 5 | 1 | 4 x 6 |
| KMS CL2 0218 | 2 | 18 | 6 x 8 |
Required with chemicals that release gas (e.g. peroxides), to prevent the pump from becoming air-locked.
| Code | Max pressure (bar) | Max flow rate (l/h) | Tubing (mm) |
|---|---|---|---|
| KMSA CL2 1801 | 18 | 1 | 4 x 6 |
| KMSA CL2 1503 | 15 | 3 | 4 x 6 |
| KMSA CL2 103.5 | 10 | 3.5 | 4 x 6 |
| KMSA CL2 100.5 | 10 | 0.5 | 4 x 6 |
| KMSA CL2 085.5 | 8 | 5.5 | 4 x 6 |
| KMSA CL2 057.5 | 5 | 7.5 | 4 x 6 |
| KMSA CL2 0213 | 2 | 13 | 6 x 8 |
For chemicals with a viscosity up to 8,000 cP.
| Code | Max pressure (bar) | Max flow rate (l/h) | Delivery tube (mm) | Suction tube (mm) |
|---|---|---|---|---|
| KMS CL2 LPV 1802 | 18 | 2 | 8 x 12 | 16 x 22 |
| KMS CL2 LPV 1504 | 15 | 4 | 8 x 12 | 16 x 22 |
| KMS CL2 LPV 1005 | 10 | 5 | 8 x 12 | 16 x 22 |
| KMS CL2 LPV 0808 | 8 | 8 | 8 x 12 | 16 x 22 |
| KMS CL2 LPV 0510 | 5 | 10 | 8 x 12 | 16 x 22 |
| KMS CL2 LPV 0218 | 2 | 18 | 8 x 12 | 16 x 22 |
Nominal flow rate measured with water at room temperature. The LPV version is supplied with a 3/4" injection valve, PE delivery tube, PVC suction tube and a priming kit with syringe, without level probe.
| Specification | Value |
|---|---|
| Strokes | From 1 per hour to 180 per minute |
| Mechanical adjustment of the single stroke | Linear from 30 to 100 % |
| Maximum chemical viscosity | 100 cP; 8,000 cP in the LPV version |
| Average power draw at maximum flow rate | 19 W at 230 VAC, 24 W at 115 VAC, 12 W at 24 VAC and 24 VDC, 8.8 W at 12 VDC |
| Protection rating | IP65 |
| Noise level | 73.4 dB(A); 74 dB(A) in the LPV version |
| Weight | 4.1 kg |
| Housing | PP |
| Maximum altitude | 2,000 m a.s.l. |
| Mounting | Horizontal, or vertical with the dedicated bracket |
| Ambient temperature | 10 – 45 °C |
| Product temperature | 0 – 50 °C |
| Transport and storage temperature | -10 – 50 °C |
| Relative humidity | 85 % up to 40 °C, 70 % at 45 °C, non-condensing |
| Installation category | II |
| Pollution degree | 2 |
| Component | Material |
|---|---|
| Diaphragm | PTFE, in all versions |
| Dynamic O-rings (pump head) | Viton (FKM) or Dutral (EPDM) |
| Static O-rings | Viton (FKM), Dutral (EPDM), Nitrile (NBR) or Teflon (PTFE) |
| Valve balls | Ceramic; stainless steel in the AISI 316L pump head |
| Pump head | Material | O-rings | Valves | Balls | Delivery hose | Suction hose | Max viscosity (cP) |
|---|---|---|---|---|---|---|---|
| K | PVDF | FKM | PVDF | Ceramic | PVDF | PVC | 100 |
| P | PVDF | EPDM | PVDF | Ceramic | PVDF | PVC | 100 |
| Y | PVDF | NBR | PVDF | Ceramic | PVDF | PVC | 100 |
| V | PP | FKM | PVDF | Ceramic | PE | PVC | 100 |
| D | PP | EPDM | PVDF | Ceramic | PE | PVC | 100 |
| J | PVDF | FKM + PTFE | PVDF | Ceramic | PVDF | PVC | 100 |
| A | PMMA | FKM | PVDF | Ceramic | PVDF | PVC | 100 |
| Z | AISI 316L | FKM | AISI 316L | AISI 316L | – | – | 100 |
| $ (LPV) | PMMA | FKM | PP | Stainless steel, Hastelloy spring | PE | PVC | 8,000 |
PTFE diaphragm for all pump heads. 4 × 6 mm hoses, 6 × 8 mm for models 0218 and 0213: the size may vary with the pump head material. In some applications the $ head for slightly viscous liquids may reduce the flow rate.
| Code | Power supply |
|---|---|
| 00 | 230 VAC, Schuko plug |
| 0S | 230 VAC, Australian plug |
| 01 | 230 VAC, no plug |
| 03 | 115 VAC, US plug |
| 04 | 24 VAC, no plug |
| 05 | 12 VDC (some models only) |
| 07 | 24 VDC |
Suitable for most acids, for peroxides and for sodium hypochlorite (chlorine).
Suitable for sodium hydroxide (caustic soda).
Suitable for peracetic acid and sodium hydroxide.
Suitable for medium and high viscosity substances.
In addition to the standard configuration, versions dedicated to particular applications are available; the performance of each is given in the technical data. The pages by application compare the suitable pumps of all the series.
Self-venting pump head, required with chemicals that release gas (e.g. sodium hypochlorite and peroxides): it vents the gas and prevents the pump from locking.
PMMA pump head for viscous liquids up to 8,000 cP.
Measurements in mm [inches], the same for the K and KMS series.
The most frequent causes of malfunction and the corrective actions to check before contacting technical support.
Learn more: the pump does not prime and does not dose →Adjustment is linear between 30 and 100%: below 30% the actual flow rate may differ from the expected one and must therefore be checked.
Connect all the tubing, open the bleed valve and set the adjustment to 100%; start the pump and close the bleed valve as soon as the chemical comes out. With viscous liquids the operation can be assisted with a 20 cc syringe applied to the bleed port.
With the pump switched off, hold down both arrow keys and restore power: LOAD DEFAULT appears and the programming is reset to the factory values (password 0000).
If the problem persists, contact us. Before sending the pump for servicing, empty the pump head of chemical and dry it.
According to the operating mode and the set parameters, the pump automatically adapts the injection frequency to ensure the required dosing.
The knob reduces the stroke length of the diaphragm, i.e. the volume of each injection and, consequently, the maximum flow rate. This offers two advantages:
Linear dosing: a high number of small-volume injections promotes mixing of the chemical into the water flow and avoids concentration peaks.
Accuracy at low dosing rates: with a 10 l/h pump required to dose 1 l/h, reducing the stroke length to 50% brings the maximum flow rate down to 5 l/h and doubles the injection frequency. Particularly suitable in combination with the pulse-output water meter.
The pump is supplied with a low-level probe for the tank: when the chemical runs out, it shows the alarm on the display and activates the corresponding output.
On request, in the event of a fault a volt-free contact is activated, configurable as normally open (N.O.) or normally closed (N.C.), to drive a visual or audible signalling device, send an SMS or report the event to a PLC.
A dedicated button allows the lines to be filled with the chemical to be dosed.
Horizontal installation, or vertical installation by means of a dedicated bracket.