Controllers

MTOWER 2CH

The MTOWER 2CH adds a second parameter to conductivity, chosen among pH, Redox and chlorine, with its own control. Besides bleed-off and antiscalant it manages two biocides with two activators; in the versions with Redox or chlorine the biocide can also be dosed according to the measurement.

  • CD pH, CD Rh and CD CL versions
  • Second channel ON/OFF, PWM or proportional
  • Two biocides and two activators
  • Biocide also according to the measurement
MTOWER 2CH controller with conductivity and pH
MTOWER 2CHCD pH
MTOWER 2CH controller with conductivity and chlorine
MTOWER 2CHCD CL
2Measuring channels
3Versions
2 + 2Biocides and activators
IP65Protection rating
Versions

Versions

The second channel is chosen when ordering, according to the treatment of the tower.

MTOWER 2CH CD pH

CD pH

It measures conductivity and pH and controls the pH of the tower water.

MTOWER 2CH CD Rh

CD Rh

It measures conductivity and the Redox potential, which can be used for biocide dosing.

MTOWER 2CH CD CL

CD CL

It measures conductivity and chlorine or another biocide, with the suitable amperometric cell.

Functions

What the controller manages

Antiscalant and biocide programming →
1

Bleed-off

Opening of the bleed-off valve when the conductivity set point is exceeded, with opening delay, dead band, maximum bleed-off time and manual control.

2

Antiscalant

Dosing linked to bleed-off (Feed & Bleed, Feed & % Bleed), to a percentage of time (Feed & % Time) or to the make-up volume measured by the water meter, or at a constant ppm.

3

Biocides

Two biocides (one on the PLUS version) and two activators on a weekly programme, on a 4-week cycle, or daily; in the versions with Redox or chlorine the biocide can also be dosed according to the measurement.

4

Pre-bleed

Before the biocide and the activator, the controller bleeds off water, for a set time or down to the set conductivity.

5

Lock-out

After the biocide has been dosed, bleed-off remains blocked for the set time, so that the chemical acts without being lost to bleed-off.

6

pH

In the versions with pH, the controller also regulates the pH of the tower water.

The model

MTOWER 2CH

MTOWER 2CH controller with conductivity and pH
Conductivity · pH, Redox or chlorine

MTOWER 2CH

Conductivity plus a second parameter of choice: pH (CD pH), Redox (CD Rh) or chlorine or another biocide (CD CL). On request, mA output and 12 or 24 VDC power supply.

Available versions
CD pH CD pHConductivity and pH
CD Rh CD RhConductivity and Redox
CD CL CD CLConductivity and chlorine
Inputs and outputs

Inputs, outputs and alarms

Inputs

  • 6 chemical level inputs
  • 2 water meter inputs: make-up and bleed-off
  • Flow input
  • Input for one temperature probe
  • Stand-by input

Outputs

  • Bleed-off valve control
  • Proportional outputs: 2 in the CD pH version (inhibitor and pH)
  • Control of the pumps for 2 biocides and 2 activators
  • Alarm output
  • mA output on request

Alarms

  • No water flow
  • 2 chemical level alarms
  • Bleed-off timeout

The probes are not included and are chosen according to the installation.

Display

Display

Settings

Bleed-off set point, antiscalant mode, biocide and activator programmes, pre-bleed and lock-out are set from the controller or remotely from the web portal.

Parameters

Measurable parameters

Conductivity, with a contacting or inductive probe, is measured by all models; pH, Redox and chlorine by the 2CH and PLUS models. All measurements are temperature compensated.

ConductivitypH, Redox and chlorine

Probe data sheets

Contacting probes – ECDC

PVDF body, graphite electrodes.

ModelMountingConnectionRangeK factorTemperature compensation
ECDC/1In-line / bypassR3/4"0 – 20 mS1–
ECDCC/1In-line / bypassR3/4"0 – 20 mS1NTC 10K
ECDCCPT/1In-line / bypassR3/4"0 – 20 mS1PT100
ECDC/10In-line / bypassR3/4"0 – 200 mS10–
ECDCC/10In-line / bypassR3/4"0 – 200 mS10NTC 10K
ECDCCPT/10In-line / bypassR3/4"0 – 200 mS10PT100
ECDCIM/1ImmersionG1/2"0 – 20 mS1–
ECDCCIM/1ImmersionG1/2"0 – 20 mS1NTC 10K
ECDCCIMPT/1ImmersionG1/2"0 – 20 mS1PT100
ECDCIM/10ImmersionG1/2"0 – 200 mS10–
ECDCCIM/10ImmersionG1/2"0 – 200 mS10NTC 10K
ECDCCIMPT/10ImmersionG1/2"0 – 200 mS10PT100

Operating temperature 1 – 60 °C (100 °C at 2 bar), operating pressure 7 bar (2 bar at 100 °C).

