JA PRO controller · JACL PRO
Single-channel controller plus temperature, for 96×96 flush mounting, with two volt-free contact outputs, one proportional pump output, one 0-4/20 mA output and Modbus RTU communication.
JA PRO →The system continuously measures the ozone dissolved in the water with the SCL10 closed amperometric cell and the JA PRO controller, flush-mounted on the front of the electrical panel of the plant. Since ozone is generated on site and decomposes rapidly, the volt-free contact outputs do not drive a dosing pump but switch on the ozone generator until the set point is reached; the Modbus RTU port connects the controller to the PLC network of the plant.
The ozone system has no dosing pump: the controller acts directly on the ozone generator of the plant.
Single-channel controller plus temperature, for 96×96 flush mounting, with two volt-free contact outputs, one proportional pump output, one 0-4/20 mA output and Modbus RTU communication.
JA PRO →
The selective membrane allows ozone alone to be measured; the cell is available in two ranges and automatically compensates for temperature. The galvanic part, the only one subject to wear, can be regenerated without replacing the electronic part.
SCL10 cell →
Probe holder connected in a bypass line to the circuit, with 5" filter with washable 60 µm PET cartridges or 100 µm wound cartridges (maximum 5 bar).
Probe holders →The set points of the parameter to be controlled are entered; the controller drives the connected equipment automatically and continuously.
The sample water flows through the filter and the probe holder in a bypass line, where the SCL10 cell measures the dissolved ozone and the PT100 probe the temperature; the display shows the measured value, the temperature and the status of the outputs.
The volt-free contact outputs switch on the ozone generator: when the concentration falls below the set point the controller starts it and once the set point is reached it stops it.
The flow input suspends control when no water flows through the probe holder; the stand-by input stops the activity of the controller on an external command. The Modbus RTU port connects the controller to the PLC of the plant.
The probes, the external contacts and the controlled loads are connected to the terminal board of the controller.
The controller is flush-mounted on the front of the electrical panel of the plant, in a 96×96 mm cut-out; ABS housing, IP40 protection (IP54 on request), 230 VAC or 12 or 24 VDC power supply.

The RS485 port with Modbus RTU protocol connects the controller to the PLC network of the plant, for reading the measurements.
The sample water is taken with a T-fitting on the pipe, flows through the filter and the probe holder and returns to the circuit or to drain.
Probe holders →Ozone disinfects at the moment of contact with the water and decomposes rapidly into oxygen, without leaving a residual: where the distribution network must be protected, it is combined with a disinfectant with a residual effect, such as chlorine.
In drinking water treatment plants, measuring the dissolved ozone allows production to be regulated according to the concentration actually present.
Learn more: drinking water →
In the processing and washing water of food plants, the ozone concentration remains controlled and documented.
Learn more: food industry →
Versions and models, parameters, measuring ranges, inputs, outputs and technical characteristics are given on the controller page.