Tank level
The level probe with 0-4/20 mA current loop output installed on each tank provides a signal proportional to the level: from its decrease the controller derives the product consumption and the remaining quantity.
The LDLOG mA controller detects the level of the chemicals in up to four tanks by means of sensors with 0-4/20 mA output, powered by the controller itself. From the change in level it calculates the daily, monthly and yearly consumption and the remaining quantity of each product, and raises an alarm when the set minimum level is reached.
LDLOG controllers acquire the signals of the devices installed on the plant and permanently store their totalised values, making it possible to document operation and to verify that the treatments are carried out correctly.
The level probe with 0-4/20 mA current loop output installed on each tank provides a signal proportional to the level: from its decrease the controller derives the product consumption and the remaining quantity.
The log can be viewed directly on the controller, with the daily, monthly and yearly totals of each input.
Quantity of product present in each of the 4 tanks.
Totalised consumption of each product.
Detects the level of chemical products in up to 4 tanks by means of sensors with 0-4/20 mA current loop output and totalises their daily, monthly and yearly consumption, as well as the remaining quantity; the concentration of the solution and a minimum level with end-of-product alarm can be set.
For each tank the product name, the litres corresponding to 4 mA and to 20 mA and the alarm threshold in litres are set; when the threshold is reached the alarm is shown on the display and sent by SMS or e-mail, if the communication module is installed.
| Feature | LDLOG mA |
|---|---|
| Inputs | 4 × 0-4/20 mA inputs for level sensors |
| Sensor power supply | 12 VDC from the controller terminals |
| Logged quantities | Level, consumption and remaining quantity of the products |
| Settings for each tank | Name, litres at 4 mA and at 20 mA, alarm threshold in litres |
| Settings | Percentage concentration of the solution |
| Totalisation | Daily, monthly, yearly |
| Logging interval | 15 minutes, 1 hour, 6 hours, 12 hours or 1 day |
| Log file format | CSV and encrypted EMC |
| Alarms | Minimum level and end of product, by SMS or e-mail |
| Alarm recipients | Up to 3 telephone numbers and 2 e-mail addresses |
| Communication | RS485, Modbus, USB, Ethernet, 4G |
| Data protection | Password-protected access |
| Display | RGB LCD display |
| Power supply | 85 – 264 VAC or 18 – 36 VAC, 50/60 Hz |
| Average power consumption | 25 W |
| Protection rating | IP65 |
| Ambient temperature | −10 – 50 °C |
| Relative humidity | 0 – 95 %, non-condensing |
For recording the level and consumption of the products in the tanks, the composition is defined on the characteristics of the plant: contact us.
The controllers support two-way remote access via Ethernet or the 4G network, with SMS or e-mail notifications when alarms are triggered, or can be integrated into the PLC via Modbus; the USB port also allows the recorded data to be downloaded to external memory for analysis with a spreadsheet. Access is password-protected, ensuring that the data cannot be altered from the controller to the point of delivery (web server or PLC).
Download of the logged data to a USB memory stick, for archiving and analysis with a spreadsheet.
Connection to the web portal via network cable: measurements, set points, dosing and alarms accessible from a PC, tablet or smartphone.
Connection via the 4G network for installations without a local network, with alarm notification by SMS or e-mail.
Integration into your PLC via serial port.
Tell us the quantities to be logged, the number of water meters, pumps and tanks and how the data are to be consulted: we will propose the most suitable controller and accessories.
Call or write to us: a technician will reply with a tailored proposal of controllers, pumps, probes and accessories.