Contacting probes – ECDI

PVDF body, stainless steel electrodes.

ModelMountingConnectionRangeK factorTemperature compensation
ECDI/1In-line / bypassR3/4"0 – 5 mS1–
ECDIC/1In-line / bypassR3/4"0 – 5 mS1NTC 10K
ECDICPT/1In-line / bypassR3/4"0 – 5 mS1PT100
ECDI/01In-line / bypassR3/4"0 – 200 µS0.1–
ECDIC/01In-line / bypassR3/4"0 – 200 µS0.1NTC 10K
ECDICPT/01In-line / bypassR3/4"0 – 200 µS0.1PT100
ECDIIM/1ImmersionG1/2"0 – 5 mS1–
ECDICIM/1ImmersionG1/2"0 – 5 mS1NTC 10K
ECDICPTIM/1ImmersionG1/2"0 – 5 mS1PT100
ECDIIM/01ImmersionG1/2"0 – 200 µS0.1–
ECDIIM/02ImmersionG1/2"0 – 500 µS0.2–
ECDICIM/01ImmersionG1/2"0 – 200 µS0.1NTC 10K
ECDICPTIM/01ImmersionG1/2"0 – 200 µS0.1PT100

Operating temperature 1 – 60 °C (100 °C at 2 bar), operating pressure 7 bar (2 bar at 100 °C).

Contacting probes – ECDHL

Epoxy body, platinum electrodes, diameter 12 mm.

ModelMountingRangeK factorTemperature compensation
ECDHL/1In-line / bypass0.2 – 20 mS1–
ECDHLC/1In-line / bypass0.2 – 20 mS1NTC 10K
ECDHLCPT/1In-line / bypass0.2 – 20 mS1PT100
ECDHL/01In-line / bypass0 – 200 µS0.1–
ECDHLC/01In-line / bypass0 – 200 µS0.1NTC 10K
ECDHLCPT/01In-line / bypass0 – 200 µS0.1PT100
ECDHL/10In-line / bypass20 – 200 mS10–
ECDHLC/10In-line / bypass20 – 200 mS10NTC 10K
ECDHLCPT/10In-line / bypass20 – 200 mS10PT100

Operating temperature 1 – 70 °C, operating pressure 7 bar.

Contacting probes – EICDC

Stainless steel body and electrodes, R3/4" connection, in-line or bypass mounting.

ModelRangeK factorTemperature compensationOperating temperature
EICDC/10 – 20 mS1NTC 10K1 – 130 °C
EICDCPT/10 – 20 mS1PT1001 – 130 °C
EICDC/010 – 200 µS0.1NTC 10K1 – 130 °C
EICDCPT/010 – 200 µS0.1PT1001 – 130 °C
EICDC/0010 – 20 µS0.01NTC 10K1 – 130 °C
EICDCPT/0010 – 20 µS0.01PT1001 – 130 °C
EICDCHPT/10 – 20 mS1PT1001 – 200 °C
EICDCHPT/010 – 200 µS0.1PT1001 – 200 °C
EICDCHPT/0010 – 20 µS0.01PT1001 – 200 °C

Operating pressure 15 bar.

Inductive probes
ECDINDPTECDSINDPT
Measuring range0.3 – 3 mS
0.3 – 30 mS
0.3 – 300 mS
0.3 – 10 mS
Measuring systemInductiveInductive
BodyPEEKPEEK
MountingIn-line / bypass / immersionIn-line / bypass / immersion
Temperature compensationPT100PT100
Operating temperature1 – 85 °C (100 °C for short periods)1 – 85 °C (100 °C for short periods)
Operating pressure8 bar8 bar
pH electrodes
ElectrodePressureConnectionBodyMinimum conductivityJunctionTemperatureCableDiameterNotes
EpHS7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)0.8 m12 mm–
EpHM7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)4.5 m12 mm–
EpHL7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)15 m12 mm–
EpHSN67 bar (3.5 bar)SN6 with PG13.5 threadEpoxy100 µS–70 °C (80 °C)1 – 100 m12 mm–
EpHMD/1007 barBNCEpoxy100 µSDouble100 °C4.5 m12 mm–
EpHM/D7 bar (3.5 bar)BNCEpoxy100 µSDouble70 °C (80 °C)4.5 m12 mm–
EpHM/D/SN67 bar (3.5 bar)SN6 with PG13.5 threadEpoxy100 µSDouble70 °C (80 °C)1 – 100 m12 mm–
EpHMD/LI7 bar (3.5 bar)SN6 with PG13.5 threadEpoxy3 µSDouble70 °C (80 °C)1 – 100 m12 mmFor low-conductivity water
EpHSC7 bar (3.5 bar)BNCEpoxy100 µSDouble70 °C (80 °C)4.5 m12 mmSelf-cleaning
EpHSC/SN67 bar (3.5 bar)SN6 with PG13.5 threadEpoxy100 µSDouble70 °C (80 °C)1 – 100 m12 mmSelf-cleaning
EpHM/HF7 bar (3.5 bar)BNCEpoxy100 µSDouble70 °C (80 °C)4.5 m12 mmResistant to 1% hydrofluoric acid
EpHSN6 GK10 barSN6Glass150 µS–−5 / 135 °C1 – 100 m12 mmHigh temperature

All models: combination electrode, range 0 – 14 pH, resolution 0.01.

Redox electrodes
ElectrodeRangePressureConnectionBodyMinimum conductivityJunctionTemperatureCableDiameterNotes
ERhS± 1,000 mV7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)0.8 m12 mm–
ERhM± 1,000 mV7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)4.5 m12 mm–
ERhL± 1,000 mV7 bar (3.5 bar)BNCEpoxy100 µS–70 °C (80 °C)15 m12 mm–
ERhHLB SN6± 1,500 mV6 barSN6 with PG13.5 threadGlass100 µS–80 °C10 m12 mmHigh linearity and sensitivity, for low chlorine concentrations
ERhSN6± 1,000 mV7 barSN6 with PG13.5 threadEpoxy100 µS–100 °C1 – 100 m12 mm–
ERhMD/100± 1,000 mV7 barBNCEpoxy100 µSDouble100 °C4.5 m12 mm–
ERhM/D± 1,000 mV7 bar (3.5 bar)BNCEpoxy100 µSDouble70 °C (80 °C)4.5 m12 mm–
ERhSC± 1,000 mV7 bar (3.5 bar)BNCEpoxy100 µSDouble70 °C (80 °C)4.5 m12 mmSelf-cleaning
ERhSC/SN6± 1,000 mV7 bar (3.5 bar)SN6 with PG13.5 threadEpoxy100 µSDouble70 °C (80 °C)1 – 100 m12 mmSelf-cleaning

All models: combination electrode, resolution 1 mV.

Closed (membrane) amperometric cells – Free chlorine
SCL3N/0.5SCL3N/2SCL3N/20SCL18/0.5SCL18/2SCL18/20SCL3S/20
Measuring range0 – 0.5 mg/l0 – 2 mg/l0 – 20 mg/l0 – 0.5 mg/l0 – 2 mg/l0 – 20 mg/l0 – 20 mg/l
Resolution0.0010.0010.010.0010.0010.010.01
Free chlorineInorganicInorganicInorganicInorganicInorganicInorganicOrganic and inorganic
WaterFreshFreshFreshFreshFreshFreshFresh or salt
Electrodes2223332
Selective membrane●●●–––●
Automatic compensationpH and temperaturepH and temperaturepH and temperaturepH and temperaturepH and temperaturepH and temperatureTemperature
Self-cleaning–––●●●–
Operating pH5 – 9.55 – 9.55 – 9.55 – 95 – 95 – 95.5 – 9.5
Operating temperature1 – 40 °C1 – 40 °C1 – 40 °C5 – 70 °C5 – 70 °C5 – 70 °C5 – 45 °C
Operating pressure1 bar1 bar1 bar8 bar8 bar8 bar1 bar
Water flow30 l/h30 l/h30 l/h40 l/h40 l/h40 l/h30 l/h
Closed (membrane) amperometric cells – Chlorine dioxide
SCL2/0.5SCL2/2SCL2/20SCL17/0.5SCL17/2SCL17/20
Measuring range0 – 0.5 mg/l0 – 2 mg/l0 – 20 mg/l0 – 0.5 mg/l0 – 2 mg/l0 – 20 mg/l
Resolution0.0010.0010.010.0010.0010.01
Electrodes222333
Selective membrane●●●–––
Self-cleaning–––●●●
Operating pH4 – 114 – 114 – 115 – 95 – 95 – 9
Operating temperature1 – 40 °C1 – 40 °C1 – 40 °C5 – 70 °C5 – 70 °C5 – 70 °C
Operating pressure1 bar1 bar1 bar8 bar8 bar8 bar
Water flow30 l/h30 l/h30 l/h40 l/h40 l/h40 l/h

Automatic temperature compensation on all models.

Closed (membrane) amperometric cells – Other oxidants
SCL8/2SCL8/20SBR/20SCL9SCL11/200SCL11/2000SCL10SCT
MeasurementTotal chlorineTotal chlorineBromineHydrogen peroxidePeracetic acidPeracetic acidOzoneChlorites
Measuring range0 – 2 mg/l0 – 20 mg/l0 – 20 mg/l0 – 200 mg/l0 – 200 mg/l0 – 2,000 mg/l0 – 2 mg/l
0 – 20 mg/l
0 – 2 mg/l
Resolution0.0010.010.010.10.110.001
0.01
0.001
Operating pH4 – 124 – 126.5 – 9.51 – 111 – 91 – 92 – 115.5 – 9.5
Operating pressure1 bar1 bar0.5 bar1 bar1 bar1 bar1 bar1 bar

All models: 2 electrodes, selective membrane, automatic temperature compensation, operating temperature 1 – 40 °C, water flow 30 l/h.

Technical data

Technical data

The conductivity ranges depend on the probe chosen; chlorine and the other biocides are measured with the amperometric cell suited to the product.

Technical specifications

FeatureMTOWER 2CH
Measured parametersConductivity and pH, Redox or chlorine, with temperature
VersionsCD pH, CD Rh, CD CL
Contacting conductivity0 – 300 µS … 0 – 300 mS
Inductive conductivity0 – 3, 30 or 300 mS
pH0 – 14
Redox±999 mV
Chlorine and other biocidesAccording to the cell
Second channel controlON/OFF, PWM or proportional
Inputs6 levels, 2 water meters, flow, temperature, stand-by
Proportional outputs2 in the CD pH version: inhibitor and pH
Biocides and activators2 + 2
Biocide programmesTimer 1 and Timer 2, over 1, 2 or 4 weeks
AlarmsFlow, 2 levels, bleed-off timeout
Average power consumptionAbout 20 W
Antiscalant modesFeed and bleed, feed as a percentage of bleed-off, feed as a percentage of time, with water meter for a set time or with water meter at constant ppm
Temperature probes1, compensating all measurements
DisplayBacklit graphic LCD display
CommunicationOptional, one of USB, Ethernet, 4G, Wi-Fi and Modbus; 0-4/20 mA output optional
Power supply90 – 265 VAC, 50/60 Hz; 12 or 24 VDC on request
Protection ratingIP65 (NEMA 4X)
HousingABS
Dimensions325 × 255 × 118 mm
Ambient temperature−10 – 50 °C
Relative humidity0 – 95 %, non-condensing

The probes are not included and are ordered separately, according to the installation.

Complete systems

Complete systems with MTOWER

The controller is the core of the measuring and dosing system: the system page gives the composition, the installation diagram and the installation.

Cooling towers

Cooling towersCooling towers

The MTOWER is supplied pre-assembled on a panel or on a frame with probe holder, bleed-off valve, dosing pumps and water meters; the page also describes the programming of the antiscalant and biocides.

The system →
Summary

Main features

Conductivity-based bleed-off

When the conductivity set point is reached, the controller opens the drain valve, with opening delay, dead band and safety timer (timeout): beyond the set time the drain closes and the alarm is triggered.

Metered make-up and bleed-off

Inputs for pulse-output water meters: counting of make-up and drain volumes and control of the cycles of concentration.

Antiscalant proportional to make-up

The antiscalant is dosed in proportion to the make-up water (via a water meter or at constant ppm), together with the bleed-off or for a percentage of its duration.

Two alternating biocides

Management of two different biocides with daily or weekly scheduling, alternated to prevent microorganisms from adapting to a single product.

Pre-biocides (activators)

Two outputs dedicated to pre-biocides, dosed for the set time before the biocide: they generally act as activators of the subsequent dosing.

Pre-bleed

Before biocide dosing the controller opens the drain, on a timed basis or down to a lower conductivity value; with conductivity-based pre-bleed, the bleed-off timeout applies.

Drain lock-out

After biocide dosing the drain remains inhibited for the set time, so as to ensure the necessary contact time and prevent loss of chemical through the drain.

pH control

pH measurement and dosing of acid or base, for pH-controlled towers.

Measurement-based biocide (Redox or chlorine)

The oxidising biocide is dosed according to the Redox potential or the concentration in mg/l measured by an amperometric cell (chlorine, bromine, chlorine dioxide…).

Flow control

In the absence of flow in the probe holder (circulation pump stopped), dosing is suspended and the alarm is triggered.

Remote control

System remote control

The controllers support two-way remote access (read and write) through the web portal from a PC, tablet or smartphone: measurements can be viewed, set points, dosing and alarms changed, alarms received and logs downloaded. Alternatively, they can be integrated into your PLC via Modbus.

4G

Connection via the 4G network for installations without a local network, with alarm notification by SMS or e-mail.

Optional (one only)

Ethernet

Connection to the web portal via network cable: measurements, set points, dosing and alarms accessible from a PC, tablet or smartphone.

Optional (one only)

USB port

Download of the logged data to a USB memory stick, for archiving and analysis with a spreadsheet.

Optional (one only)
NIMBUS web portal for remote control of the systemsWeb portalPC, tablet and smartphone

Wi-Fi

Wireless connection to the web portal, with the same functions as the cable connection.

Optional (one only)

Modbus RTU

Integration into your PLC via serial port.

Optional (one only)

0-4/20 mA current loop output

Current signal proportional to the measured value, for remote monitoring or for controlling pumps and other instrumentation.

Optional

Optional communication: one only, chosen from 4G, Ethernet, USB, Wi-Fi and Modbus. The 0-4/20 mA current loop output is available as an option with all communication types.

The NIMBUS portal

A single account brings together all registered installations, each with its own devices: the web portal, free of charge and with no subscription, can be accessed from a PC, Mac, tablet or smartphone and allows every parameter to be both viewed and changed, with an encrypted connection and protected access.

The NIMBUS portal on monitor, laptop, tablet and smartphone

Overview

On a single screen: probe readings, chemical levels, pump activation thresholds and active alarms, with the status of installations and devices (normal, warning, alarm, standby, not connected).

Installation map

Installations appear on an interactive map with their status and open with a click; for each one, the local weather conditions and temperature are also shown.

History and charts

Archive of measurements and alarms, available for consultation at any time with charts and numerical reports exportable in Excel format.

Alarms and notifications

Alarm thresholds for readings, dosing, faulty probe and out-of-range readings, with notification by e-mail or SMS depending on the communication system; a warning is also issued when an installation remains disconnected beyond the set time.

Set points and dosing

Remote modification of the set points, of the dosing pump activation thresholds and of the corresponding hourly flow rate.

Inputs and outputs

Status of relays, pulse outputs, digital inputs and current outputs, with the name assigned to each connection.

Maintenance calendar

Tasks are scheduled by installation or by device and assigned to technicians; a reminder is sent by e-mail two days before the due date. Each task is shown as scheduled, due, overdue or completed.

Team and permissions

The main account has full access and creates the technicians’ accounts, each enabled only for the assigned installations and devices; the last login and activity of each technician are visible.

Reports and activity log

Reports on devices, tasks and technicians, downloadable in PDF or CSV with the customer’s logo; the log keeps the history of operations and disconnections.

Customisation

Logo, main colour and light or dark theme; the tiles on the main screen can be rearranged by dragging them. Two installations can be displayed side by side for comparison.

Guided registration

Each device is added through a guided procedure: the model is recognised automatically and associated with the installation, together with the technician to be contacted.

PLC integration

As an alternative to the portal, the Modbus RTU port allows integration into the plant supervision system.

NIMBUS portal: Real-time readings, counters and timers
Real-time readings, counters and timers
NIMBUS portal: Free chlorine and temperature trends
Free chlorine and temperature trends
NIMBUS portal: Set point and operating mode of each channel
Set point and operating mode of each channel
NIMBUS portal: Status of relays, pulses, inputs and mA outputs
Status of relays, pulses, inputs and mA outputs

Choosing the controller

Tell us the characteristics of the tower and the chemicals used: we will propose the most suitable model, probes and panel.

Contact

Tell us about your plant